> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-b.-hvac-system-simulation-parameters.md).

# Appendix B. HVAC system simulation parameters

The peak gain values that must be used for both the *Proposed* and *Reference building* during the project simulation are as specified in this section, which (refer to Modelling criteria) must be used in place of those given in NCC Section J Specification S35C2(1).

*Table 3: HVAC simulation parameters – for all buildings*

<table data-search="false"><thead><tr><th>Item</th><th>Proposed building</th><th>Reference building</th></tr></thead><tbody><tr><td>Temperature and humidity control band</td><td>For all air-conditioned spaces, including process/manufacturing spaces and specialist labs such as clean rooms, the air conditioning must be modelled on the basis of the design temperature and humidity (where applicable) control ranges.<br><br>Where spaces in the project have been designed to operate comfortably within a broader temperature band than for the <em>Reference building</em>, this widened temperature band may be used in the modelling provided that:<br>• The design criteria for the project lists these space temperatures in the mechanical specifications for system sizing and selection; and<br>• The owner provides confirmation in a letter that the spaces will be operated under the design criteria provided; and that the thermostats will be programmed to these values; and<br>• Where an anchor tenant (at least 30% of NLA) has been confirmed for a speculative development, an executed lease agreement or letter from the tenant confirming their agreement for operating within this broader temperature band, is provided.</td><td>Where the design temperature range is within the relevant range below for the space occupancy type, the <em>Reference building</em> shall use the same control band as the <em>Proposed building</em>.<br><br>Where the design temperature range is outside of this range, the <em>Reference building</em> shall use the temperature limits described in the NCC 2025 Section J Specification S34C2 (c):<br>• For transitory occupancy – within the temperature range 18 to 25 °C for at least 95% of plant operating hours (excluding the first hour of operation in each day) in all conditioned spaces, and,<br>• For all other conditioned spaces - within the temperature range 21 to 24 °C for at least 95% of plant operating hours (excluding the first hour of operation in each day) in all conditioned spaces.<br><br>The intent of this requirement is so that the <em>Reference building</em> matches the <em>Proposed building's</em> level of occupant service. Additionally, gains in energy efficiency do not come at the expense of comfort, except where the building owner has explicitly accepted this outcome.<br><br>For any spaces where humidity control is also provided, the <em>Reference building</em> shall use the same temperature and humidity control bands as the <em>Proposed building</em>.<br><br>Exceptions to the above are as follows:<br>• Swimming pools: as per design conditions<br>• Kitchens (preparation and store areas): as per design conditions</td></tr><tr><td>Maximum occupancy</td><td>The maximum occupancies that should be used in conjunction with the appropriate occupancy schedules, is the maximum design occupancy when known. Where it is not known, the occupancies given in NCC Section D Table D2D18 should be used.</td><td>As <em>Proposed building</em> (per NCC Section J Specification S34C3 (6)(e) and Specification 45 Table S45C (3)(d)).</td></tr><tr><td>Sensible and latent heat gain per person</td><td>The degree of activity within each space must be assessed by the design team and the appropriate sensible and latent gains used, and must be appropriate for the space design temperature.<br><br>Acceptable sources of metabolic rates ASHRAE Standard 55-2013 (or later) and CIBSE Guide A.</td><td>As <em>Proposed building</em> (per NCC Section J Specification S34C3 (6)(e)).</td></tr><tr><td>Maximum lighting</td><td>The maximum lighting power density that should be used in conjunction with the lighting profile should be the adjusted lighting power density based on the <em>Proposed building</em> lighting design and control i.e. after the adjustment factors (refer to Automatic lighting controls) have been applied.</td><td>The maximum lighting power density that is permitted by NCC Section J Clause J7D3.<br><br>For residential units in a Class 2 building, as <em>Proposed building</em>, using day- and night-time lighting power densities in NCC Section J Specification 45 Table S45C3d.</td></tr><tr><td>Maximum equipment</td><td>The equipment loads that must be used in conjunction with the equipment profiles are given in Table 5 below.</td><td>As <em>Proposed building</em>.<br><br>For residential units in a Class 2 building, as <em>Proposed building</em>, using cooking and appliances power density in NCC Section J Specification 45 Table S45C3d.</td></tr><tr><td>Outdoor air rate</td><td>Outdoor air rates must be in accordance with the design.<br><br>Outdoor air rates may be modulated if demand-controlled ventilation systems are specified; otherwise the design outdoor air rate must be simulated at all times during the projects operating hours.</td><td>Reference building outdoor air rate must be as per NCC Section J Specification S34C2(a)(ii),, i.e. "the amount of ventilation required by Part F4" and Part J6D4 (1).</td></tr><tr><td>Energy usage calculations</td><td>Energy usage for all items of plant must consider:<br>• Part load performance,<br>• plant staging,<br>• For cooling plant – impact of chilled water temperature, condenser water temperature, ambient temperature on plant efficiency, pumps, thermal losses, auxiliary equipment such as controls or oil heating;<br>• For heating plant – impact of water temperature on plant efficiency, pumps, thermal losses and thermal mass<br>• Fan and pumps methods of capacity regulation, and fixed/variable pressure controls, fixed static pressure head</td><td>As specified in Tables 63 and 64.</td></tr></tbody></table>

{% hint style="info" %}
**Note 1:** Healthcare interventional suites (such as surgical operating theatres) are excluded from the requirements of NCC Section J Part J7. For these space types, a *Reference building* lighting power density of 25 W/m² shall be assumed.
{% endhint %}

*Table 4: Additional HVAC simulation parameters for a class 2 sole-occupancy unit (apartment)*

| Item                                  | Proposed building                                                                                                                                                                                                                                        | Reference building                                                  |
| ------------------------------------- | -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- | ------------------------------------------------------------------- |
| Heating and cooling load calculations | The amount of energy that is removed from conditioned spaces annually using the HVAC system must be calculated using the heating degree hours, cooling degree hours and dehumidification gram hours given in NCC Section J Specification 45 Table S45C3. | As per the *Proposed building* (NCC Section J Specification S45C3). |
| Internal zones                        | The HVAC simulation must include separate Internal zones for daytime air-conditioned zones, kitchen zones, bedroom and other zones, using the assumptions given in NCC Section J Specification S45C3.                                                    | As *Proposed building*.                                             |

*Table 5: HVAC system simulation equipment loads*

<table data-search="false"><thead><tr><th width="207">Space type</th><th width="225">Space type detail (note 1)</th><th>Equipment load (W/m²)</th></tr></thead><tbody><tr><td colspan="2">Office (including any BCA Class 5-type space in a building of another classification)</td><td>11</td></tr><tr><td rowspan="3">Industrial Space</td><td>Where temperature control is localised and is not designed to handle equipment loads (e.g. manufacturing space)</td><td>0</td></tr><tr><td>General industrial spaces (e.g. laboratory, workshop, warehouse)</td><td>15</td></tr><tr><td>Where the HVAC system has been specifically designed to handle the equipment loads from a defined industrial process (e.g. clean room, server room, cold room)</td><td>Realistic operational loads must be estimated by the design team. The design loadings must not be used as these are intended to be maximum loads and not realistic operational loads. The methodology must be clearly documented.</td></tr><tr><td rowspan="3">Retail</td><td>Showroom (including in a building of another classification)</td><td>5</td></tr><tr><td>Stores</td><td>40</td></tr><tr><td>Mall, food court, public amenities</td><td>Realistic operational loads must be estimated by the design team. The design loadings must not be used as these are intended to be maximum loads and not realistic operational loads. The methodology must be clearly documented.</td></tr><tr><td colspan="2">Fire Station</td><td>8 (office areas)<br>1 (all other areas)</td></tr><tr><td colspan="2">Kitchen</td><td>Realistic operational loads (sensible and latent) must be estimated by the design team, including consideration of the effect of exhaust ventilation on the load manifested in the space relative to the total heat and moisture generated by the kitchen equipment. The design loadings must not be used as these are intended to be maximum loads and not realistic operational loads. The methodology must be clearly documented.</td></tr><tr><td colspan="2">Gymnasium (including any gymnasium space in a building of another classification)</td><td>15</td></tr><tr><td colspan="2">Secondary spaces (e.g. circulation, corridors, stairways, store rooms, car parks)</td><td>0</td></tr><tr><td colspan="2">Healthcare</td><td>Realistic operational loads must be estimated by the design team. The design loadings must not be used as these are intended to be maximum loads and not realistic operational loads. The methodology must be clearly documented.</td></tr><tr><td rowspan="2">Residential </td><td>Living Space</td><td>1100 W (sensible), 750 W (latent) (with kitchen)<br>0 (excluding kitchen)</td></tr><tr><td>Bedrooms</td><td>0</td></tr><tr><td rowspan="3">School</td><td>Classroom, multi-purpose space, library</td><td>5</td></tr><tr><td>Computer/science laboratory</td><td>27</td></tr><tr><td>Canteen, workshop</td><td>25</td></tr><tr><td rowspan="2">University</td><td>Dry laboratories, specialist learning spaces, libraries</td><td>27</td></tr><tr><td>Wet laboratories</td><td>40</td></tr></tbody></table>

{% hint style="info" %}
**Note 1:** For any space types not referenced in this table, realistic operational loads must be estimated by the design team. The design loadings must not be used as these are intended to be maximum loads and not realistic operational loads. The methodology must be clearly documented.
{% endhint %}


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-b.-hvac-system-simulation-parameters.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.