> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/healthy-3/11-or-clean-air.md).

# 11 | Clean Air

Points: 2

## <mark style="color:$primary;">Outcome</mark>

Pollutants entering the building are minimised, and a high level of air quality is provided to reduce the impact of pollutants and the risk from the spread of infectious diseases.

## <mark style="color:$primary;">Criteria</mark>

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-11.0.1-ventilation-system-attributes](#id-11.0.1-ventilation-system-attributes "mention")**:** Levels of indoor pollutants are maintained at acceptable levels.
* [#id-11.0.2-provision-of-outdoor-air](#id-11.0.2-provision-of-outdoor-air "mention")**:** A high level of effective outdoor air is provided.
* [#id-11.0.3-exhaust-or-elimination-of-pollutants](#id-11.0.3-exhaust-or-elimination-of-pollutants "mention")**:** Pollutants entering the building are minimised.

<mark style="color:$success;">**Credit Achievement — 2 points**</mark>

In addition to *Minimum Expectation*:

* [#id-11.1.1-ventilation-system-attributes](#id-11.1.1-ventilation-system-attributes "mention")**:** The building's ventilation systems allow for easy maintenance.
* [#id-11.1.2-provision-of-outdoor-air](#id-11.1.2-provision-of-outdoor-air "mention") A high level of effective outdoor air is provided.

***

## <mark style="color:$primary;">Additional information</mark>

#### Scope of credit

All building ventilation systems being delivered in the internal, regularly occupied areas of the building. This includes existing and new building systems.

Spaces can be excluded with confirmation via a Technical Question if the use of the space justifies specific ventilation conditions. Refer to *Guidance* for examples.

#### Stage implementation

Strategy | Brief | Concept | **Design** | **Tender** | **Construction** | **Handover** | **Use**

#### Synergies with other credits

* Amenity and Comfort
* Verification and Handover
* Energy Use

#### Sustainable Development Goals

* **Goal 3:** Good Health and Wellbeing

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all three** of the following criteria:

* Ventilation System Attributes
* Provision of Outdoor Air
* Exhaust or Elimination of Pollutants

#### 11.0.1 Ventilation System Attributes

#### *Separation from pollutants*

The building's ventilation system meets minimum separation distances between pollution sources and outdoor air intakes in 95% of the regularly occupied areas. Project teams must choose from at least one of the following pathways relevant to the project's building class space type.

<table data-search="false"><thead><tr><th width="113">Pathway</th><th width="124">Requirement</th><th>.</th><th>.</th></tr></thead><tbody><tr><td rowspan="12"><strong>Class 2 and 3</strong></td><td colspan="3">The building meets the separation distances outlined in the table below. Separation distances are measured in accordance with <em>AS 1668.2:2024 – The use of ventilation and air-conditioning in buildings – Part 2: Mechanical Ventilation in buildings</em>.</td></tr><tr><td><strong>Design airflow rate within the minimum distance (L/s)</strong></td><td><strong>Minimum separation distances from discharges to intakes, or natural ventilation opening of adjacent Sole Occupancy Unit or site boundary (m)</strong></td><td><strong>Minimum separation distances from discharges to intakes, or natural ventilation opening within Sole Occupancy Unit (m)</strong></td></tr><tr><td>&#x3C;100L/s</td><td>1</td><td>N/A</td></tr><tr><td>&#x3C;150L/s</td><td>1.25</td><td><a data-footnote-ref href="#user-content-fn-1">N/A</a></td></tr><tr><td>&#x3C;200L/s</td><td>1.5</td><td><a data-footnote-ref href="#user-content-fn-1">N/A</a></td></tr><tr><td>&#x3C;300L/s</td><td>2.25</td><td>2</td></tr><tr><td>&#x3C;400L/s</td><td>3</td><td>2</td></tr><tr><td>&#x3C;600L/s</td><td>4</td><td>3</td></tr><tr><td>&#x3C;800L/s</td><td>5.5</td><td>4</td></tr><tr><td>&#x3C;1000L/s</td><td>6.2</td><td>5</td></tr><tr><td>>1000L/s</td><td>7.5</td><td>6</td></tr><tr><td colspan="3"><a data-footnote-ref href="#user-content-fn-2">ⓘ</a></td></tr><tr><td><strong>All other building classes</strong></td><td colspan="3"><p>The building meets the minimum separation distances determined by one of the following:</p><ul><li>The greater distance from either Table 5-1 in <em>ASHRAE Standard 62.1:2022 – Ventilation for Acceptable Indoor Air Quality</em> or Table 2.1 in <em>AS 1668.2:2024</em>. Distances are measured in accordance with the relevant standard.</li><li>The distance determined by the analytical method in Appendix B of <em>ASHRAE Standard 62.1: 2022</em>.</li></ul></td></tr></tbody></table>

All openable windows, doors, openings, vents, grilles, and skylights are considered outdoor air intakes.

Diversity factors cannot be applied in meeting this credit.

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
This applies to base building ventilation systems only. Airflow rates for the base building systems account for the anticipated use and design occupancy that includes the tenanted spaces.
{% endhint %}

#### *Cleaning ductwork*

New and existing ductwork in 95% of the regularly occupied areas is cleaned prior to occupation in accordance with one of the following or another recognised standard:

* *ACR 2021 – The NADCA Standard for Assessment, Cleaning and Restoration of HVAC Systems.*
* *SMACNA – IAQ Guidelines for Occupied Buildings under Construction.*

Cleaning of new ductwork occurs after installation.

This includes ductwork from the air handling unit(s) to the supply vents. If no ductwork exists, these requirements are deemed to be met.

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
This applies to base building ventilation systems only. Tenant supplementary systems where the design, maintenance and ownership are determined and controlled by the tenant can be excluded. Refer *Guidance* for further information on determining this.
{% endhint %}

#### 11.0.2 Provision of Outdoor Air

The building provides a high level of effective outdoor air to 95% of the regularly occupied areas. Project teams may choose one or more of the following pathways as relevant to the project's building class type(s). Mixed-use projects, where more than 20% of the GFA, excluding car parks, is not the predominant building type, may be required to comply with more than one pathway.

<table><thead><tr><th width="182.75">Pathway</th><th>Requirement</th></tr></thead><tbody><tr><td>Class 2 and 3</td><td><p>Effective outdoor air is provided by one of the following:</p><ul><li><strong>Mechanical ventilation</strong> that is in accordance with <em>AS 1668.2:2024</em> for the default occupancy of the regularly occupied, habitable rooms.</li><li><strong>Natural ventilation</strong> that is in accordance with <em>AS 1668.4:2024 – The use of ventilation and air-conditioning in buildings – Part 4: Natural Ventilation of buildings</em> for the default occupancy of the regularly occupied, habitable rooms.</li><li><strong>Mixed mode ventilation</strong> that meets the requirements for natural ventilation when the mechanical system is not in use and the requirements for mechanical ventilation when the mechanical system is in use.</li></ul><p>The building also provides a dedicated make-up air path for kitchen, bathroom and laundry spaces that meets Clause 2.3 from <em>AS 1668.2:2024</em>.</p></td></tr><tr><td>All other building classes</td><td><p>Effective outdoor air is provided by one of the following:</p><ul><li><strong>Mechanical ventilation</strong> where there is a 50% improvement of outdoor air required by <em>AS 1668.2:2024</em> to regularly occupied areas based on the design occupancy. Demand controlled ventilation may be used.</li><li><strong>Natural ventilation</strong> that is in accordance with <em>AS1 668.4:2024</em> for the design occupancy. Substantial cross-ventilation is also provided in accordance with Clause 3.5.2 in <em>AS 1668.4:2024</em> with no reduction to the openable area.</li><li><strong>Mixed mode ventilation</strong> that meets the requirements for natural ventilation when the mechanical system is not in use and the requirements for mechanical ventilation when the mechanical system is in use.</li></ul></td></tr><tr><td>Performance based approach</td><td>CO<sub>2</sub> sensors are provided to continuously monitor CO<sub>2</sub> levels within the breathing zone and are linked to controls to adjust the amount of effective outdoor air to each space to maintain CO<sub>2</sub> levels at or less than 800ppm within each space in the regularly occupied areas at all times in the default occupancy period. CO<sub>2</sub> sensors are located within the breathing zone to ensure accurate representative readings of CO2 concentrations with at least one in each individually controlled supply air zone and every enclosed space. The location of the sensors is justified by a qualified mechanical engineer.</td></tr><tr><td>Equivalent clean airflow approach</td><td>Where compliance with the <em>Equivalent clean airflow approach</em> pathway in <a href="#id-11.1.2-provision-of-outdoor-air">Credit Achievement</a> is demonstrated, the <em>Provision of Outdoor Air</em> criteria in <em>Minimum Expectation</em> is considered met.</td></tr></tbody></table>

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
Tenant supplementary systems where the design, maintenance and ownership are determined and controlled by the tenant can be excluded. The base building systems account for the anticipated use and design occupancy that includes the tenanted spaces.
{% endhint %}

#### 11.0.3 Exhaust or Elimination of Pollutants

Pollutants are limited within 95% of the regularly occupied areas. Sources of pollutants include printing and photocopying equipment, cooking processes and equipment and vehicles. Project teams may choose from one of the following pathways.

<table><thead><tr><th width="175.75">Pathway</th><th>Requirement</th></tr></thead><tbody><tr><td>Eliminating pollutant sources</td><td>No sources of pollutants are provided.</td></tr><tr><td>Limiting pollutant sources</td><td><p>All sources of pollutants are compliant with at least one of the following minimum emissions standards or another recognised standard:</p><ul><li><em>DE-UZ 219 – Blue Angel for Office Equipment with Printing Function</em> (superseded revisions of this standard such as DE-UZ 205 and RAL-UZ 171 are also acceptable).</li><li><em>ECMA-328 – Determination of Chemical Emission Rates from Electronic Equipment</em>.</li><li><em>UL 2819 – GREENGUARD Certification Program for Chemical and Particle Emissions for Electronic Equipment</em> (superseded revisions of this standard such as GGPS.003 are also acceptable).</li></ul><div data-gb-custom-block data-tag="hint" data-style="success" data-icon="dot" class="hint hint-success"><p><strong>Fitout scope</strong><br>Where there are fitout works excluded from the rating, sources of pollutants being delivered comply with the requirements. Minimum emissions are included in a tenancy fitout guide and model lease clauses for tenants.</p></div></td></tr><tr><td>Exhausting pollutants</td><td><p>Pollutants are exhausted directly to the outside of the project in accordance with <em>AS 1668.2:2024</em>, <em>AS 1668.4:2024</em> and/or physically separated from occupants.</p><div data-gb-custom-block data-tag="hint" data-style="success" data-icon="dot" class="hint hint-success"><p><strong>Fitout scope</strong><br>Where there are fitout works excluded from the rating, the base building systems account for sources of pollutants based on the anticipated use of the tenanted spaces. Requirements that align with the project team's assumptions are included in a tenancy fitout guide and model lease clauses for tenants<mark style="background-color:$info;">.</mark></p></div></td></tr></tbody></table>

### <mark style="color:$success;">Credit Achievement</mark>

In addition to *Minimum Expectation*, the project must comply with **both** of the following criteria:

* Ventilation Systems Attributes
* Provision of Outdoor Air

#### 11.1.1 Ventilation System Attributes

The building's ventilation system has adequate access to both sides of all moisture and debris-catching components for maintenance within the air distribution system in 95% of the regularly occupied areas.

Where it is demonstrated that it is not possible to provide access to both sides for cleaning and maintenance purposes (e.g., ducted split system fan coil units (DX split/VRF/VRV)), the system:

* Has access to the upstream side of fan coil units where the coils are protected by a filter rated at MERV 8 or F5 or higher
* Provides one of the following:
  * Heating only.
  * Cooling only where the coil assembly is no more than 4 rows deep.
  * Dual heating and cooling where the coil assembly no more than 4 rows deep.
* Where fan coil units or air handling units are located within a ceiling void, one of the following is provided:
  * Access panels in unit / ductwork that are near the coil to be cleaned.
  * Access panels in the ceiling below the unit that are near the unit / ductwork access panel.
  * The upstream surface of the coil is accessible within 1m of the ceiling panel.

Where a wall-mounted unit is installed, the unit has:

* Access to one side of the coil for cleaning and maintenance purposes;
* A filter system that is equivalent to a MERV 8 filter; and
* A coil assembly is no more than 4 rows deep.

Where the base building design requires [tenant supplementary systems to install](#user-content-fn-3)[^3] moisture or debris generating components (e.g., chilled beams, fan coil units or heating coils within VAV boxes) this criteria cannot be claimed.

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
This applies to base building systems only. Tenant supplementary systems where the design, maintenance and ownership are determined and controlled by the tenant can be excluded. Refer *Guidance* for further information on determining this.
{% endhint %}

#### 11.1.2 Provision of Outdoor Air

The building provides a high level of effective outdoor air in 95% of the regularly occupied areas. Project teams may choose from at least one of the following pathways relevant to the project's building class space type. Mixed use projects, where more than 20% of the GFA, excluding car parks, is not the predominant building type, may be required to comply with more than one pathway.

<table><thead><tr><th width="186.5">Pathway</th><th>Requirement</th></tr></thead><tbody><tr><td>Class 2 and 3</td><td><p>Effective outdoor air is provided by one of the following:</p><ul><li><strong>Mechanical ventilation</strong> where there is a 50% improvement of outdoor air required by <em>AS1668.2:2024</em> to regularly occupied, habitable rooms for the default occupancy.</li><li><strong>Natural ventilation</strong> that is supplemented by a mechanical ventilation system that delivers outdoor air to habitable rooms via a continuous, intermittent or demand-controlled mechanism.<br>The minimum design supply airflow rate of the system is:<br>Q = 0.075A + 3.5(N<sub>b</sub> + 1)<br><br>Where<br>A = total internal area of the sole-occupancy unit<br>N<sub>b</sub> = number of bedrooms or 0.5 of a studio<br>Q = minimum design supply airflow rate<br>The airflow rate per m2 (i.e.. Q/A) is no less than 0.2L/s/m<sup>2</sup>.<br>For bedrooms, the minimum design supply airflow rate is the greater between Q and 3.5L/s.<br>The ventilation system has at minimum a F5 grade filter.</li><li><strong>Mixed mode ventilation</strong> that meets the requirements for natural ventilation when the mechanical system is not in use and the requirements for mechanical ventilation when the mechanical system is in use.</li></ul></td></tr><tr><td>All other building classes</td><td><p>Effective outdoor air is provided by one of the following:</p><ul><li><strong>Mechanical ventilation</strong> where there is a 100% improvement of outdoor air required by <em>AS 1668.2:2024</em> to regularly occupied areas based on the design occupancy. Demand controlled ventilation may be used.</li><li><strong>Natural ventilation</strong> where there is a 50% improvement of outdoor air required by <em>AS 1668.4:2024</em> to regularly occupied areas based on the design occupancy.</li><li><strong>Mixed mode ventilation</strong> that meets the requirements for natural ventilation when the mechanical system is not in use and the requirements for mechanical ventilation when the mechanical system is in use.</li></ul></td></tr><tr><td>Performance based approach</td><td>CO<sub>2</sub> sensors are provided to continuously monitor CO<sub>2</sub> levels within the breathing zone and are linked to controls to adjust the amount of effective outdoor air to each space to maintain CO<sub>2</sub> levels at or less than 700ppm within each space in the regularly occupied areas at all times in the default occupancy period. CO<sub>2</sub> sensors are located within the breathing zone to ensure accurate representative readings of CO<sub>2</sub> concentrations with at least one in each individually controlled supply air zone and every enclosed space. The location of the sensors is justified by a qualified mechanical engineer.</td></tr><tr><td>Equivalent clean airflow approach</td><td>The minimum Equivalent Clean Airflow (ECAi) per person as outlined in Table 5-1 in <em>ASHRAE Standard 241:2023 – Control of Infectious Aerosols</em> is permanently provided. The ECAi meets the safety and performance requirements within Section 7 and Appendix A of <em>ASHRAE Standard 241:2023</em>. A Building Readiness Plan, as mentioned in <em>ASHRAE 241</em>, is not required.<br><br>Where compliance with the Equivalent clean airflow approach pathway in <em>Credit Achievement</em> is demonstrated, the Provision of Outdoor Air in <em>Minimum Expectation</em> is considered met.</td></tr></tbody></table>

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
Tenant supplementary systems where the design, maintenance and ownership are determined and controlled by the tenant can be excluded. The base building systems account for the anticipated use and design occupancy that includes the tenanted spaces.
{% endhint %}

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#default-occupancy)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#default-occupancy-period)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#design-occupancy)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#ducted-fan-coil-units)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#habitable-room)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#regularly-occupied-area)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#qualified-mechanical-engineer)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#ventilation)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**Separation from pollutants for Class 2 and Class 3 spaces**\
The separation from pollutants for Class 2 and Class 3 buildings table is an increase above *Table 3.5 in AS 1668.2:2024*. *Table 5-1 in ASHRAE 62.1:2022* is considered too stringent, and thus not appropriate for local Class 2 and Class 3 building context. The minimum separation distances requirements for Class 2 and Class 3 buildings provides appropriate best practice targets between Australian Standards and ASHRAE.

**Tenant supplementary systems**\
For further guidance regarding tenant supplemental systems refer to the most current version of NABERS' *Energy and Water for Offices Rules* to determine base building and tenant allocation. Where NABERS assesses a system as a tenant load, these systems can be excluded from the credit, where NABERS assesses a system as base building, these systems must be shown to be compliant for the credit to be awarded. Systems which are excluded for the purposes of a NABERS base building rating may also be excluded for this credit.

**Recognised standard**\
Where another recognised standard is proposed, a Technical Question may be submitted to the GBCA for confirmation. Project teams are to explain why the proposed standard is equivalent to those listed in the credit requirements.

**Provision of outdoor air for Class 2 and 3 space by natural ventilation**\
Make-up air systems that provide effective outdoor air to any habitable rooms may be counted towards the ventilation rates prescribed in the requirements (based on typical usage assumptions), provided that their flow path is defined and clearly passes through the habitable space(s) before being exhausted.

For Class 2 spaces, where the supplementary mechanical ventilation system operates intermittently, it is controlled with a timer.

**Excluded spaces**\
Below are some examples of spaces that can be typically excluded for different criteria. If the project has other types of spaces where the function justifies specific ventilation conditions, a Technical Question may be submitted to the GBCA for confirmation to be excluded.

*Exhaust or Elimination of Pollutants*\
Example of spaces that can be excluded include kitchenette and tea preparation areas that do not require local exhaust in accordance with Clause 3.3.1 in *AS 1668.2:2024.*

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

* Mechanical drawings for each ventilated space with annotations highlighting compliance with targeted criteria (i.e. separation distances, CO<sub>2</sub> sensor locations, supply air zones, access for cleaning etc.).
* For naturally ventilated buildings, provide drawings of openings and opening schedule.
* Extracts from the ventilation system specification for each system.
* Extracts from equipment specifications highlighting emissions.
* Certificates demonstrating compliance with emissions standards.
* Extracts from the Environmental Management Plan that specify ventilation cleaning.
* Extract from the Commissioning Report demonstrating that the HVAC and CO<sub>2</sub> monitoring systems are operating as intended. For naturally ventilated areas, this is only relevant where automation systems and the like are included.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources supporting this credit:

* ACR 2021 – The NADCA Standard for Assessment, Cleaning and Restoration of HVAC Systems.
* AS1668.2:2024 – The use of ventilation and air-conditioning in buildings – Part 2: Mechanical ventilation in buildings
* AS1668.4:2024 – The use of ventilation and air-conditioning in buildings – Part 4: Natural Ventilation of buildings
* ASHRAE Standard 241:2023 – Control of Infectious Aerosols
* ASHRAE Standard 62.1:2022 – Ventilation for Acceptable Indoor Air Quality
* DE-UZ 219 – Blue Angel for Office Equipment with Printing Function
* ECMA-328 – Determination of Chemical Emission Rates from Electronic Equipment
* NABERS – [Energy and Water for Offices Rules](https://www.nabers.gov.au/publications/nabers-energy-and-water-offices-rules)
* SMACNA – IAQ Guidelines for Occupied Buildings under Construction
* UL 2819 – GREENGUARD Certification Program for Chemical and Particle Emissions for Electronic Equipment

[^1]: **18/11/26**\
    Ad-hoc: Corrected from "1" to "N/A" to align with FAQ F-00443.

[^2]: **18/11/2026**\
    Ad-hoc: Statement removed and incorporated into table above to align with FAQ F-00443.

[^3]: **18/11/26**\
    Ad-hoc: Clarification that this requirement applies to tenant supplementary systems.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/healthy-3/11-or-clean-air.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.