> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-d.-supplementary-building-and-systems.md).

# Appendix D. Supplementary building and systems

## Reference building refrigerated cool room and cold room wall construction

Where refrigerated cool rooms and/or cold rooms are present, the assumed construction for the *Reference building* shall be taken as follows:

*Table 39: Reference building construction for refrigerated cool rooms and cold rooms*

| Construction (ordered outside to inside of refrigerated room)                           | R value (m² K/W) |
| --------------------------------------------------------------------------------------- | ---------------- |
| <p>Concrete (100mm)<br>Insulation (90mm)<br>Cavity (50mm)<br>Composite Panel (25mm)</p> | 4.17             |

## Reference building HVAC Systems

The following guidance has been based on Appendix G of ASHRAE Standard 90.1-2022 and where appropriate the requirements have been modified to better suit the Australian market and the intent of Green Star Buildings v1.1.

The *Reference building* HVAC systems must be of the type and description given in *Table 40* as applicable to all of the space usages within the *Proposed building*. Where reference system types are based on space usage areas, areas are for that specific space usage only; refer to the below example of Reference building HVAC systems definition. The systems shall meet the general HVAC system requirements and any system-specific requirements as nominated in *Table 41* (items 1-10 and 11-25 respectively) that are applicable to the *Reference building* HVAC system type(s). All requirements given in NCC Section J Part J6 must be met by the *Reference building* HVAC systems.

Where the *Proposed building* HVAC services incorporate humidity control (whether dehumidification, humidification or both) for some or all systems, the same areas within the *Reference building* shall be provided with humidity control by an equivalent means compatible with the reference system type applicable to those areas. Where the design team considers that the reference HVAC system for a specific space usage is not appropriate to achieve the specified humidity control range, the reference system may be modified to be of the same type as the proposed system for those areas only.

For all projects, any areas of the building which are only fitted out to shell and core standard, a notional fit out must be modelled that meets the NCC Section J DTS provisions. The design team must demonstrate the HVAC design provision (e.g. space allowance, available pipework or ductwork connections) and basis of thermal zoning (e.g. design guidance included in the tenant fit out guide) that has been incorporated to accommodate the system type modelled.

Where a space usage within the *Proposed building* is not adequately represented by any of the defined space usages in *Table 40*, the project team should either:

* Select the most appropriate system type from those available in *Table 40* with appropriate justification for the system selected; or
* Adopt the same system type as the *Proposed building* and apply cooling and heating to the space usage in question by comparable means to the reference systems in the adjacent spaces, e.g. CHW/HHW coils if VAV AHU or FCU, VRF if VRF FCU, etc.

### Example Reference building HVAC systems definitions

Reference system types are based on space usage therefore buildings with multiple difference space usages would expect to include a variety of reference systems.

The following example is for a mixed office and hotel building in climate zone 5. The total office NLA is 11,000 m2 across low- and high-rise portions (i.e. two rises for mechanical services) and the hotel has a total of 70 guest suites and associated guest facilities.

* Office high-rise floors (8,000 m2 NLA): System type 7a (high-rise set)
* Office low-rise floors (3,000 m2 NLA): System type 7a (low-rise set)
* Office main entry: System type 7a (combined with low-rise set)
* Car park: NA (unconditioned)
* Office end of trip facility: System type 4 (refer to Table 41 Item 1)
* Hotel guest suites (total number 70): System type 4c (one per floor)
* Hotel guest facilities:
  * Swimming pool and gym: System type 6 for swimming pool and System type 4c for gym
  * Restaurant, bar and kitchen: System type 4c for restaurant and bar and System type 5 for kitchen
* Hotel main entry: System type 4c
* Hotel BOH facilities: System type 4c

*Table 40: Reference building HVAC system types by space usage type*

<table data-search="false"><thead><tr><th width="152">Space usage type</th><th width="218">System description — Climate zone 1, 2 and 5</th><th width="170">System description — Climate zone 3, 4, 6 and 7</th><th>System description — Climate zone 8</th></tr></thead><tbody><tr><td colspan="4"><strong>Residential spaces including SOUs and common areas for residents</strong></td></tr><tr><td>Residential SOUs for small apartment blocks &#x3C;100 apartments</td><td>System type 1: Air-source packaged/split DX reverse cycle (heat pump) systems (one per SOU) and local outside air provision.</td><td>System type 1</td><td>System type 1</td></tr><tr><td>Residential SOUs for large apartment blocks >=100 apartments</td><td>System type 2a: Air- source heat pump VRF (one per floor) with dedicated outside air fan (one per SOU) sized to AS1668.2-2024 Table A.1 requirements</td><td>System type 2a</td><td>System type 2a</td></tr><tr><td>Residential common areas, excluding sole-occupancy units and swimming pool areas</td><td>System type 2b: Air- source heat recovery VRF (one per floor) with dedicated outside air fan (one per floor) sized to AS1668.2-2024 Table A.1 requirements</td><td>System type 2b</td><td>System type 2b</td></tr><tr><td colspan="4"><strong>Spaces with daytime operation only and occasional overnight use</strong></td></tr><tr><td>Industrial - warehouses</td><td>System type 3: Naturally ventilated. Where temperature-controlled, packaged roof-top heat pump with variable-speed compressors. DCV appropriate unless precluded by the functional requirements of the space usage</td><td>System type 3</td><td>System type 3</td></tr><tr><td>Non-office and non-retail buildings (including healthcare, education and university buildings)</td><td>System type 4a: Air-source heat recovery VRF (one per floor)<br>Dedicated outside air system with variable volume fan coil units (one per zone). DCV appropriate</td><td>System type 4a</td><td>System type 4a</td></tr><tr><td>Commercial kitchen</td><td>System type 5:<br><br>For general cooking areas: variable volume 100% outside air make up air to balance the total kitchen exhaust (excess outside air from other parts of the same floor may be used to reduce the required make up air where suitable consistent with the proposed design), tempered to minimum 18 °C and maximum 26 °C or 8 K below the ambient dry bulb temperature, whichever is the greater. Total exhaust air flow rate as per the applicable requirements of AS1668.2:2024, including exhaust of all cooking and dishwashing equipment. Exhaust and make up air demand may be assumed to follow the equipment load profile in Table 13. DCV not appropriate<br><br>For preparation and store areas: spot cooling by constant volume fan coil units.<br><br>Cooling and heating in kitchen areas shall be by a comparable means to the adjacent spaces, e.g. CHW/HHW coils if VAV AHU or FCU, VRF if VRF FCU, etc.</td><td>System type 5</td><td>System type 5</td></tr><tr><td>Swimming pool</td><td>System type 6:<br><br>Constant volume 100% outside air make up air to balance the total exhaust (excess outside air from other parts of the same floor may be used to reduce the required make up air where suitable consistent with the proposed design) with ventilation heat recovery (sensible heat transfer effectiveness of 60%), and supply air heating only . Total exhaust air flow rate as per the applicable requirements of AS1668.2:2024. DCV not appropriate.</td><td>System type 6</td><td>System type 6</td></tr><tr><td colspan="4"><strong>Office (includes all front of house transitory areas, e.g. main entry and lift lobbies)</strong></td></tr><tr><td>Office base building systems for office areas up to 5,000 m² NLA</td><td>System type 4a</td><td>System type 4a</td><td>System type 4a</td></tr><tr><td>Office base building systems for office areas between 5,000 m2 to 20,000 m2 NLA</td><td>System type 7a: Variable air volume AHUs with terminal electric duct heaters only, one system per perimeter orientation (where differing by 45° or more) and for internal zones based on the same number of rises as the proposed building. DCV appropriate<br><br>Air-cooled chillers<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td><td>System type 7b: Variable air volume AHUs with terminal reheat, one system per perimeter orientation (where differing by 45° or more) and for internal zones based on the same number of rises as the proposed building. DCV appropriate<br><br>Air-source heat pump (shared with cooling)<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td><td>System type 7b<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td></tr><tr><td>Office base building systems for office areas greater than 20,000 m2 NLA</td><td>System type 7d: Variable air volume AHUs with terminal electric duct heaters only, one system per perimeter orientation (where differing by 45° or more) and for internal zones based on the same number of rises as the proposed building. DCV appropriate<br><br>Water-cooled chillers<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td><td>System type 7e: Variable air volume AHUs with terminal reheat, one system per perimeter orientation (where differing by 45° or more) and for internal zones based on the same number of rises as the proposed building. DCV appropriate<br><br>Water-cooled chillers<br><br>Air-source heat pumps<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td><td>System type 7e<br><br>Where provided for the Proposed building, tenant supplementary condenser water system with open-circuit cooling towers</td></tr><tr><td colspan="4"><strong>Retail (includes all front-of-house circulation areas, e.g. malls)</strong></td></tr><tr><td>Retail that is street facing (any size)</td><td>System type 1: Air-source packaged/split DX reverse cycle (heat pump) systems (one per retail unit) and local outside air provision.</td><td>System type 1</td><td>System type 1</td></tr><tr><td>Retail with enclosed area (including large format retail) up to 10,000 m2 GLA</td><td>System type 8a: Air-source heat pump VRF for shops and food courts<br>Dedicated outside air system with variable volume fan coil units (one per zone). DCV appropriate<br>Air-source packaged roof-top heat pump for other common areas</td><td>System type 8a</td><td>System type 8a</td></tr><tr><td>Retail with enclosed area between 10,000 m2 to 20,000 m2 GLA</td><td>System type 8b: AHUs with variable air volume with electric duct heaters only for common areas<br>Dedicated outside air system with variable volume CHW fan coil units for shops and food court (with zonal electric heaters) (one per zone). DCV appropriate<br>Air-cooled chillers</td><td>System type 8c: Variable air volume AHUs with terminal reheat for common areas<br>Dedicated outside air system with variable volume fan coil units for shops and food court (one per zone). DCV appropriate<br>Air-source heat pumps (shared with cooling)</td><td>System type 8c</td></tr><tr><td>Retail with enclosed area greater than 20,000m2 GLA</td><td>System type 8d: Variable air volume AHUs with electric duct heaters only for common areas (one system per floor)<br>Dedicated outside air system and variable volume CHW fan coil units for shops and food court (with zonal electric heaters) (one per zone). DCV appropriate<br>Water-cooled chillers</td><td>System type 8e: Variable air volume AHUs with terminal reheat for common areas (one system per floor)<br>Dedicated outside air system with variable volume CHW/HHW fan coil units for shops and food court (one per zone). DCV appropriate<br>Water-cooled chillers<br>Air-source heat pumps</td><td>System type 8f: Variable air volume AHUs with terminal reheat for common areas (one system per floor)<br>Dedicated outside air system with variable volume HHW fan coil units for shops and food court (one per zone). DCV appropriate<br>Air-source heat pumps (shared with cooling)</td></tr><tr><td colspan="4"><strong>Buildings with permanent overnight operation (hospital ward, aged care or hotel)</strong></td></tr><tr><td>Residential aged care (Class 9c)</td><td>System type 4b: Air-source heat recovery VRF (one system per floor).<br>Dedicated outside air fan sized to AS1668.2-2024 Table A.1 requirements (one per floor) with constant volume fan coil units serving all conditioned areas (one per zone). DCV not appropriate</td><td>System type 4b</td><td>System type 4b</td></tr><tr><td>Hotels (&#x3C;100 guest rooms)</td><td>System type 4c: Air-source heat recovery VRF (one system per floor)<br>Dedicated outside air system with constant volume FCUs serving all conditioned areas(one per zone). DCV not appropriate</td><td>System type 4c</td><td>System type 4c</td></tr><tr><td>Hotels (≥100 guest rooms)</td><td>System type 9a: Variable air volume AHUs and terminal VAV units with electric heaters for common areas (one AHU for each functional space type e.g. conference rooms, main entry administration offices, restaurant and bar, wellness suite, etc with non-conditioned bathrooms/toilets; and one terminal unit per zone). DCV appropriate<br><br>Dedicated outside air system incorporating heat recovery from guest room bathroom exhaust with variable volume FCUs with electric heaters for guest suites (one per room) and corridors (one per zone). DCV not appropriate.<br><br>Water-cooled chillers</td><td>System type 9b: Variable air volume AHUs and terminal VAV units with reheat for common areas (one AHU for each functional space type e.g. conference rooms, main entry administration offices, restaurant and bar, etc with non-conditioned bathrooms/toilets; and one terminal unit per zone). DCV appropriate<br><br>Dedicated outside air system incorporating heat recovery from guest room bathroom exhaust with variable-volume FCUs for guest suites (one per room) and corridors (one per zone). DCV not appropriate.<br><br>Water-cooled chillers<br>Air-source heat pumps</td><td>System type 9c: Variable air volume AHUs and terminal VAV units with reheat for common areas (one AHU for each functional space type e.g. conference rooms, main entry administration offices, restaurant and bar, etc with non-conditioned bathrooms/toilets; and one terminal unit per zone). DCV appropriate<br><br>Dedicated outside air system incorporating heat recovery from guest room bathroom exhaust with variable-volume FCUs for guest suites (one per room) and corridors (one per zone). DCV not appropriate.</td></tr><tr><td>Hospitals with wards<br><br>For hospitals without wards and other healthcare facilities refer to Buildings with daytime operation only and occasional overnight use</td><td>System type 10a: Constant volume AHUs for common areas and non-ward rooms applying the same zoning and configuration as per the proposed building systems. DCV appropriate unless precluded by the functional requirements of the space usage<br><br>Dedicated outside air system with CHW variable air volume FCUs with terminal electric heaters for ward rooms (one per room). DCV not appropriate<br><br>Air-cooled chillers (cooling only)<br><br>Electric duct heaters (for each HVAC zone and terminal unit)</td><td>System type 10b: Constant volume AHUs for common areas and non-ward rooms applying the same zoning and configuration as per the proposed building systems. DCV appropriate unless precluded by the functional requirements of the space usage<br><br>Dedicated outside air system CHW/HHW with variable air volume FCUs for ward rooms (one per room). DCV not appropriate<br><br>Air-cooled chillers<br>Air-source heat pumps</td><td>System type 10c: Constant volume AHUs for common areas and non-ward rooms applying the same zoning and configuration as per the proposed building systems. DCV appropriate unless precluded by the functional requirements of the space usage<br><br>CHW/HHW Variable air volume FCUs for ward rooms with dedicated outside air system. DCV not appropriate<br><br>Air-source heat pumps (shared with cooling)</td></tr></tbody></table>

*Table 41: Reference building HVAC system design and operating parameters*

<table data-search="false"><thead><tr><th width="95">Item</th><th width="177">Description</th><th>Requirement</th></tr></thead><tbody><tr><td>1</td><td>Standard practice HVAC system type and description</td><td>The HVAC systems in the <em>Reference building</em> shall be based on the usage, conditioned floor area and heating sources as specified in Table 40.<br><br>For unitary/packaged system types 1, 2, and 4 (packaged or split DX units), each thermal block (HVAC zone) shall be modelled with its own HVAC system. Zones with different occupancy or internal gains must be modelled with a separate HVAC system, unless a VRF HVAC system with heat recovery is modelled.<br><br>Individual spaces that have occupancy or process loads or schedules that differ significantly (note 1) from the rest of the space type, or with specific pressurization requirements, require separate single-zone systems conforming to the requirements of unitary/packaged system type 1, 2 or 4 (if less than 500 m²), or an independent CAV or VAV system type 5, 6 or 7 (if greater than 500 m²) (whichever of these system types most closely aligns with the system(s) serving the rest of the space type).<br><br>(Modified from G3.2.1 from ASHRAE Standard 90.1-2022)<br><br>All mechanical ventilation systems must be capable of being deactivated when the building or part of the building served by that system is unoccupied as per NCC Section J Part J6D3.</td></tr><tr><td>2</td><td>Equipment efficiencies</td><td>All equipment efficiencies in the <em>Reference building</em> shall be modelled in accordance with NCC Section J Parts J6 to J8 and/or Minimum Energy Performance Standards (MEPS) requirements as applicable to the type and capacity of equipment.</td></tr><tr><td>3</td><td>Equipment capacities</td><td>The <em>Reference building</em> HVAC plant shall be sized to meet the design criteria of the <em>Reference building</em> (refer to Appendix A. HVAC system design parameters).<br><br>The number of unmet load hours from the system simulation must be reported. It must be justified that the accuracy of the simulation is not significantly compromised by the unmet cooling or heating loads.</td></tr><tr><td>4</td><td>Fan system operation</td><td>Supply and return fan operation in the <em>Reference building</em> shall be as required by NCC Section J Part J6D5. Where variable air flow control applies, minimum fan air flow shall be set to 25% of maximum flow.</td></tr><tr><td>5</td><td>Economizers</td><td>The <em>Reference building</em> HVAC systems shall include economy cycles where required by NCC Part J6D3.</td></tr><tr><td>6</td><td>Design outside airflow rates</td><td>In accordance with the minimum requirements of NCC Part F6 and consistent with the baseline calculation in the Clean Air credit (i.e. in accordance with AS1668.2:2024 or AS1668.4:2024 without any improvement in outdoor air where required in the Clean Air credit).</td></tr><tr><td>7</td><td>Ventilation heat recovery, demand-controlled ventilation or indirect evaporative cooling</td><td>Where required by NCC Section J Part J6D4, either a ventilation energy reclaim system, demand-controlled modulating ventilation or indirect evaporative cooling must be included in accordance with the requirements of this clause. Reference systems descriptions in Table 40 include nomination of DCV appropriate or not. Energy reclaiming systems must have a minimum sensible heat transfer effectiveness of 60%, and be capable of allowing outdoor air to bypass the heat reclaiming system when conditions do not provide a heat reclaim benefit.</td></tr><tr><td>8</td><td>Dedicated outside air system</td><td>100% outside air system providing required outside air for ventilation of occupied spaces served by fan coil units, incorporating the required control measure as per item 7 above and supplementary heating and cooling coils as required. Heating and cooling shall be by the same method as the fan coils served, i.e. direct electric, VRF or air-source heat pumps for heating, VRF or chillers for cooling. Supply air dry bulb temperature set point for heating 18 °C and for cooling 24 °C.</td></tr><tr><td>9</td><td>Design supply airflow rates</td><td>System design supply airflow rates for the <em>Reference building</em> shall be based on a supply-air-to-room-air temperature difference of 11 K, or the required ventilation air or makeup air, whichever is greater. If return or relief fans are specified in the <em>Proposed building</em>, then the <em>Reference building</em> shall also be modelled with fans serving the same functions and sized for the <em>Reference building</em> (modified from G3.2.2.7.1 from ASHRAE Standard 90.1-2022).</td></tr><tr><td>10</td><td>System fan power</td><td>The system fan power of the <em>Reference building</em> system design shall be as specified below:<br><br>The method for determining reference fan power is as follows. The same method is applied for all fans applicable to the <em>Reference building</em>:<br>• System pressure loss is based on the design value without adjustment. Where a project considers there to be reasonable further benefit to be demonstrated by a more detailed calculation of the equivalent reference building pressure loss, as per NCC Section J Parts J6D5 (3) and (4), this is allowed, but detailed calculation is not mandatory.<br>• System flow rate is calculated for air conditioning systems from the total building cooling/heating load (as calculated by the software) and the defined system supply air temperature difference herein; and for ventilation-only systems based on the design supply or exhaust value, or the minimum quantity required by the most recent version of the AS 1668.2.<br>• The above pressure and flow parameters define the reference duty point for the fan.<br>• The fan system efficiency is minimum required value, as per NCC Section J Part J6D5 (2), assuming the same fan type and installation arrangement as for the actual system.<br>• The fan power is calculated as: $P_{ref} = \frac{q\Delta p}{1{,}000{,}000 \cdot \eta_{system}}$<br>Where $P_{ref}$ is the reference fan power (kW), $q$ is the duty flow rate (L/s), $\Delta p$ is the system duty pressure loss (Pa) and $\eta_{system}$ is the system efficiency (and pressure and efficiency are either static or total values, as applicable for the fan installation type).</td></tr><tr><td>11</td><td>Air-to-air heat pumps (unitary AC) (System types 1 and 2)</td><td>Heat pumps shall be modelled with the required EER (cooling mode) and COP (heating mode) as per the minimum requirements of NCC Section J Part J6D12 or MEPS. Where only EER is specified, the COP shall be assumed to be equal to the EER. Where AEER and ACOP values are specified, the EER and COP shall be taken as equal to the stated values.<br><br>Part load operation of heat pumps should be modelled as per the specified unit, and must consider varying ambient temperatures and coil air on and air off temperatures. The same part load curves must be used for both the proposed and reference models.</td></tr><tr><td>12</td><td>Air-source VRF (System type 4)</td><td>Air-source VRF systems shall be modelled with the required EER (cooling mode) and COP (heating mode) as per the minimum requirements of NCC Section J Part J6D12 or MEPS. Where only EER is specified, the COP shall be assumed to be equal to the EER. Where only AEER and ACOP values are specified, the EER and COP shall be taken as equal to the stated values.<br><br>For the purpose of reference system design sizing, the heating-to-cooling capacity ratio of the outdoor unit at the reference conditions applicable to NCC Section J Part J6D12 or MEPS shall be taken as 1.1, regardless of the design sizing of room loads (this is to ensure that the part-load characteristics of the system are appropriately represented in both modes of operation).<br><br>Part load operation of heat pumps should be modelled as per the specified unit and must consider varying ambient temperatures and coil air on and air off temperatures. The same part load curves must be used for both the proposed and reference models.<br><br>System cooling operation shall not be permitted below ambient dry bulb temperature of 4 °C and heating operation shall not be permitted above ambient dry bulb temperature of 16 °C.</td></tr><tr><td>13</td><td>Direct electric heating</td><td>Where applicable, direct electric heating will be applied with an associated efficiency of 100%. If in any instance a reference system specified with electric heating coils has a system heating capacity exceeding the maximum allowable value in NCC Section J Part J6D10(1)(e) then they must be substituted for HHW coils served by air-source heat pumps.</td></tr><tr><td>14</td><td>Air-to-water heat pumps</td><td>All space heating fuel sources shall be electric, and heating equipment is shared with the cooling system where specified in Table 40. The number and capacity of air source heat pumps or 4-pipe chillers shall be determined as follows:<br>• For heat pumps, minimum of two heat pumps sized equally and limited to 1,000 kWr each heat pump. Where the total system load exceeds 2,000 kWr, add heat pumps as required such that they are sized equally and less than 1,000 kWr each at design conditions.<br>• For 4-pipe chillers shared with cooling duty, minimum of three 4-pipe chillers sized equally and limited to 1,000 kWr each chiller. Where the total system load exceeds 3,000 kWr, add 4-pipe chillers as required such that they are sized equally and less than 1,000 kWr each at design conditions. The capacity of units shall be based on the larger of the required heating or cooling duty, and the ratio of heating to cooling capacity at rated conditions shall be 1.1.<br><br>For heat pumps and 4-pipe chillers, staging shall be assumed to occur in increments of one unit added/removed at a time at the load threshold of 85% of a single heat pump's capacity, e.g. for a system with three units of capacity 800 kW, first staging threshold is at 680 kW (1 unit below and 2 units above) and second staging threshold is at 1360 kW (2 units below and 3 units above).<br><br>Part load operation of heat pumps or 4-pipe chillers (heating mode) should be modelled as per the specified unit and must consider varying ambient temperature and leaving water temperature.<br><br>Each connected group of air-source heat pumps, including 4-pipe reverse cycle chillers, shall meet the requirements of NCC 2025 Section J6D10 (8)(a) and (b), as applicable. All air-source heat pumps shall be modelled with the same COP for heating mode and EER for cooling mode</td></tr><tr><td>15</td><td>Heating hot water supply and operating temperature</td><td>Heating hot water system design flow and return temperatures fixed at 55 and 45°C respectively. Operational temperatures shall be reset as follows:<br>• Outside air temperature &#x3C;7 °C: 55 °C supply temperature<br>• Outside air temperature 7-16 °C: linear variation from 55 to 45 °C<br>• Outside air temperature >16 °C: 45 °C supply temperature.</td></tr><tr><td>16</td><td>Heating hot water pumps</td><td>Systems shall be modelled with one pump per heat pump and pump operation interlocked with operation of the associated heat pump. The <em>Reference building</em> hot-water pumps shall meet all the requirements of the NCC Part J6D8 (refer to Reference building pump power).</td></tr><tr><td>17</td><td>Piping losses and thermal inertia</td><td>Piping losses for heating hot water and chilled water shall be the same for the <em>Reference building</em> as modelled in the <em>Proposed building</em>. Thermal inertia for heating hot water systems in the <em>Reference building</em> shall be varied in proportion to the ratio of the peak heating load between the <em>Reference</em> and <em>Proposed building</em>.</td></tr><tr><td>18</td><td>Type and number of chillers</td><td>Chillers shall be modelled in parallel configuration. The number and capacity of chillers shall be determined as follows:<br>• For 4-pipe chillers shared with heating duty, minimum of three 4-pipe chillers sized equally and limited to 1,000 kWr each chiller. Where the total system load exceeds 3,000 kWr, add 4-pipe chillers as required such that they are sized equally and less than 1,000 kWr each at design conditions. The capacity of units shall be based on the larger of the required heating or cooling duty, and the ratio of heating to cooling capacity at rated conditions (as per NCC 2025 Part J6D10) shall be 1.1.<br>• For air-cooled chillers, minimum of two chillers sized equally and limited to 1,000 kWr each chiller. Where the total system load exceeds 2,000 kWr, add chillers as required such that they are sized equally and less than 1,000kWr each at design conditions. Air-cooled scroll chillers shall be used unless the chiller thermal capacity > 528kWr, for which variable-speed screw chillers shall be used.<br>• For water-cooled chillers, minimum of two chillers sized equally and limited to 2,000 kWr each chiller. Where the total building load exceeds 4,000 kWr, add chillers as required such that they are sized equally and less than 2,000 kWr each at design conditions. Centrifugal chillers shall be used except in the following scenarios:<br>  − In climate zones 1, 2 and 3, VSD screw chillers for chiller capacity &#x3C;265 kWr<br>  − In all other climate zones, VSD screw chillers for chiller capacity &#x3C;1400 kWr<br>• For all chiller types, staging shall be assumed to occur in increments of one chiller added/removed at a time at the load threshold of 85% of a single chiller's capacity, e.g. for a system with three units of capacity 800 kW, first staging threshold is at 680 kW (1 unit below and 2 units above) and second staging threshold is at 1360 kW (2 units below and 3 units above).<br><br>The chillers will have the minimum required EER and IPLV values as given in the NCC 2025 Section J Part J6D11 (2). Chiller operation across the operating range must be modelled using the performance curve details in Table 42 (applicable to NCC 2022) (see Note 2) or Table 43 (applicable to NCC 2025).</td></tr><tr><td>19</td><td>Chilled water design and operating supply temperature</td><td>Chilled-water design supply temperature shall be modelled at 6 °C and return water temperature at 12 °C. Operational temperatures shall be reset as follows:<br>• Outside air temperature &#x3C;16 °C: 10 °C supply temperature<br>• Outside air temperature 16-25 °C: linear variation from 10 to 6 °C<br>• Outside air temperature >25 °C: 6 °C supply temperature</td></tr><tr><td>20</td><td>Chilled water pumps</td><td>Systems shall be modelled with one pump per chiller or 4-pipe heat pump and pump operation interlocked with operation of the associated chiller or 4-pipe heat pump. The <em>Reference building</em> chilled water pumps shall meet the requirements of the NCC Part J6D8 (refer to Reference building pump power). Pumping systems shall be modelled with variable primary flow, with a minimum flow rate of 70% of design through each chiller.</td></tr><tr><td>21</td><td>Heat rejection</td><td>The <em>Reference building</em> heat rejection fan power shall meet the requirements of the NCC Section J Part J6D13 for the applicable fan type.</td></tr><tr><td>22</td><td>Condenser water pumps</td><td>Systems shall be modelled with one pump per chiller and pump operation interlocked with operation of the associated chiller. The <em>Reference building</em> condenser water pumps shall meet all the requirements of the NCC Section J clause J6D8 (refer to Reference building pump power). Pumping systems shall be modelled with variable primary flow, with a minimum flow rate of 70% of design through each chiller.</td></tr><tr><td>23</td><td>Tenant condenser water supplementary heat rejection</td><td>Where Tenant supplementary heat rejection is provided by the base building, this shall be provided by a dedicated single-cell axial fan cooling tower sized for 100% of duty. Staged primary/secondary variable speed pumping (both two pumps each at 50% of design flow rate) shall be used, with a heat exchanger to separate primary (open) and secondary (closed) systems.<br><br>Where actual heat rejection duty is unknown, assume 50% of design load Monday to Friday, 8am to 6pm, and 20% of design load at all other times.<br><br>Cooling tower control shall be based on maintaining a tower leaving condenser water temperature of 25 °C with minimum wet bulb approach of 5 K; and a heat exchange temperature difference of 1 K (i.e. nominal secondary system flow temperature of 26ºC). The cooling tower fan shall be variable-speed controlled to maintain leaving water temperature at set point.<br><br>The <em>Reference building</em> condenser water pumps shall meet all the requirements of the NCC Section J clause J6D8 (refer to Reference building pump power). The minimum variable speed pump operating point shall be assumed to be 25% of design flow rate (for an individual pump). The minimum flow rate through the cooling tower shall be assumed to be 40% of design flow rate. The variable primary pump speed shall modulate to maintain the secondary circuit flow temperature at 26°C – reducing its speed for less water flow when the secondary circuit flow temperature drops below 26°C.<br><br>The <em>Reference building</em> cooling tower fan power shall meet the requirements of NCC Section J Part J6D13 for the applicable fan type.</td></tr><tr><td>24</td><td>VAV minimum flow setpoints</td><td>Minimum turndown ratio for each zone of a VAV system shall be modelled at 30% of design supply air flow rate or equal to the outdoor air supply rate, whichever is greater.</td></tr><tr><td>25</td><td>VAV fan part-load performance</td><td>VAV system supply fans and return air fans (where applicable) shall have variable speed drives, and their part-load performance characteristics shall be modelled using Method 2 in Variable air volume fan speed control in Appendix D.</td></tr></tbody></table>

> Note 1: Peak thermal loads that differ by 30% or more from the average of other spaces served by the system, or schedules that differ by more than 40 equivalent full-load hours per week from other spaces served by the system are considered to differ significantly.

> Note 2: In order to model chiller part-load operation to achieve the required IPLV, apply the multipliers as per Table 42 to the full-load EER to calculate the EER at 75%, 50% and 25% of full-load output at nominated reference conditions (modified from AS/NZS 4776.2:2008).

*Table 42: Reference building chiller part-load EER multipliers (applicable to NCC 2022)*

<table data-search="false"><thead><tr><th>Chiller Type — Heat Rejection</th><th>Chiller Type — Compressor</th><th>Capacity — Min</th><th>Capacity — Max</th><th>EER Multiplier at Part Load Factor — 75%</th><th>50%</th><th>25%</th></tr></thead><tbody><tr><td>Air-cooled</td><td>Any</td><td>0</td><td>528</td><td>1.59</td><td>1.79</td><td>1.2</td></tr><tr><td>Air-cooled</td><td>Any</td><td>>528</td><td></td><td>1.62</td><td>1.83</td><td>1.22</td></tr><tr><td>Water-cooled</td><td>Screw</td><td>0</td><td>264</td><td>1.51</td><td>1.71</td><td>1.16</td></tr><tr><td>Water-cooled</td><td>Screw</td><td>264</td><td>528</td><td>1.49</td><td>1.69</td><td>1.11</td></tr><tr><td>Water-cooled</td><td>Screw</td><td>528</td><td>1055</td><td>1.52</td><td>1.68</td><td>1.17</td></tr><tr><td>Water-cooled</td><td>Screw</td><td>1055</td><td>2110</td><td>1.48</td><td>1.68</td><td>1.14</td></tr><tr><td>Water-cooled</td><td>Screw</td><td>>2110</td><td></td><td>1.49</td><td>1.7</td><td>1.15</td></tr><tr><td>Water-cooled</td><td>Centrifugal</td><td>0</td><td>528</td><td>1.54</td><td>1.75</td><td>1.13</td></tr><tr><td>Water-cooled</td><td>Centrifugal</td><td>528</td><td>1055</td><td>1.39</td><td>1.59</td><td>1.12</td></tr><tr><td>Water-cooled</td><td>Centrifugal</td><td>1055</td><td>1407</td><td>1.49</td><td>1.68</td><td>1.11</td></tr><tr><td>Water-cooled</td><td>Centrifugal</td><td>>1407</td><td></td><td>1.49</td><td>1.7</td><td>1.15</td></tr></tbody></table>

*Table 43: Reference building chiller part-load performance curve parameters (applicable to NCC 2025)*

<table data-search="false"><thead><tr><th></th><th>Type 1</th><th>Type 2</th><th>Type 3</th><th>Type 4</th><th>Type 5</th><th>Type 6</th><th>Type 7</th><th>Type 8</th></tr></thead><tbody><tr><td>Type</td><td>4-pipe (cooling mode)</td><td>Air-cooled</td><td>Air-cooled</td><td>Water-cooled</td><td>Water-cooled</td><td>Water-cooled</td><td>Water-cooled</td><td>Water-cooled</td></tr><tr><td>Rated capacity range (kWr)</td><td>All</td><td>≤550</td><td>>550</td><td>≤250</td><td>>250 and ≤500</td><td>>250 and ≤500</td><td>>500 and ≤1500</td><td>>1500</td></tr><tr><td>Climate zone</td><td>All</td><td>All</td><td>All</td><td>All</td><td>1,2,4,5,6,7 and 8</td><td>3</td><td>All</td><td>All</td></tr><tr><td>Rated ELWT (°C)</td><td>7</td><td>7</td><td>7</td><td>7</td><td>7</td><td>7</td><td>7</td><td>7</td></tr><tr><td>Rated CEAT (°C)</td><td>35</td><td>35</td><td>35</td><td>NA</td><td>NA</td><td>NA</td><td>NA</td><td>NA</td></tr><tr><td>Rated CEWT (°C)</td><td>NA</td><td>NA</td><td>NA</td><td>30</td><td>30</td><td>30</td><td>30</td><td>30</td></tr><tr><td>CAPFT C00</td><td>1.456040</td><td>1.479360</td><td>1.479360</td><td>1.263510</td><td>1.417910</td><td>1.456040</td><td>1.479360</td><td>1.443750</td></tr><tr><td>CAPFT C10</td><td>0.046280</td><td>0.051520</td><td>0.051520</td><td>0.018070</td><td>0.038870</td><td>0.046280</td><td>0.051520</td><td>0.043750</td></tr><tr><td>CAPFT C20</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td></tr><tr><td>CAPFT C01</td><td>-0.021268</td><td>-0.022512</td><td>-0.022512</td><td>-0.011817</td><td>-0.019297</td><td>-0.021268</td><td>-0.022512</td><td>-0.020625</td></tr><tr><td>CAPFT C02</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td></tr><tr><td>CAPFT C11</td><td>-0.000676</td><td>-0.000784</td><td>-0.000784</td><td>-0.000169</td><td>-0.000529</td><td>-0.000676</td><td>-0.000784</td><td>-0.000625</td></tr><tr><td>EIRFT C00</td><td>0.619585</td><td>0.615120</td><td>0.606807</td><td>0.758578</td><td>0.673578</td><td>0.656660</td><td>0.637832</td><td>0.648045</td></tr><tr><td>EIRFT C10</td><td>-0.019703</td><td>-0.020680</td><td>-0.020592</td><td>-0.011829</td><td>-0.017230</td><td>-0.018287</td><td>-0.018655</td><td>-0.017805</td></tr><tr><td>EIRFT C20</td><td>0.000628</td><td>0.000709</td><td>0.000716</td><td>0.000181</td><td>0.000537</td><td>0.000677</td><td>0.000790</td><td>0.000643</td></tr><tr><td>EIRFT C01</td><td>0.007314</td><td>0.006654</td><td>0.006835</td><td>0.007127</td><td>0.005058</td><td>0.003657</td><td>0.002715</td><td>0.004423</td></tr><tr><td>EIRFT C02</td><td>0.000453</td><td>0.000499</td><td>0.000506</td><td>0.000161</td><td>0.000439</td><td>0.000542</td><td>0.000625</td><td>0.000520</td></tr><tr><td>EIRFT C11</td><td>-0.000675</td><td>-0.000742</td><td>-0.000764</td><td>-0.000205</td><td>-0.000600</td><td>-0.000760</td><td>-0.000906</td><td>-0.000744</td></tr><tr><td>EIRFPLT C00</td><td>0.160932</td><td>0.160932</td><td>0.118251</td><td>0.273871</td><td>0.204911</td><td>0.187251</td><td>0.147880</td><td>0.118251</td></tr><tr><td>EIRFPLT C10</td><td>0.005255</td><td>0.005255</td><td>0.072325</td><td>-0.146594</td><td>-0.036630</td><td>0.004090</td><td>0.026743</td><td>0.072325</td></tr><tr><td>EIRFPLT C20</td><td>0.833813</td><td>0.833813</td><td>0.809424</td><td>0.872724</td><td>0.831720</td><td>0.808659</td><td>0.825376</td><td>0.809424</td></tr><tr><td>EIRFPLT C01</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td></tr><tr><td>EIRFPLT C02</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td></tr><tr><td>EIRFPLT C11</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td><td>0.000000</td></tr></tbody></table>

ELWT: Evaporator leaving water temperature

CEAT: Condenser entering dry bulb air temperature (for air-cooled chillers and 4-pipe chillers (cooling mode))

CEWT: Condenser entering water temperature (for water-cooled chillers)

Coefficients in Table 43 are to be used in conjunction with the following biquadratic equations, as are commonly implemented in simulation software, to determine the adjustment factors to be applied to rated capacity and rated energy input ratio (EIR = 1/COP) to define chiller performance across the range of operating temperatures and load:

* Capacity as a function of chilled water temperature and condensing temperature (condenser water entering temperature for water-cooled chillers and entering ambient dry bulb temperature for air-cooled and 4-pipe chillers) (CAPFT):

$$
CAPFT(T\_{chw}, T\_{cond}) = C\_{00} + C\_{10}T\_{chw} + C\_{20}T\_{chw}^2 + C\_{01}T\_{cond} + C\_{02}T\_{cond}^2 + C\_{11}T\_{chw}T\_{cond}
$$

* Energy input ratio (EIR = 1/EER) as a function of chilled water temperature and condensing temperature (condenser water entering temperature for water-cooled chillers and entering ambient dry bulb temperature for air-cooled and 4-pipe chillers) (EIRFT):

$$
EIRFT(T\_{chw}, T\_{cond}) = C\_{00} + C\_{10}T\_{chw} + C\_{20}T\_{chw}^2 + C\_{01}T\_{cond} + C\_{02}T\_{cond}^2 + C\_{11}T\_{chw}T\_{cond}
$$

* EIR as a function of part-load ratio and chiller temperature difference (T diff = Tcond-Tchw) (EIRFPLT):

$$
EIRFPLT(p, T\_{diff}) = C\_{00} + C\_{10}p + C\_{20}p^2 + C\_{01}T\_{diff} + C\_{02}T\_{diff}^2 + C\_{11}pT\_{diff}
$$

*Table 44: Reference building unitary AC – Variable Refrigerant Flow (VRF) performance*

| Cooling Capacity (kWr) | Energy Efficiency Ratio (EER) |
| ---------------------- | ----------------------------- |
| <39                    | 3.48                          |
| >39                    | 3.17                          |

*Table 45: Reference building water-cooled unitary AC performance*

| Cooling Capacity (kWr) | Water-cooled unitary AC (package conditioners, split DX or VRF) |
| ---------------------- | --------------------------------------------------------------- |
| <65                    | As required by MEPS                                             |
| >=65                   | 4.0                                                             |

## Variable air volume fan speed control

Where the *Proposed* and/or *Reference building* contain variable air volume (VAV) systems their part-load performance characteristics shall be modelled using Method 1 given below (based on Method 2 – Part-Load Fan Power Equation from Table G3.2.3.15 in ASHRAE Standard 90.1-2022). Where the *Proposed building* adopts system pressure optimisation reset control, Method 2 may be applied:

### Method 1 – part-load fan power equation for standard control

$$
P\_{fan} = 0.0013 + 0.1470,PLR\_{fan} + 0.9506,PLR\_{fan}^2 - 0.0998,PLR\_{fan}^3
$$

Where $P\_{fan}$ is the proportion of full-load fan power used at any given fan part-load ratio, and $PLR\_{fan}$ is the fan part-load ratio (ratio of actual system air flow rate (m³/s) in any given hour to the design system air flow rate (m³/s)).

### Method 2 – part-load fan power equation for system pressure optimisation reset control

$$
P\_{fan} = 0.0012 - 0.0579,PLR\_{fan} + 0.5864,PLR\_{fan}^2 + 0.4712,PLR\_{fan}^3
$$

Where definitions of variables $P\_{fan}$ and $PLR\_{fan}$ are as per Method 1.

The difference in proportion of full-load fan power calculated using these methods is illustrated in *Figure 1: Proportion of full-load fan power for Method 1 and Method 2:*

<figure><img src="https://749968417-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FRL05MQuVhZhkDMQBuGrI%2Fuploads%2F6yOjYlnoUoXpN5EqUl9N%2FGSBv1.1_CG_EU_fig1.png?alt=media&amp;token=479900af-8e03-4866-ba09-efe3e25c40e5" alt=""><figcaption></figcaption></figure>

## Reference building pump power

The method for determining reference pump power is as follows. The same method is applied for all pumps applicable to the *Reference building*:

* System pressure loss is based on the design value without adjustment. Where a project considers there to be reasonable further benefit to be demonstrated by a more detailed calculation of the equivalent *Reference building* pressure loss, as per NCC Section J Part J6D8, this is allowed, but detailed calculation is not mandatory.
* System flow rate is calculated from the total building cooling/heating load (as calculated by the software) and the defined system temperature flow and return temperatures herein.
* The above pressure and flow parameters define the reference duty point for the pump.
* To determine the pump motor power, assuming the same pump type and rated motor speed as for the actual system:
  * For glandless impeller pumps, pump motor input power is based on the reference power as follows, assuming that the maximum flow and head values occur are at the reference duty point:

$$
P\_{ref} = 0.623 \cdot q\Delta p + 17(1 - e^{-0.11 \cdot q\Delta p})\\\[1.5em]

Where:\P=Reference:pump:power:(W)\\
q=duty:flow:rate:(L/s)\\
\Delta:p=system:pressure:loss:(kPa)
$$

* For other pump types, pump efficiency is based on the minimum required efficiency as per EU 547/2012 Annex III, assuming that the reference duty point is the best efficiency point (BEP), as follows:

$$
\eta\_{pump} = 88.59 \cdot \ln n\_s + 13.46 \cdot \ln q - 11.48(\ln n\_s)^2 - 0.85(\ln q)^2 - 0.38 \cdot \ln n\_s \cdot \ln q - C\\\[1.5em]
Where:\\
\eta\_{pump}=pump:combined:mechanical:and:hydraulic:efficiency\\
n\_s=pump:specific:speed\\
q=duty:flow:rate (m^3/hour)\\
C=efficiency:parameter
$$

Pump specific speed is defined as follows:

$$
n\_s = n\frac{\sqrt{q}}{(1/i,\Delta p)^{\frac{3}{4}}}\\\[1.5em]
Where:\\
n=pump:speed:(rev/min)\\
i=number:of:pump:stages:(in:the:case:of:a:multistage:pump)\\
\Delta=system:pressure:head
$$

C values are defined as follows, based on the specified minimum efficiency index (MEI) of 0.4:

*Table 46: Pump efficiency parameter (C) by pump type and speed \[MEI = 0.4]*

<table data-search="false"><thead><tr><th>Pump type</th><th>Pump speed (rev/minute)</th><th>C</th></tr></thead><tbody><tr><td>End suction – own bearing</td><td>1450</td><td>128.07</td></tr><tr><td>End suction – own bearing</td><td>2900</td><td>130.27</td></tr><tr><td>End suction – close coupled</td><td>1450</td><td>128.46</td></tr><tr><td>End suction – close coupled</td><td>2900</td><td>130.77</td></tr><tr><td>End suction – close coupled inline</td><td>1450</td><td>132.30</td></tr><tr><td>End suction – close coupled inline</td><td>2900</td><td>133.69</td></tr><tr><td>Multistage – vertical</td><td>2900</td><td>133.95</td></tr><tr><td>Multistage – submersible</td><td>2900</td><td>128.79</td></tr></tbody></table>

The pump power is then evaluated as:

$$
P\_{ref} = \frac{2.725 \cdot q\Delta p}{\eta\_{pump} \cdot \eta\_{elec}}\\\[1.5em]

P\_{ref}=reference:pump:power:(W)\\
q=duty:flow:rate:(m^3/hour)\\
\Delta p=system:pressure:head:(m)\\
\eta\_{elec}=overall:electrical:efficiency:of:the:pump:drive:system:(motor:and:variable:speed:drive)\\
$$

This value is taken to be the product of the MEPS minimum motor efficiency as applicable to the motor type (assuming high efficiency motor) (note: 2900 rev/minute is a 2-pole and 1450 rev/minute is a 4-pole motor) and a default value of 97% for a variable speed drive. MEPS values must be based on the 2018 GEMS Determination, not the 2012 version. Since the motor efficiency is a function of motor rated output, it is necessary to apply an iterative approach. With an initial efficiency value of 0.85, calculate the motor power and hence efficiency, then adjust the efficiency value in the motor power calculation to the new efficiency value. Continue until the successive values of P<sub>ref</sub> differ by no more than 0.1, which generally requires only three or four iterations.

## Reference building domestic hot water systems

The *Reference building* domestic hot water system(s) must generally be of the same type as installed in the *Proposed building*, except that in all cases the fuel will be electricity. Where a system in the *Proposed building* has a design peak usage exceeding 150 L/hour then it will be a heat pump water heater supplemented with direct electric heating; otherwise a direct electric water heater. The efficiency of direct electric water heaters shall be as per Table 41 Item 11. The efficiency of heat pump water heaters shall be nominal coefficient of performance of 3.25 at 7 °C ambient dry bulb temperature. The effect of ambient temperature variation on heating output and power input shall be included as follows (heat pump operation is assumed to be limited to ambient dry bulb temperature of 0 °C and above, hence the direct electric heating operates below this temperature):

*Table 47: DHW heat pump full-load performance parameters*

<table data-search="false"><thead><tr><th>Ambient dry bulb temperature</th><th>Proportion of rated heating output</th><th>Proportion of rated electricity input</th></tr></thead><tbody><tr><td>&#x3C;0</td><td>1.0</td><td>3.25</td></tr><tr><td>0</td><td>0.82</td><td>0.97</td></tr><tr><td>4</td><td>0.92</td><td>0.99</td></tr><tr><td>7</td><td>1.00</td><td>1.00</td></tr><tr><td>10</td><td>1.08</td><td>1.01</td></tr><tr><td>15</td><td>1.21</td><td>1.03</td></tr><tr><td>20</td><td>1.29</td><td>1.05</td></tr><tr><td>25</td><td>1.38</td><td>1.07</td></tr><tr><td>30</td><td>1.42</td><td>1.09</td></tr><tr><td>40</td><td>1.47</td><td>1.11</td></tr></tbody></table>

### Storage systems and tanks

Where the *Proposed building* has storage systems, the *Reference building* may assume that the total storage volume is varied in proportion to the annual domestic hot water usage by use of the prorating method (refer to Modelling operation of heat pump hot water plant / Modelling domestic hot water systems), and that the number of storage tanks is equal to the *Proposed building*.

The standing loss factors shall be used for the *Reference building*, shown below. The storage tank volume is the volume of each individual storage tank in the system. Interpolation between values is allowed, but not outside of the range:

| Storage tank volume (L) | Storage tank turnover ratio 0.5 | 1    | 2    | 5    |
| ----------------------- | ------------------------------- | ---- | ---- | ---- |
| 25                      | 0.46                            | 0.38 | 0.30 | 0.21 |
| 50                      | 0.38                            | 0.30 | 0.23 | 0.15 |
| 100                     | 0.31                            | 0.24 | 0.17 | 0.09 |
| 250                     | 0.23                            | 0.16 | 0.10 | 0.02 |
| 500                     | 0.17                            | 0.11 | 0.05 | 0.01 |
| 1000                    | 0.12                            | 0.06 | 0.02 | 0    |

The storage tank turnover ratio is a measure of the number of times the water within the tank is replaced per day. This is calculated as follows:

$$
R\_{tank} = \frac{q\_{DHW}}{N V\_{total}}\\\[1.5em]
Where:\\
R\_{tank}=storage:tank:turnover:ration:(cycles:per:day)\\
q\_{DHW}=system:annual:hot:water:usage:(L/annum)\\
N=annual:number:of:days:of:operation:of:the:system:(days/annum)\\
V\_{total}=total:storage:volume:of:all:tanks:in:the:system
$$

The standing loss factor of 0.03 shall be used for the *Reference building*.

### Distribution loss factor

For all system types the distribution loss factor is as follows. For the *Reference building*, use the values noted with an asterisk (\*):

| No of outlets per system | Without recirculation pump | With recirculation pump |
| ------------------------ | -------------------------- | ----------------------- |
| 1-10                     | 0.01\*                     | 0.01                    |
| 11-50                    | 0.04\*                     | 0.03                    |
| 51-100                   | 0.07                       | 0.05\*                  |
| 100-250                  | 0.10                       | 0.08\*                  |
| 251-500                  | 0.13                       | 0.10\*                  |
| 500+                     | 0.20                       | 0.15\*                  |

For the *Reference building*, these values may be determined by prorating the *Proposed building* values as follows:

$$
X\_{ref} = \frac{q\_{ref}}{q\_{prop}} X\_{prop}\\\[1.5em]
Where:\\
X=quantity:to:be:prorated\\
q=annual:domestic:hot:water:usage:(L/annum):for:the:system\\
q\_{ref}:and:q\_{prop}=Reference:building:and:proposed:building:values:respectively
$$

## External artificial lighting

Lighting power densities to be applied for the *Reference building* (and *Proposed building* where minimum illuminance values as per AS 1158.3.1:2020 are not achieved by the design) shall be applied according to the applicable lighting subcategory as defined in AS 1158.3.1:2020 as follows:

*Table 48: Standard practice external lighting power densities*

<table data-search="false"><thead><tr><th>Category</th><th>Power density</th></tr></thead><tbody><tr><td>PR1 and PP1 (note 1)</td><td>7.1 W/m</td></tr><tr><td>PR2 and PP2 (note 1)</td><td>4.3 W/m</td></tr><tr><td>PR3 and PP3 (note 1)</td><td>3.5 W/m</td></tr><tr><td>PR4 and PP4 (note 1)</td><td>3.5 W/m</td></tr><tr><td>PR5 and PP5 (note 1)</td><td>2.6 W/m</td></tr><tr><td>PR6 (note 1)</td><td>2.2 W/m</td></tr><tr><td>PA1</td><td>2.1 W/m²</td></tr><tr><td>PA2</td><td>1.4 W/m²</td></tr><tr><td>PA3</td><td>0.8 W/m²</td></tr><tr><td>PE1</td><td>1.7 W/m²</td></tr><tr><td>PE2</td><td>Match adjacent category</td></tr><tr><td>PC1</td><td>1.5 W/m²</td></tr><tr><td>PC2</td><td>0.6 W/m²</td></tr><tr><td>PC3</td><td>0.2 W/m²</td></tr><tr><td>PCD and PCX</td><td>9.0 W/m²</td></tr></tbody></table>

> Note 1: Based on path widths up to 6 metres. For path widths greater than 6 metres, multiply power density by number of 6 metre widths or part thereof, e.g. if path is 8 metres wide, this is 1.33 widths, therefore multiply by 2.

## Lift energy calculation methodology

In this section all symbols used are as defined in and references to table numbers and formulae are to ISO 25745-2:2015 (as AS ISO 25745.2:2019) unless stated otherwise.

{% stepper %}
{% step %}

### Determine shared lift parameters

Based on design specifications (at Design Review), lift technical data (at As-Built Submission) and building design, determine the following parameters for each lift (the same values of all variables apply to both the *Reference* and *Proposed building*):

* Number of stopping floors (i.e. floors with opening doors)
* One-way terminal travel distance for the reference cycle, i.e. the distance travelled between the bottom and top terminal landings (src, m)
* Travel distance within any express zone for the lift (where an express zone is defined as three or more consecutive levels at which a lift car does not stop) (sez, m) (this is an additional item included here to represent better the energy consumption of lift cars with express zone travel)
* Rated load (Q, kg)
* Rated speed, acceleration and jerk (v, a and J, m/s, m/s² and m/s³)

Based on the definitions in Table A.1, determine the usage category for each lift within the project.

Based on either the definitions in Table A.1 or with reference to project brief, PPR or similar documentation, determine the number of operating days (ndays,r, per annum) for each lift (where Table A.1 states 360 days, use 365 days; where Table A.1 states 260 days, use 260 days less any public holidays included in the assessment as per Table 1 (of this guide) item 10, if appropriate for the building type).

Based on the usage category, determine the number of trips (nd, per day) for each lift from Table 1.

Based on the usage category and number of stopping floors, determine the average travel distance factor (kav) for each lift from Table 2 and hence the average one-way travel distance (sav, m) for each lift as follows:

$$
s\_{av} = k\_{av}(s\_{rc} - s\_{ez}) + s\_{ez}
$$
{% endstep %}

{% step %}

### For the Reference building

Determine the reference door opening cycle time (td, s) for each lift from Table 49 based on assumed lift door opening, closing and hold times (adapted from CIBSE Guide D):

*Table 49: Reference building lift door opening cycle times*

| Lift Rated Speed (m/s) | Door Opening time (s) | Door Hold Time (s) | Door closing time (s) | Opening cycle time (s) |
| ---------------------- | --------------------- | ------------------ | --------------------- | ---------------------- |
| ≤2.5                   | 2.4                   | 6.0                | 2.6                   | 11.2                   |
| >2.5                   | 1.7                   | 6.0                | 2.5                   | 10.2                   |

Determine the average travel time (tav) for each lift as per Equation 13.

Determine the total running time per day (trd) for each lift as per Equation 12.

Determine the total non-running time (tnr) of each lift as per Equation 14.

Based on NCC Table J7D8b, determine the energy efficiency class of each lift for its usage category and hence the applicable daily running energy consumption formula in Table 7. Calculate the daily running energy consumption for each lift using the rated load and applicable values of number of trips per day, average travel distance and non-running time determined above.

Based on NCC Table J7D8a and the specified rated load, determine the idle and standby energy performance level of each lift, and hence from Table 6 determine the 30-minute standby power (Pst30, W) for each lift. Calculate the daily total energy consumption on days when not operating (Ed,nr, kWh/day) as follows:

$$
E\_{d,nr} = \frac{24 P\_{st30}}{1000}
$$
{% endstep %}

{% step %}

### For the Proposed building

Based on design specifications (at Design Review) or lift technical data or measurement (at As-Built Submission) determine the following additional parameters for each lift:

* Lift type (traction, hydraulic or positive drive)
* Counterbalancing (counterbalance mass divided by rated load, Q).

By simulation (at Design Review) or measurement (at As-Built Submission), determine the one-way travel distance of the short-cycle (ssc, m), running energy consumption of the reference and short cycles (Erc and Esc respectively, Wh), standby power at idle, 5-minute standby and 30-minute standby (Pid, Pst5 and Pst30, W), and door opening cycle time (td, s) for each lift. Refer to ISO 25745-1:2012 (as AS ISO 25745.1:2019) for further details.

Calculate the average energy consumption of a running cycle with an empty car (Erav) using Formulae 1 to 3, which can be combined as follows for simplicity:

$$
E\_{rav} = E\_{rc} + (E\_{rc} - E\_{sc})\left(\frac{s\_{av} - s\_{rc}}{s\_{rc} - s\_{sc}}\right)
$$

Or If the travel distance for the short cycle does not allow the rated speed to be reached use Formula 4.

Based on the usage category and rated load, determine the average car load (%Q) for each lift from Table 3, then, based on the lift type, counterbalancing and average car load, determine the applicable load factor (kl) of each lift as per Formulae 6 to 11 (notes 1 and 2 may be applied where applicable).

Calculate the daily running energy consumption (Erd) as per Formula 5.

Determine the average travel time (tav) for each lift as per Formula 13.

Determine the total running time (trd) for each lift as per Formula 12.

Determine the total non-running time (tnr) of each lift as per Equation 14.

Based on the usage factor, determine the time ratios in idle and standby mode for each lift from Table 4 and hence calculate the daily non-running energy consumption (Enr) as per Formula 15.

Calculate the daily total energy consumption on days when operating (Ed) as per Formula 16.

Calculate the daily total energy consumption on days when not operating (Ed,nr) as follows:

$$
E\_{d,nr} = \frac{24 P\_{st30}}{1000}
$$
{% endstep %}

{% step %}

### For both the Reference and Proposed building

Calculate the annual energy consumption for each lift for both buildings based on the daily running and non-running energy consumption and number of days of running operation as follows:

$$
E\_{annual} = E\_d, n\_{days,r} + E\_{d,nr}(365 - n\_{days,r})
$$

Hence calculate the total lift energy consumption for each building as the sum of the annual energy consumption of each lift.
{% endstep %}
{% endstepper %}

## Reference building appliances

For Class 2 buildings, appliances shall be included in the building total energy consumption. The performance standard to be used in the *Reference building* is as follows:

*Table 50: Reference building appliance energy ratings*

| Item                    | Reference specification                                 | Reference performance                                           | Maximum available rating (note 1) | Normalised energy consumption |
| ----------------------- | ------------------------------------------------------- | --------------------------------------------------------------- | --------------------------------- | ----------------------------- |
| Refrigerator/freezer    | <p>Group: 5T<br>Fresh food: 250 L<br>Freezer: 100 L</p> | <p>1.5-star below maximum available star rating<br>2.5 Star</p> | 4 Star                            | 436 kWh/annum (2.5 Star)      |
| Dishwasher              | Place settings: 12                                      | <p>1.5-star below maximum available star rating<br>3.0 Star</p> | 4.5 Star                          | 282 kWh/annum (3.0 Star)      |
| Clothes washer (note 2) | Load: 7 kg                                              | <p>1.5-star below maximum available star rating<br>3.5 Star</p> | 5 Star                            | 367 kWh/annum (3.5 Star)      |
| Clothes dryer           | Load: 6 kg                                              | <p>1.5-star below maximum available star rating<br>4.5 Star</p> | 6 Star                            | 200 kWh/annum (4.5 Star)      |

> Note 1: Based on energy performance reported at [www.energyrating.gov.au](http://www.energyrating.gov.au) current at the time of publication of this guide.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-d.-supplementary-building-and-systems.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.