> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/categories-and-credits/positive/22-or-energy-use.md).

# 22 | Energy Use

Points: 6

## <mark style="color:$primary;">Outcome</mark>

The building has low energy consumption.

### <mark style="color:$primary;">Strategy</mark>

<table data-search="false"><thead><tr><th>Registration</th><th width="199">Star rating</th><th>Requirement</th></tr></thead><tbody><tr><td rowspan="3"><strong>Registering from 2020 onwards</strong></td><td><strong>4 Star</strong></td><td rowspan="2">Meets the <em>Minimum Expectation</em></td></tr><tr><td><strong>5 Star</strong></td></tr><tr><td><strong>6 Star</strong></td><td>Meets the <em>Credit Achievement</em></td></tr><tr><td rowspan="3"><strong>Registering from 2023 onwards</strong></td><td><strong>4 Star</strong></td><td>Meets the <em>Minimum Expectation</em></td></tr><tr><td><strong>5 Star</strong></td><td rowspan="2">Meets the <em>Credit Achievement</em></td></tr><tr><td><strong>6 Star</strong></td></tr><tr><td><strong>Certified after 1st January 2030, regardless of registration date</strong></td><td><strong>All certifications</strong></td><td>Meets the <em>Credit Achievement</em></td></tr></tbody></table>

### <mark style="color:$primary;">Pathways</mark>

There are three pathways available for this credit. Projects can choose from one of the following based on their building type:

* Reference building pathway
* NABERS Commitment Agreement pathway (available to Class 3 Hotels, Class 5 Offices and Class 6 Shopping Centre)
* Residential pathway (available to Class 2 Residential Buildings only)

Refer below for pathway criteria.

Mixed use projects may use a combination of these pathways to demonstrate compliance, however they must meet the criteria for all targeted pathways to be eligible for points.

## <mark style="color:$primary;">Criteria</mark>

#### **Energy Use - Reference building pathway A**

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-22a.0.1-reducing-energy-use](#id-22a.0.1-reducing-energy-use "mention"): The building's energy use is at least 10% less than a reference building.

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

**– Climate Positive Pathway –**

In conjunction with the *Minimum Expectation:*

* [#id-22a.1.1-reducing-energy-use](#id-22a.1.1-reducing-energy-use "mention"): The building's energy use is at least 20% less than a reference building.

<mark style="color:$success;">**Exceptional Performance — 3 points**</mark>

In conjunction with the *Credit Achievement:*

* [#id-22a.2.1-reducing-energy-use](#id-22a.2.1-reducing-energy-use "mention"): The building's energy use is at least 30% less than a reference building.

#### **Energy Use - NABERS commitment agreement pathway B**

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-22b.0.1-nabers-commitment-agreement](#id-22b.0.1-nabers-commitment-agreement "mention"): The building's energy use is modelled to perform at a specified minimum NABERS star rating (by building class).

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

**– Climate Positive Pathway –**

In conjunction with the *Minimum Expectation:*

* [#id-22b.1.1-nabers-commitment-agreement](#id-22b.1.1-nabers-commitment-agreement "mention"): The building's energy use is modelled to perform at a specified NABERS star rating (by building class).

<mark style="color:$success;">**Exceptional Performance — 3 points**</mark>

In conjunction with the *Credit Achievement:*

* [#id-22b.2.1-nabers-commitment-agreement](#id-22b.2.1-nabers-commitment-agreement "mention"): The building's energy use is modelled to perform at a specified NABERS star rating (by building class).

#### **Energy Use - Residential pathway C**

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-22c.0.1-nathers-ratings](#id-22c.0.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 6.5 stars and meets at least NatHERS 5 stars for each sole-occupancy unit.
* [#id-22c.0.2-domestic-hot-water](#id-22c.0.2-domestic-hot-water "mention"): The building addresses domestic hot water demand.
* [#id-22c.0.3-pool-covers](#id-22c.0.3-pool-covers "mention"): Where a pool exists, it has a pool cover.
* [#id-22c.0.4-energy-efficiency-requirements](#id-22c.0.4-energy-efficiency-requirements "mention"): The building complies with NCC Parts J3 to J8.

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

**– Climate Positive Pathway –**

In conjunction with the *Minimum Expectation:*

* [#id-22c.1.1-nathers-ratings](#id-22c.1.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 7 Stars and meets at least NatHERS 5.5 Stars for each sole-occupancy unit.
* [#id-22c.1.2-building-services](#id-22c.1.2-building-services "mention"): The building addresses four out of nine building services energy uses.

<mark style="color:$success;">**Exceptional Performance — 3 points**</mark>

In conjunction with the *Credit Achievement:*

* [#id-22c.2.1-nathers-ratings](#id-22c.2.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 8 Stars and meets at least NatHERS 6 Stars for each sole-occupancy unit.
* [#id-22c.2.2-building-services](#id-22c.2.2-building-services "mention"): The building addresses six out of nine building services energy uses.

***

## <mark style="color:$primary;">Additional information</mark>

#### Stage implementation

Strategy | **Brief** | **Concept** | **Design** | **Tender** | Construction | Handover | Use

#### Synergies with other credits

* Verification and Handover
* Life Cycle Impacts
* Climate Change Resilience
* Operations Resilience
* Grid Resilience

#### Sustainable Development Goals

* **Goal 7:** Affordable and Clean Energy
* **Goal 13:** Climate Action

#### Relevant reporting initiatives

* GRESB
* Task Force on Climate-related Financial Disclosures **(TCFD)**

#### Climate Positive Pathway – Leadership point

This credit is part of the Climate Positive Pathway in Green Star Buildings. When the pathway is achieved, a Leadership Challenge point is awarded to the building for a total of 15 points for this path.

***

## <mark style="color:$primary;">Requirements</mark>

{% tabs %}
{% tab title="A: Reference building pathway " %}

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with the following criteria:

* Reducing Energy Use

#### 22A.0.1 Reducing Energy Use

The building uses 10% less energy compared to a reference building.

Energy use is measured as MJ/year.

#### *Modelling requirements*

This credit defines the reference building as a building modelled to Section J requirements of the National Construction Code 2019 or later. If the building's approval is subject to a later code, the building must use that version.

The results from the energy model must include all energy consumed by base building systems. Consumption from commercial tenant systems such as plug loads, domestic appliances, and manufacturing or process loads are excluded from the calculation. Refer to the Energy Use calculation guide for more information.

It must be demonstrated that for the Proposed Project each of the following building system complies with the relevant DTS requirements of NCC Section J:

* The performance of wall-glazing constructions and display windows (J1.5) must comply with the total system R value, total system U value and system SHGC requirements, inclusive of thermal bridging effects
* The performance of fan systems (J5.4), pump systems (J5.7), refrigerant chillers (J5.10) and heat rejection equipment (J5.12) must comply with the applicable efficiency requirements
* The performance of artificial lighting systems (J6.2) must comply with the overall lighting efficiency requirements

#### *On-site renewables*

The *Minimum Expectation* addresses the energy use from the building's systems and the effect of the building's façade. Therefore, on-site renewable energy generation systems connected behind the meter **cannot** be used to calculate reductions in energy use of the building for the Minimum Expectation.

On-site renewable energy generation systems connected behind the meter can be used to calculate reductions in energy use of the building for *Credit Achievement* and *Exceptional Performance*, however electricity exported to the grid cannot be counted.

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with the *Minimum Expectation*, the project must comply with the following criteria:

* Reducing Energy Use

#### 22A.1.1 Reducing Energy Use

The building uses 20% less energy compared to a reference building.

See *Minimum Expectation* for further information on modelling requirements and on-site renewables.

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with the Credit Achievement, the project must comply with the following criteria:

* Reducing Energy Use

#### 22A.2.1 Reducing Energy Use

The building uses 30% less energy compared to a reference building.

See *Minimum Expectation* for further information on modelling requirements and on-site renewables.

***

## <mark style="color:$primary;">Submission content</mark>

#### Submissions for this credit must contain:

* **Submission for**m through Green Star Online
* **Energy Use calculator** (if pathway used)
* **Evidence** to support claims made in the submission

#### Recommended evidence:

* Energy modelling report
* Extracts from specifications
* Extracts from commissioning reports
* As built drawings of the façade
* Evidence of renewable energy generation on-site (e.g., contracts, as built drawings)
* Schedule identifying all on-site storage systems installed in the building

Alternate documentation can also be used by project teams to demonstrate compliance.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

The key requirement is that evidence is provided to support each claim made within the Submission form.

***

## <mark style="color:$primary;">Guidance</mark>

**Tenanted and cold shell spaces**\
For tenanted and cold shell spaces, modelling of energy use can be based on the provision of base building systems to the tenancy and an assumption that minimum NCC requirements will be met. Modelled energy use for tenanted spaces to be based on the most energy-intensive allowed by base building system requirements outlined in leasing agreement/Tenancy Fitout Guide and NCC DTS provisions. For Cold Shell spaces where there is no provision for connection to base building systems, the project team are to model standalone (supplementary) tenant systems based on the most energy-intensive allowed by requirements outlined in leasing agreement documentation.

Tenancy Fitout Guidance to identify (including but not limited to) the tenant's allowable internal loads (tenant lighting and equipment power allowances), HVAC system zoning requirements (internal and perimeter zones with independent temperature control), HVAC system type & design capacities, and outdoor air rates. The design team must demonstrate the design provision (e.g., space allowance) that has been made for accommodating the system type modelled.

**Calculation Guide**\
[Energy Use calculation guide](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/energy-use-calculation-guide.md)

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* Australian Building Codes Board (ABCB), National Construction Code Volume One, Australian Building Codes Board, Australia (2019 or later)
* Green Star Buildings Energy Use calculator
* Energy Use calculation guide
* GBCA's Climate positive buildings and our net zero ambitions
* [GBCA's Climate Positive Roadmap](https://gbca-web.s3.amazonaws.com/media/documents/carbon-positive-roadmap-discussion-paper-rev-a.pdf)
* World GBC's [Net Zero Carbon Buildings Commitments](https://worldgbc.org/thecommitment/)
  {% endtab %}

{% tab title="B: NABERS commitment agreement pathway " %}

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with the following criteria:

* NABERS Commitment Agreement

#### 22B.0.1 NABERS Commitment Agreement

Project teams must demonstrate that the project is subject to a NABERS Energy Commitment Agreement. This pathway recognises NABERS Energy Commitment Agreements where a NABERS-recognised Independent Design Reviewer has completed a full peer review of the base building design and associated energy performance simulation assessment.

The building has a NABERS Energy Commitment Agreement to predict the project's energy and greenhouse gas performance achieving the rating for its building class as outlined in the below table.

| Building class           | NABERS energy rating commitment agreement |
| ------------------------ | ----------------------------------------- |
| Class 3 Hotels           | 4.5 Stars                                 |
| Class 5 Offices          | 5.5 Stars                                 |
| Class 6 Shopping Centres | 4.5 Stars with 20% modelling margin\*     |

\* The modelling margin is inclusive of the modelling margin for the NABERS Commitment Agreement, not in addition.

The scope of the NABERS Energy rating is base building only.

The energy performance results shall use reference scenario modelling inputs, not off-axis scenario inputs. Refer to the NABERS Energy Guide to Building Energy Estimation for more information.

This pathway may be used to assess the relevant class component building GFA. Another pathway must be selected to model the remainder of the building if it does not fall under any of the above Classes.

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with the *Minimum Expectation*, the project must comply with the following criteria:

* NABERS Commitment Agreement

#### 22B.1.1 NABERS Commitment Agreement

The building has a NABERS Energy Commitment Agreement to predict the project's energy and greenhouse gas performance achieving the rating for its building class as outlined in the below table.

| Building class           | NABERS commitment agreement outcomes    |
| ------------------------ | --------------------------------------- |
| Class 3 Hotels           | 4.5 Stars with a 20% modelling margin\* |
| Class 5 Offices          | 5.5 Stars with 25% modelling margin\*   |
| Class 6 Shopping Centres | 5 Stars                                 |

See *Minimum Expectation* for further information.

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with the *Credit Achievement*, the project must comply with the following criteria:

* NABERS Commitment Agreement

#### 22B.2.1 NABERS Commitment Agreement

The building has a NABERS Energy Commitment Agreement to predict the project's energy and greenhouse gas performance achieving the rating for its building class as outlined in the below table.

| Building class           | NABERS commitment agreement outcomes |
| ------------------------ | ------------------------------------ |
| Class 3 Hotels           | 5 Stars                              |
| Class 5 Offices          | 6 Stars                              |
| Class 6 Shopping Centres | 5.5 Stars                            |

See *Minimum Expectation* for further information.

***

## <mark style="color:$primary;">Submission content</mark>

#### Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence:

* Signed copy of the NABERS Energy Commitment Agreement
* Independent Design Review report outlining the results to the Energy Efficiency Review of the project
* GreenPower or other off-site renewable contracts

Alternate documentation can also be used by project teams to demonstrate compliance.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

The key requirement is that evidence is provided to support each claim made within the Submission form.

***

## <mark style="color:$primary;">Guidance</mark>

**Calculation Guide**\
[Energy Use calculation guide](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/energy-use-calculation-guide.md)

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* Australian Building Codes Board (ABCB) 2019, National Construction Code 2019 Volume One, Australian Building Codes Board, Australia
* GBCA's *Climate positive buildings and our net zero ambitions*
* GBCA's [Climate Positive Roadmap](https://gbca-web.s3.amazonaws.com/media/documents/carbon-positive-roadmap-discussion-paper-rev-a.pdf)
* World GBC's [Net Zero Carbon Buildings Commitments](https://worldgbc.org/thecommitment/)
* NABERS Commitment Agreements: Handbook for Estimating NABERS Ratings
  {% endtab %}

{% tab title="C: Residential pathway " %}
This pathway is available to Class 2 Buildings (or parts of buildings) only.

Where reference is made to Section J requirements of the National Construction Code it refers to the 2019 version. If the building's approval is subject to a later code, the building must use that version in this credit.

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all** the following criteria:

* NatHERS ratings
* Domestic Hot Water Demand
* Pool Covers
* Energy Efficiency Requirements

#### 22C.0.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building must achieve a NatHERS energy rating of at least 6.5 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit must achieve a NatHERS energy rating of at least 5 stars.

#### 22C.0.2 Domestic Hot Water

The relevant fixtures and water-using appliances installed within the project's scope must, at a minimum, meet the following WELS ratings to reduce the Domestic Hot Water energy use:

| Fixture type            | WELS rating                                  |
| ----------------------- | -------------------------------------------- |
| Showers                 | 3 Stars with a maximum flow rate of 9L/min   |
| Taps – kitchen          | 4 Stars with a maximum flow rate of 7.5L/min |
| Taps – hand wash basins | 5 Stars with a maximum flow rate of 6L/min   |

#### 22C.0.3 Pool Covers

Where heated pools are installed, they must have a pool cover with a minimum R-value of 0.075 for external pools or 0.05 for internal pools.

#### 22C.0.4 Energy Efficiency Requirements

All buildings, irrespective of location, are required to comply with NCC Parts J3 to J8. No state amendments or exclusions are allowed.

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with the *Minimum Expectation*, the project must comply with **all** the following criteria:

* NatHERS ratings
* Building Services

#### 22C.1.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building must achieve a NatHERS energy rating of at least 7 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit must achieve a NatHERS energy rating of at least 5.5 stars.

#### 22C.1.2 Building Services

Project teams must comply with one of the following:

* Building Services Requirements
* BASIX Building Services

#### *Building Services Requirements*

The project team must address at least four out the nine building services requirements.

<table data-search="false"><thead><tr><th width="184">Building service</th><th>Requirements</th></tr></thead><tbody><tr><td><strong>Domestic Hot Water</strong></td><td>All showers have a minimum WELS rating of 4 Stars with a maximum flow rate of 7.5L/min.<br><br>All hot water pipes outside of the sole-occupancy units are insulated with a minimum R-value of 2.0. All hot water pipes inside sole-occupancy units are insulated with a minimum R-value of 0.5.</td></tr><tr><td><strong>Domestic Hot Water Generation</strong></td><td><p>The building provides one or a combination of:</p><ul><li>A solar thermal heating system is provided, or heat is recovered from another process (for example chiller heat recovery) or a combination of both, which contributes at least 30% of the annual thermal energy requirement for water heating</li><li>The primary non-renewable heat source for domestic hot water is an electric heat pump with a minimum COP of 3.0 at 20°C ambient and 65°C leaving temperature</li></ul></td></tr><tr><td><strong>Heating and Cooling of Sole Occupancy Units</strong></td><td><p>The building provides efficient outcomes for heating and cooling.<br><br>For cooling, the building provides one or a combination of the following:</p><ul><li>DX Split Systems: a minimum 3.5 Star SEER Cooling Star Rating (mixed zone)</li><li>Centralised Condenser Water System: water cooled packaged units with a minimum cooling EER of 3.5 AND the condenser water system exceeds energy efficiency requirements of NCC Section J5.7 and J5.12 by at least 10%</li><li>Central Chilled Water System: the chiller and chilled water systems exceed energy efficiency requirements of NCC Section J5.7 and J5.10 by at least 10%. If a cooling tower is installed, then this must exceed energy efficiency requirements of NCC Section J5.12 by at least 10%</li><li>No refrigerant-based cooling is provided</li></ul><p><br>For heating, the building provides one or a combination of the following:</p><ul><li>DX Split Systems: 3 Star SEER Heating Star Rating (mixed zone)</li><li>Centralised Condenser Water System: water cooled package units with a minimum heating EER of 4.0 AND the condenser water pump system exceeds energy efficiency requirements of Section J5.7 by at least 10%</li><li>Central Heating Hot Water System: the heat source is a heat pump with a with a minimum COP of 4.0 at 10°C ambient outside air temperature AND the heating hot water pumping system exceeds energy efficiency requirements of NCC Section J5.7 by at least 10%</li><li>Electric heater: 10% better than Section J5.9 requirements</li><li>No electric or combustion-based heating is provided</li></ul></td></tr><tr><td><strong>Clothes Drying</strong></td><td><p>95% of dwellings contain both:</p><ul><li>External clothes drying facility</li><li>Either no available space for a clothes dryer OR a heat pump clothes dryer with auto-sensing feature and vented to the outside</li></ul></td></tr><tr><td><strong>Ceiling Fans</strong></td><td>Ceiling fans are installed in all bedrooms and living rooms and comply with the requirements of NCC Section J0.3.</td></tr><tr><td><strong>Car Parking</strong></td><td><p>The building complies with one of the following:</p><ul><li>No undercover car parking is provided</li><li>75% of undercover car parking is naturally ventilated with no mechanical ventilation systems</li><li>Undercover car parking is limited to 1 car space per 5 sole-occupancy units<br>Where undercover parking is provided, lighting control linked to occupancy sensors must be installed, with minimum lighting levels provided for safety and security purposes.</li></ul></td></tr><tr><td><strong>Vertical Transportation</strong></td><td><p>The energy associated with lift machinery or other vertical transportation complies with all the following:</p><ul><li>The minimum lift energy efficiency is class A or B in accordance with ISO 25745-2</li><li>The lift idle and standby energy performance level is 1 in accordance with ISO 25745-2.</li><li>The minimum escalator energy performance is class A+ to A+++ in accordance with ISO 25745-3.<br>Requirements must be met for all relevant systems where present.</li></ul></td></tr><tr><td><strong>Lift Lobbies and Corridors</strong></td><td><p>Lift lobbies and hallways (excluding main entrance lobby to the building) are either:</p><ul><li>Naturally ventilated</li><li>Supply / exhaust air only with no heating or cooling (A/C or tempered)</li></ul></td></tr><tr><td><strong>On-site solar PV</strong></td><td>A minimum of 500kWh of annual electricity generation per dwelling is provided by an on-site solar PV system.</td></tr></tbody></table>

#### *BASIX*

Projects in NSW may demonstrate compliance for Building Services by achieving a BASIX Energy score 20% better than minimum compliance (rounded down to nearest integer).

The BASIX Energy score for Green Star credit purposes must be calculated using the following assumptions:

* Fridges to be entered as "not specified"

All other inputs are to be as per the BASIX assessment used for the Occupancy Certificate.

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with the Credit Achievement, the project must comply with **both** the following criteria:

* NatHERS ratings
* Building Services

#### 22C.2.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building must achieve a NatHERS energy rating of at least 8 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit must achieve a NatHERS energy rating of at least 6 stars.

#### 22C.2.2 Building Services

Project teams must comply with **one** of the following:

* Building Services Requirements
* BASIX Building Services

#### *Building Services Requirements*

The project team must address at least **six** out the nine building services requirements.

See Credit Achievement requirements for further information.

#### *BASIX*

Projects in NSW may demonstrate compliance for Building Services by achieving a BASIX Energy score 30% better than minimum compliance (rounded down to nearest integer).

The BASIX Energy score for Green Star credit purposes must be calculated using the following assumptions:

* Fridges to be entered as "not specified"

All other inputs are to be as per the BASIX assessment used for the Occupancy Certificate.

***

## <mark style="color:$primary;">Submission content</mark>

#### Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence:

* **NatHERS certification summary report** issued to the Building Certifier at time of Building Approval
* **As built documentation** showing compliance with the nominated building services requirements
* **BASIX Certificate**
* **BASIX Report** showing BASIX score without fridges (unless BASIX certificate already excludes these)

**Domestic Hot Water**

* **Schedule** demonstrating that all fittings achieve the required WELS rating

**Domestic Hot Water Generation**

* **Manufacturers' documentation** showing the gross thermal efficiency or coefficient of performance (COP) of the heating appliance.
* **Documentation** demonstrating that the solar heating system and/or heat recovery systems contributes at least 30% of the annual requirement.

**Heating and Cooling**

* **Schedule** identifying all air-conditioners installed in the building, their capacities and the manufacturer and model of each.
* **Manufacturers' documentation** or information from [www.energyrating.gov.au](http://www.energyrating.gov.au) confirming the energy star rating applicable to each air-conditioner or heater.

**Clothes Drying**

* **As built drawings** demonstrating provision of external drying facilities
* **Documentation** demonstrating the specification of the dryer installed

**Ceiling Fans**

* **As built drawing**s demonstrating that ceiling fans have been provided to all living rooms and bedrooms
* **Schedule** identifying all ceiling fans installed the in the building, and the manufacturer and model of each

**Car Parking**

* **As built drawings** demonstrating that no undercover parking is provided
* **Extract from the Commissioning Report** demonstrating enclosed car parking areas are naturally ventilated.
* **Documentation** showing that no more than 1 car space per 5 sole-occupancy units is provided
* **Documentation** showing location and CO sensors and Variable Speed Drive on all fans

**Vertical Transportation**

* **Schedule** identifying all vertical transportation systems installed in the building, and the manufacturer and model of each.
* **Documentation** showing the energy efficiency class and idle and standby energy performance level in accordance with ISO 25745-2 for all installed lifts (where applicable).
* **Documentation** showing the energy performance class in accordance with ISO 25745-3 for all installed escalators (where applicable).
* **Extract(s) from the commissioning report** demonstrating (through supporting evidence) that the vertical transportation systems have been commissioned and operate as intended by the design.

**Lift lobbies and corridors**

* **As built drawings** for each naturally ventilated space showing openings, with dimensions clearly indicated, and ventilation inlets and outlets.
* **Documentation showing** supply / exhaust air only with no heating or cooling

**Pool Cover**

* **Documentation** showing the specification and R value of the pool cover installed

**Solar PV**

* **Installation** drawings and specifications
* **Calculations** demonstrating annual energy generation

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Guidance</mark>

**Passivhaus Certification**\
Projects which have achieved a Passivhaus Certification are considered to have met all requirements in the Minimum Expectation, Credit Achievement and Exceptional Performance. Project teams must submit a Technical Question outlining how they have also met similar outcomes for the Building Services requirement.

**NatHERS**\
The NatHERS modelling must be carried out by an accredited assessor and the NatHERS Universal Certificate produced by an NatHERS accredited assessor.

* Projects located in NSW must meet the maximum heating and cooling loads as per the BASIX® Thermal Comfort Protocol
* Projects located in all other states must meet the heating and cooling loads applicable as per the ABCB Standard - NatHERS heating and cooling loads limits.
* NatHERS rating is based on thermal loads only, and excludes any Star rating benefit provided by ceiling fans, water tanks or other ESD provisions allowable in some States

**ABCB Standard - NatHERS heating and cooling loads limits**\
For further information about the heating and cooling load limits, please refer to the ABCB web page <https://www.abcb.gov.au/resource/standard/nathers-heating-and-cooling-load-limits>

**Electric vehicle charging**\
Project teams may use to the Movement and Place credit for requirements for electric vehicle charging.

**On-site solar PV calculation methodology**\
Where on-site photovoltaic (PV) systems are provided, the associated power and energy generation must be assessed based on the methodology outlined in the Green Star Buildings – Energy Use guide – section 7.1 Photovoltaic Systems.

As per the methodology, the source of the annual solar irradiation value used must be stated and must account the orientation, inclination, and location of the panels. The energy generation must consider the effects of any overshadowing, either from buildings or other panels and account for system losses.

The system losses include multiple factors such Inverter losses, temperature losses, DC cables losses & AC cables losses, losses at weak radiation, losses due to soiling and the derating of PV efficiency over time. For Green Star purposes, the combined system losses used in the calculation cannot be less than 20%.

**On-site solar PV cap**\
On-site PV system capacity can be capped at 99.5kW.

**Calculation Guide**\
[Energy Use calculation guide](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/energy-use-calculation-guide.md)

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* Australian Building Codes Board (ABCB), National Construction Code 2019 Volume One, Australian Building Codes Board, Australia
* GBCA's *Climate positive buildings and our net zero ambitions*
* GBCA's [Climate Positive Roadmap](https://gbca-web.s3.amazonaws.com/media/documents/carbon-positive-roadmap-discussion-paper-rev-a.pdf)
* [World GBC's Net Zero Carbon Buildings Commitments](https://worldgbc.org/thecommitment/)
  {% endtab %}
  {% endtabs %}

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

#### <mark style="color:$primary;">**Green Star Buildings - Apartments Pathway**</mark>

{% hint style="info" %}
Please note that if this pathway is chosen, all credits that have an Apartments pathway must be followed. For more detail on what this includes, please navigate to<mark style="color:$success;">:</mark> [Apartments Pathway](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/categories-and-credits/apartments-pathway.md)
{% endhint %}

<mark style="color:$danger;">**Residential Pathway**</mark>

**Minimum Expectation — Nil:**

* Domestic hot water fixture efficiency (WELS ratings).
* Pool covers (where a pool exists).
* Compliance with NCC Parts J3–J8.

**Credit Achievement (Mandatory) — 3 points:** In conjunction with the Minimum Expectation:

* **NatHERS ratings** — 7-star weighted-area average / 5.5-star minimum per unit under NCC 2019; 7.5 / 6 under NCC 2022.
* **Building services** — at least four of nine defined measures, or a BASIX energy score 20% better than minimum in NSW.
* **Energy efficient appliances** — minimum energy-efficiency ratings for any appliances provided.

**Exceptional Performance (Optional) — 3 points:** For NCC 2022 projects:

* **NatHERS** — 8-star average / 7-star minimum per unit.
* **Building services** — at least six of the nine measures, or a 30%-better BASIX score.

Full requirements: [A22 | Energy Use – Residential pathway](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/categories-and-credits/apartments-pathway/categories-and-credits/positive/a22-or-energy-use-residential-pathway.md)

***

#### <mark style="color:$success;">Energy Use – Industrial - Sector Specific Credit</mark>

Available to industrial buildings leased to tenants (e.g. distribution centres, storage warehouses, manufacturing). Alternative to the Energy Use credit — cannot be claimed in addition to it.

The required performance level depends on registration date and target rating (see Strategy table in the full credit).

**Minimum Expectation — Nil:**

* **Minimum energy efficiency** — prescriptive requirements for unconditioned warehouse spaces (LPD, daylight sensors, skylights) and conditioned office spaces (LPD, envelope fabric).

**Credit Achievement (Mandatory) — 3 points**: In conjunction with the Minimum Expectation:

* **Energy efficiency measures** — any three of the seven defined measures (lighting, envelope, glazing, hot water, HVAC, on-site storage), OR
* **Onsite renewables** — at least 99 kW of solar PV per 10,000 m² of GLA, consumed behind the meter.

**Exceptional Performance (Optional) — 3 points:**

* **Energy efficiency measures** and **onsite renewables** (both), OR
* **High energy efficiency measures** — at least six of the seven measures, OR
* **High onsite renewables** — at least 198 kW of solar PV per 10,000 m² of GLA.

Full requirements: [Energy Use – Industrial](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/categories-and-credits/sector-specific-credits/energy-use-industrial.md)

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/categories-and-credits/positive/22-or-energy-use.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.