> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/daylight-and-views-calculation-guide.md).

# Daylight and Views calculation guide

Guidance on calculation methods for daylight and views requirements in Green Star Buildings v1 and v1.1 and Green Star Fitouts.

{% hint style="warning" %}
**Release 2 - 18/11/2026**

* Update to relevant Green Star Buildings v1.1 credits in ‘Relevant rating tools’ table.

[#version-control](#version-control "mention")
{% endhint %}

<table data-search="false"><thead><tr><th width="730.25">Section</th></tr></thead><tbody><tr><td><a href="#introduction"><strong>Introduction</strong></a></td></tr><tr><td><a href="#version-control">Version control</a></td></tr><tr><td><a href="#daylight"><strong>Daylight</strong></a></td></tr><tr><td><a href="#overshadowing">Overshadowing</a></td></tr><tr><td><a href="#visual-light-transmittance-vlt">Visual light transmittance (VLT)</a></td></tr><tr><td><a href="#zone-of-compliance">Zone of compliance</a></td></tr><tr><td><a href="#compliant-areas">Compliant areas</a></td></tr><tr><td><a href="#views"><strong>Views</strong></a></td></tr><tr><td><a href="#line-of-sight">Line of sight</a></td></tr><tr><td><a href="#conditions">Conditions</a></td></tr><tr><td><a href="#compliant-areas-1">Compliant areas</a></td></tr><tr><td><a href="#references"><strong>References</strong></a></td></tr><tr><td><a href="#appendix"><strong>Appendix</strong></a></td></tr><tr><td><a href="#appendix-a-daylight-calculation-example">Appendix A: Daylight calculation example</a></td></tr><tr><td><a href="#appendix-b-views-calculation-example">Appendix B: Views calculation example</a></td></tr></tbody></table>

## <mark style="color:$primary;">Introduction</mark>

### Daylight and Views

This calculation guide outlines a methodology to demonstrate compliance with the requirements of Daylight and Views in Green Star Buildings and Green Star Fitouts projects.&#x20;

Using the methodologies provided, project teams can identify areas within the project with high levels of daylight and access to views for the relevant credits. Project teams are encouraged to use this calculation guide instead of daylight modelling for the Green Star Building credit: Light Quality - Minimum Expectation: Daylight.

*Relevant rating tools*\
The table below provides the relevant rating tools, credits, and requirements for which this calculation guide can be used.

<table><thead><tr><th>Rating tool</th><th>Credit</th><th>Performance level</th><th>Requirement</th></tr></thead><tbody><tr><td rowspan="2">Green Star Buildings v1</td><td>Light Quality</td><td>Minimum Expectation</td><td>Daylight</td></tr><tr><td>Connection to Nature</td><td>Credit Achievement &#x26; Exceptional Performance</td><td>Views</td></tr><tr><td rowspan="2">Green Star Buildings v1.1</td><td>Light Quality</td><td>Minimum Expectation</td><td>Daylight Strategy</td></tr><tr><td>Connection to Nature</td><td>Credit Achievement</td><td>Views</td></tr><tr><td>Green Star Fitouts</td><td>Light Quality</td><td>Credit Achievement</td><td>Daylight Access</td></tr></tbody></table>

***

## <mark style="color:$primary;">Daylight</mark>

The daylight hand calculation methodology determines the areas within buildings with high levels of daylight.

The following are required for this calculation:

* The project is not overshadowed
* The building glazing has a visual light transmittance (VLT) of at least 40%

This calculation methodology is based on Good Practice Guide 245: Desktop guide to daylighting - for architects (DETR, 1998).

Refer to Appendix A for a worked example.

### Overshadowing

Projects with external shading unaffected by a direct 25° line from the centre of the window are considered not overshadowed as illustrated in Figure 1 below. External shading can include buildings, cliffs, or any other solid structure, but does not include trees.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FUHj0riZVLNQshKS6O8Zo%2FFigure%201.png?alt=media&amp;token=52af39bb-4ba3-4142-a5ae-dda6aeb3c4b0" alt=""><figcaption></figcaption></figure>

*Figure 1: Angle of obstruction for external shading*

### Visual light transmittance (VLT)

The glazing must have a visible light transmittance of at least 40% with the assumption that there is no significant loss of light due to external obstructions, tinted glazing, or interior screening.

The following table provides typical VLT values for various types of glazing.

| Glazing type                                 | VLT range                                       |
| -------------------------------------------- | ----------------------------------------------- |
| Clear single glazing                         | \~70 - 90%                                      |
| Tinted single glazing (green)                | \~70%                                           |
| Tinted single glazing (grey)                 | \~20%                                           |
| Clear double glazing                         | \~70 - 80%                                      |
| Double glazing with a low emissivity coating | <p>\~40 - 70%<br>(but can be as low as 10%)</p> |

{% hint style="info" %}

* Project teams may use these values as a guide but must provide verification that the glazing used for the project has a VLT of 40% or greater.
* Dirt can provide a further 5% reduction in VLT with normal cleaning in an urban setting. Reductions in VLT due to dirt do not need to be included for the purposes of Green Star.
  {% endhint %}

### Zone of compliance

The zone of compliance is an area in the horizontal plane (as shown in Figure 2) is the area within the regularly occupied area where there is access to daylight and is calculated as follows:.

$$\text{Zone of compliance} = d \times w$$

Where:

* $d = depth = 2h$
* $w = width = \text{width of the glazing}$

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2F9ukiUrazqFw61tm66U6V%2FFigure%202.jpg?alt=media&amp;token=d4c69fc6-250d-40cf-b0b7-1bca49267e4f" alt=""><figcaption></figcaption></figure>

*Figure 2: Dimensions for calculating the zone of compliance*

{% hint style="info" %}

* When plotting the depth of the zone of compliance, the zone cannot be drawn past permanent solid or glazed partitions
* Any column or mullion ˂ 0.5 m in width can be disregarded, and the glazing width considered to be continuous
* Desktop / tabletop level is set at 700 mm AFFL for all Green Star rating tools
  {% endhint %}

### Defining ‘h’

The value of ‘h’ is defined as the height of the window head, which can be calculated based on how occupants will use the space.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FVS5F7wdCxIwcVAeuH0Ie%2FFigure%203.jpg?alt=media&amp;token=8fd46143-e155-48a3-885b-a0cc3de73bd9" alt=""><figcaption></figcaption></figure>

*Figure 3: How to determine the dimension of ‘h’*

For spaces, where a desk is provided such as office settings, ‘h’ is calculated as:

* Height above the desktop / tabletop level of 700 mm (Figure 3 Diagram A)
* Height above the bottom sill of the glazing, where the bottom sill is above desktop / tabletop level of 700mm (Figure 3 Diagram B)

For spaces, where there is no desk provided such as living rooms or bedrooms in residential apartments, ‘h’ is calculated as:

* Height of the window as installed.

### Compliant areas

#### Regularly occupied area

The percentage of compliant regularly occupied area can be calculated as follows:

$$\text{Zone of compliance } (m^2) = h \times 2 \times w$$

$$\text{Regularly occupied area } (m^2) = A\_{\text{regularly occupied}}$$

$$\text{Compliant area } (%) = \frac{\text{Zone of compliance}}{A\_{\text{regularly occupied}}} \times 100$$

*Refer to the Submission Guidelines to identify the regularly occupied areas for your project.*

## <mark style="color:$primary;">Views</mark>

The views hand calculation methodology determines the areas within buildings with access to views.

Refer to Appendix B for a worked example.

### Line of sight

The line of sight to the view is used to determine the area of compliance, or a complying workstation. A primary space or workstation that has direct line of sight within 8 meters of a qualifying view will meet the requirements. A qualifying view can be a window, atrium, or high-quality internal view, depending on the rating tool. When calculating the distance to the view, the thickness of external walls must be considered.

The line of sight is determined by drawing a line from the qualifying view to the eye of the building occupant. The occupant must be seated or standing at a work setting or mobile within a retail, industrial, or other space. A line at 45° can be used for corners of high-quality views.

### Conditions

#### All types of views

For calculations with any type of views, the following conditions apply:

* Permanent partitions must be accounted for
  * If the view is obscured by a permanent partition, the area behind this partition must be excluded from the area of compliance
  * If the view is obscured by a temporary partition, which can be removed during occupied hours, then this area can be counted towards the area of compliance
  * Workstations and partitions which are less than 1.5m tall can be excluded
* Internal and external columns can be excluded
* Internal, fully glazed partitions can be excluded

#### External Views

For calculations with external views, the following conditions apply:

* The view must extend from the perimeter of the building and be unblocked by any permanent solid structure (i.e. there must not be another building within 8 m)
* The area behind any solid portion of the perimeter of the external wall must be excluded
* Glazing below 720 mm or above 2,400 mm cannot contribute to external views
  * There is no minimum dimension for glazing prescribed within this guide, however project teams are encouraged to consider the intent of the credit in the context of their building to establish whether the glazing provided within their project will have the capacity to provide views to occupants. For example, it is unlikely that a 400 mm high window at 2,000 mm above floor levels would have the capacity to provide high quality views to occupants.

See Figures 4 and 5 for illustrations.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2F3m5ajysuoCVFopUjiYhM%2Ffigure%204.png?alt=media&amp;token=258de135-f602-4ba5-ab6f-719555f7523e" alt=""><figcaption></figcaption></figure>

*Figure 4: External views*

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FQZJkP3ZKWFpEK7ZiIPSN%2Ffigure%206.jpg?alt=media&amp;token=77cf2456-3414-4338-b9cf-e8f13d7420dd" alt=""><figcaption></figcaption></figure>

*Figure 5: Vision glazing*

### Daylit atrium views

A combination of external and atrium views may be used to demonstrate compliance as a ‘view’.

For calculations with daylit atrium views, the following conditions apply:

* The atrium must be at least 8 m wide and 8 m deep (depth across the atrium, this is not referring to the height of the atrium) at any point where the line of sight is demonstrated
* If the space opens directly onto the atrium, calculations must be made from the vision glazing or from the internal perimeter of the atrium if no internal glazing is installed
* The area behind any solid portion of the atrium perimeter must be excluded from the calculations
* A minimum daylight factor of 3% must be achieved for 90% of the atrium area on the lowest level for which compliance is claimed
* A combination of external and atrium views may be used to demonstrate compliance

See Figure 6 for illustrations.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FpReFtyTCXZPzU0NDdcSh%2FFigure%206.png?alt=media&amp;token=153a2a99-9e4f-42f8-8ecf-45f1dd9cbfb6" alt=""><figcaption></figcaption></figure>

*Figure 6: Daylight atrium views*

### High-quality internal views

A combination of multiple internal views may be used to demonstrate compliance as a ‘view’

See Figure 7 for illustrations.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FkPNNkZX4IuYsjjtWTioD%2FFigure%207.png?alt=media&amp;token=ea1647f1-199b-40da-b7fe-70c275ca0fe1" alt=""><figcaption></figcaption></figure>

*Figure 7: High quality internal views*

### Compliant areas

#### Regularly occupied area

The percentage of area within 8 m of views can be calculated as follows:

$$
\begin{aligned}
\text{Area with views} = A\_{\text{views}}\ (m^2) &= (\text{width of compliant external view} \times 8m + \text{area within } 45^{o}) \\
&+ (\text{width of compliant atrium view} \times 8m + \text{area within } 45^{o}) \\
&+ (\text{width of compliant internal view} \times 8m + \text{area within } 45^{o})
\end{aligned}
$$

$$\text{Regularly occupied area} = A\_{\text{regularly occupied}}\ (m^2)$$

$$\text{Compliant area } (%) = \frac{A\_{\text{views}}}{A\_{\text{regularly occupied}}} \times 100$$

*Refer to the Submission Guidelines to identify the regularly occupied areas for your project.*

#### Work settings

The percentage of work settings within 8 m of views can be calculated as follows:

$$\text{Work settings with views} = W\_{\text{views}} = (\text{work settings within 8 m of an external view}) + (\text{work settings within 8 m of an atrium view})$$

$$\text{Total number of work settings} = W\_{\text{total}}$$

$$\text{Compliant work settings } (%) = \frac{W\_{\text{views}}}{W\_{\text{Total}}} \times 100$$

## <mark style="color:$primary;">References</mark>

The Department of Environment, Transport and the Regions (DETR), 1998, Good Practice Guide 245 ‘Desktop guide to daylighting – for Architects’, <http://www.cibse.org/getmedia/19b5aa2a-309f-4e8d-8e72-07b5c4c4cf72/GPG245-Desktop-Guide-to-Daylighting-for-Architects.pdf>

## <mark style="color:$primary;">Appendix</mark>

### Appendix A: Daylight calculation example

The plans in this appendix are provided as an example and illustration of the daylight hand calculation methodology but is not an example of meeting the requirements.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FJUTFiBER9qaIKqjgsuCt%2Fappendix%20a%201.png?alt=media&amp;token=ffc41eb8-296f-413d-a335-6a807a50352b" alt=""><figcaption></figcaption></figure>

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FNRULFfYQqsuAp8EFjqWO%2Fappendix%20a%202.png?alt=media&amp;token=f7a1adc3-d7e5-4f9e-8bb6-70722c35873a" alt=""><figcaption></figcaption></figure>

### Appendix B: Views calculation example

The plans in this appendix are provided as an example and illustration of the daylight hand calculation methodology but is not an example of meeting the requirements.

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2FEO5GKq8WQIzTeWl4qvX0%2Fappendix%20b%201.png?alt=media&amp;token=4578044e-fc49-46ea-8477-36cfa8845e0a" alt=""><figcaption></figcaption></figure>

### Version control

<table><thead><tr><th width="115.25">Version</th><th width="133.75">Date</th><th>Description</th></tr></thead><tbody><tr><td>3</td><td>18/11/2026</td><td>Update to relevant Green Star Buildings v1.1 credits in ‘Relevant rating tools’ table.</td></tr><tr><td>2</td><td>27/10/2026</td><td>Updated ‘relevant rating tools’ table to include reference to relevant Green Star Buildings v1.1 and Green Star Fitouts credits.</td></tr><tr><td>1</td><td>07/03/2022</td><td>Initial release for Green Star Buildings.<br>(Adapted from Green Star – Design &#x26; As Built)</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/daylight-and-views-calculation-guide.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.