> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-e.-energy-consumption-adjustment-factors.md).

# Appendix E. Energy consumption adjustment factors

## Car park and loading dock atmospheric contaminant control systems

The following energy consumption adjustment factors apply to the installation of atmospheric contaminant monitoring systems and associated variable-speed fan control in car parks and loading docks. The adjustment factor provided in *Table 51* is used to establish the adjusted full-load absorbed fan power as follows:

$$
P\_{fan,adj} = P\_{fan} \times F\_{adj}\\\[1.5em]
P\_{fan,adj}=adjusted:fullload:absorbed:fan:power:(kW)\\
P\_{fan}=absorbed:fan:power:at:the:specified:operating:duty:point:(kW)\\
F\_{adj}=adjustement:factor:for:atmospheric:containment:monitoring:and\\
variable:speed:fan:control:from:Table:51
$$

The adjusted absorbed fan power is then used with the appropriate car park/loading dock HVAC profile to establish the annual energy use of the *Proposed building*.

*Table 51: Adjustment factor for atmospheric contaminant monitoring and variable-speed fan control*

<table><thead><tr><th width="584">Requirement for adjustment factor</th><th>Adjustment factor</th></tr></thead><tbody><tr><td>Car park and/or loading dock mechanical ventilation fans that include variable-speed drives on supply and exhaust fans (as applicable) controlled by an atmospheric contaminant monitoring system in accordance with AS1668.2:2024</td><td>0.7</td></tr></tbody></table>

Where a project contains multiple physically separate car parks and/or loading docks, the adjustment factor must be applied individually to each area with a qualifying atmospheric contaminant monitoring and variable-speed fan control system.

## Automatic lighting controls

The adjustment factors are used to establish an adjusted illumination power density for the *Proposed building* as follows:

$$
LPD\_{prop,adj} = LPD\_{prop} \times F\_{adj}\\\[1.5em]
Where:\\
LPD\_{prop,adj}=adjusted:proposed:lighting:power:density:(W/m^2)\\
LPD\_{prop}=nominal:proposed:lighting:power:density:(W/m^2)\\
F\_{adj}=adjustment:factor:of:the:proposed:automatic:lighting:control:system,:as:detailed\\
in:table:52
$$

The adjustment factors can only be applied to luminaires controlled by the control system, not to the entire space.

Where more than one illumination power density adjustment factor applies to an area, they are to be combined using the following formula:

$$
F\_{adj} = F\_{adj,A} \times \left(F\_{adj,B} + \frac{1 - F\_{adj,B}}{2}\right)\\\[1.5em]
Where:\\
F\_{adj,A}=lowest:of:the:applicable:lighting:power:density:adjustement:factors\\
F\_{adj,B}=second:lowest:of:the:applicable:lighting:power:density:adjustment:factors
$$

Note that if addressable lighting control is included, the fixed increment should be subtracted after the above calculation.

The adjusted proposed lighting power density is then used with the standard lighting profile for the space type (refer to Appendix C. Default operating schedules) to establish the annual lighting energy use of the *Proposed building*.

{% hint style="info" %}
If your project includes automatic lighting controls that are not included here, approval to use specific alternative adjustment factors is required from the GBCA. The project team may submit a Technical Question describing how they propose to apply adjustments for the specific control features and how the improvements have been assessed.
{% endhint %}

*Table 52: Automatic lighting control adjustment factors*

<table data-search="false"><thead><tr><th>Item</th><th>Reference specification</th><th>Reference performance</th><th>Adjustment Factor</th></tr></thead><tbody><tr><td>Motion detector in accordance with Specification J6</td><td>All spaces within a building except for 'industrial spaces' and car parks</td><td>Where an area of 200 m² or less is switched or dimmed as a block by one or more detectors.</td><td>0.9 (note 1)</td></tr><tr><td></td><td>For 'industrial spaces'</td><td>Where the maximum area switched or dimmed as a block by one or more detectors is the area of the space divided by 10, or 2000 m², whichever is smaller. The minimum required block size is 200 m².</td><td>0.9 (note 1)</td></tr><tr><td></td><td>All spaces within a building except for car parks</td><td>Where up to and including 6 lights are switched or dimmed as a block by one or more detectors.</td><td>0.7 (note 1)</td></tr><tr><td></td><td></td><td>Where up to and including 2 lights are switched or dimmed as a block by one or more detectors.</td><td>0.55 (note 1)</td></tr><tr><td></td><td>Car parks</td><td>Where an area of a car park of less than 500 m2 is switched or dimmed as a block by one or more detectors.</td><td>0.7 (note 1)</td></tr><tr><td>Fixed dimming (note 4)</td><td>All</td><td>Lighting is controlled by fixed dimmers that reduce the overall lighting level and the power consumption of the lighting.</td><td>% of full power to which the dimmer is set</td></tr><tr><td>Daylight sensor and dynamic lighting control in accordance with Specification J6 – dimming or stepped switching of lights adjacent to windows and/or roof lights</td><td>All</td><td>(a) Lights within the space adjacent to windows other than roof lights for a distance from the window equal to the floor-to-window-head height.</td><td>0.75 (notes 2 and 3)</td></tr><tr><td></td><td></td><td>(b) Where the total area of roof lights is less than 10% of the floor area, but greater than 5%.</td><td>0.8 (notes 2 and 3)</td></tr><tr><td></td><td></td><td>(c) Where the total area of roof lights is 10% or more of the floor area</td><td>0.75 (notes 2 and 3)</td></tr><tr><td></td><td></td><td>For spaces other than those described under (a), (b) and (c), where lighting is controlled by dynamic dimming (note 5)</td><td>0.95 (notes 2 and 3)</td></tr><tr><td>Addressable lighting control system</td><td>All</td><td>Where an individually addressable system is installed, the adjustment factor can be further reduced by subtraction of an additional fixed increment.</td><td>additional fixed increment of 0.05</td></tr></tbody></table>

> **Note 1:** Where luminaires are not switched off, but are only dimmed, the following equation must be used to determine the modified adjustment factor applicable to these luminaires:
>
> $$
> F\_{adj,dimmed} = F\_{adj,switched} + (P\_{dimmed} \times F\_{adj,switched})
> $$
>
> Where $F\_{adj,dimmed}$ is the adjustment factor to be applied to dimmed luminaires, $F\_{adj,switched}$ is the adjustment factor applicable to switched luminaires (as per this table), and $P\_{dimmed}$ is the proportion of full-load power to which the luminaire input reduces when it is dimmed.

> **Note 2:** These adjustment factors do not apply to tungsten halogen or other incandescent sources.

> **Note 3:** These adjustment factors are conservative. If the design team believes that increased benefit will be realised, then the control operation should be modelled (refer to Modelling daylight-controlled artificial lighting systems). The benefits of automatic controls can also be demonstrated by proposing modifications to the lighting schedules to be used. Such modified lighting schedules need to be approved by the GBCA through the standard Technical Question process before being used in the modelling process.

> **Note 4:** Fixed dimming is the control through control gear adjustment or lighting control software of the maximum luminaire light output that cannot be adjusted by the space user.

> **Note 5:** Dynamic dimming is the automatic and continuous control of the luminaire light output in response to the signal from a photoelectric cell to compensate for the availability of natural light.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-e.-energy-consumption-adjustment-factors.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.