> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-f.-alternative-method-minimum-provisions.md).

# Appendix F. Alternative method minimum provisions

As an alternative to meeting the DTS provisions for the performance of wall-glazing constructions and display windows (NCC Section J Part J4D6), project teams may demonstrate compliance using the below:

* The project team demonstrates that energy use is equal or less (MJ/m²), than a *Reference building* modelled in accordance with the Table 1 of this guide for both the:
  * Proposed building fabric
  * Proposed building
* All three buildings (Reference, Proposed building fabric and Proposed building) meet the thermal comfort requirements where:
  * 95% of the mechanically ventilated regularly occupied areas achieve a PMV (thermal comfort) value of +1 and -1 for 98% of the annual operating hours of the building in line with ASHRAE Standard 55–2013.
  * All naturally ventilated regularly occupied areas maintain the comfort level within 80% of acceptability limits in line with ASHRAE Standard 55–2013.

## <mark style="color:$primary;">Definitions</mark>

**Predicted mean vote (PMV) method**\
The PMV index predicts the mean response of a large group of people on a 7-point thermal sensation scale, from +3 (hot) to -3 (cold), where 0 is neutral. The metric is designed for fully mechanically ventilated buildings and is determined in accordance with ASHRAE Standard 55-2013. A PMV of -1 to +1 means that 80% of people are satisfied and comfortable.

**Proposed building fabric**\
A hypothetical building of the same size, shape, floor area and same glazing shape and areas as the *Proposed building*, and including all the same building envelope design and performance characteristics as the *Proposed building*, but building services characteristics and air temperatures (as nominated in the NCC)) are based predominantly on the NCC Section J Deemed-to-Satisfy provisions as defined in this document, and whose process energy consumption is based on appropriate benchmarks.

This was formerly known as Intermediate Building under Green Star - Design & As Built v1.3.

## <mark style="color:$primary;">Thermal comfort parameters</mark>

For the purposes of PMV calculation, thermal comfort parameters are:

* Air Temperature (°C)
* Air Speed (m/s)
* Relative Humidity (%)
* Mean Radiant Temperature (°C)
* Metabolic rates (met)
* Clothing Levels (clo)

**Clothing level (clo) and Metabolic rate (met)**

ASHRAE Standard 55-2013 is utilized for Clothing level (clo) and Metabolic rate (met), when determining PMV levels in the *Proposed building*, and the comfort levels achieved by the modelling HVAC systems and building fabric. The below default figures shall be used:

<table data-search="false"><thead><tr><th>Building class space use</th><th>Clothing level (clo)</th><th>Metabolic rate (met)</th></tr></thead><tbody><tr><td>Class 2 &#x26; 3 – All living areas (Summer)</td><td>0.36</td><td>1.0</td></tr><tr><td>Class 2 &#x26; 3 – All living areas (Winter)</td><td>0.74</td><td>1.0</td></tr><tr><td>Class 5 – Office (Summer)</td><td>0.61</td><td>1.1</td></tr><tr><td>Class 5 – Office (Winter)</td><td>0.96</td><td>1.1</td></tr><tr><td>Class 6 – Shopping Centre (Summer clothing)</td><td>0.5</td><td>1.7</td></tr><tr><td>Class 6 – Shopping Centre (Winter clothing)</td><td>1.0</td><td>1.7</td></tr><tr><td>Class 7 – Distribution areas</td><td>0.96</td><td>2.1</td></tr><tr><td>Class 7 – Storage areas</td><td>0.96</td><td>1.7</td></tr></tbody></table>

Where alternative values are proposed, or where the building use or class is not adequately described in the above table, these shall be determined in accordance with ASHRAE Standard 55-2013, and a letter provided from the building owner confirming that the occupant clothing proposed, relating to these values, is appropriate for the proposed use of the building.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-f.-alternative-method-minimum-provisions.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.