> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/healthy-3/14-or-exposure-to-toxins.md).

# 14 | Exposure to Toxins

Points: 2

## <mark style="color:$primary;">Outcome</mark>

The building's occupants are not directly exposed to toxins in the spaces they spend time in.

## <mark style="color:$primary;">Criteria</mark>

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-14.0.1-paints-adhesives-sealants-and-carpets](#id-14.0.1-paints-adhesives-sealants-and-carpets "mention")**:** The building's paints, adhesives, sealants, and carpets are low in toxins or non-toxic.
* [#id-14.0.2-engineered-wood-products](#id-14.0.2-engineered-wood-products "mention")**:** The building's engineered wood products are low in toxins or non-toxic.
* [#id-14.0.3-banned-or-highly-toxic-materials](#id-14.0.3-banned-or-highly-toxic-materials "mention")**:** Occupants are not exposed to banned or highly toxic materials in the building.

<mark style="color:$success;">**Credit Achievement — 2 points**</mark>

In addition to *Minimum Expectation:*

* [#id-14.1.1-voc-and-formaldehyde-levels](#id-14.1.1-voc-and-formaldehyde-levels "mention")**:** On-site tests verify the building has low Volatile Organic Compounds (VOC) and formaldehyde levels.

***

## <mark style="color:$primary;">Additional information</mark>

#### Scope of credit

All fully enclosed covered areas of the project excluding car parks.

**Banned or Highly Toxic Materials**\
All existing buildings within the project boundary at the time of site purchase that are being retained.

#### Stage implementation

Strategy | Brief | Concept | **Design** | **Tender** | **Construction** | **Handover** | Use

#### Synergies with other credits

* Amenity and Comfort
* Responsible Finishes

#### Sustainable Development Goals

* **Goal 3:** Good Health and Wellbeing

***

## <mark style="color:$primary;">Requirements</mark>

Where standards are cited for compliance, the latest version applies once it has been in place for over two years.

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all three** of the following criteria:

* Paints, Adhesives, Sealants, and Carpets
* Engineered Wood Products
* Banned or Highly Toxic Materials

#### 14.0.1 Paints, Adhesives, Sealants, and Carpets

Toxins are limited in at least 95% of all internally applied paints, adhesives, sealants (by volume) and carpets (by area). Project teams must choose from at least one of the following pathways. A combination of methods can be used to demonstrate compliance to suit different spaces or products:

{% tabs %}
{% tab title="Eliminating toxin sources" %}

### Eliminating toxin sources

No paints, adhesives, sealants, and carpets are installed.
{% endtab %}

{% tab title="Recognised certification scheme" %}

### Recognised certification scheme

The product(s) are certified under a Recognised Product Certification Scheme listed in the GBCA's Exposure to Toxins Product Certifications Schemes Index. The certification is valid at the time of purchase.
{% endtab %}

{% tab title="Labratory Analysis" %}

### Laboratory Analysis

The product(s) have a Total Volatile Organic Compounds (TVOC) content less the limits below.

**Paints, adhesives and sealants**

<table data-search="false"><thead><tr><th>Product category</th><th>TVOC content (g/L)</th></tr></thead><tbody><tr><td>General purpose adhesives and sealants</td><td>50</td></tr><tr><td>Interior wall and ceiling paint, all sheen levels</td><td>16</td></tr><tr><td>Trim, varnishes, and wood stains</td><td>75</td></tr><tr><td>Primers, sealers, and prep coats</td><td>65</td></tr><tr><td>One and two pack performance coatings for floors</td><td>140</td></tr><tr><td>Acoustic sealants, architectural sealant, waterproofing membranes and sealant, fire retardant sealants and adhesives</td><td>250</td></tr><tr><td>Structural glazing adhesive, wood flooring and laminate adhesives and sealants</td><td>100</td></tr></tbody></table>

TVOC content in paints are determined in accordance with *ISO 11890-1, ISO 11890-2, ISO 17895* or *ASTM D3960*. TVOC content in adhesive and sealants are determined in accordance with ASTM D3960. Refer Guidance for further information.

**Carpets**

| Compliance option                      | Test protocol                                             | TVOC Limit   |
| -------------------------------------- | --------------------------------------------------------- | ------------ |
| ASTM D5116                             | ASTM D5116 - TVOC limit                                   | 0.5mg/m2/hr  |
| ASTM D5116                             | ASTM D5116 - 4-PC (4-Phenylcyclohexene)                   | 0.05mg/m2/hr |
| ISO 16000 / EN 13419                   | ISO 16000 / EN 13419 - TVOC at three days                 | 0.5mg/m2/hr  |
| ISO 10580 / ISO/TC 219 (Document N238) | ISO 10580 / ISO/TC 219 (Document N238) - TVOC at 24 hours | 0.5mg/m2/hr  |

Refer *Guidance* for excluded products.

Where *Credit Achievement* is demonstrated using the Laboratory testing or Building monitoring methods, evidence of the *Minimum Expectation* may be reduced. This is not applicable to projects that use the Real-time measurements method. Refer *Guidance* and *Submission content* for further information.
{% endtab %}
{% endtabs %}

#### 14.0.2 Engineered Wood Products

Toxins are limited in at least 95% (by area) of engineered wood products. Project teams may choose from at least one of the following pathways. A combination of methods can be used to demonstrate compliance to suit different spaces or products:

{% tabs %}
{% tab title="Eliminating toxin sources" %}

### Eliminating toxin sources

No engineered wood products are installed.
{% endtab %}

{% tab title="Recognised certification scheme" %}

### Recognised certification scheme

The product(s) are certified under a Recognised Product Certification Scheme listed in the GBCA's Exposure to Toxins Product Certifications Schemes Index. The certification is valid at the time of purchase.
{% endtab %}

{% tab title="Laboratory testing" %}

### Laboratory Analysis

The product(s) are tested and the formaldehyde emissions are less than the limits below:

<table data-search="false"><thead><tr><th width="470">Test protocol</th><th>Formaldehyde Emissions Limit</th></tr></thead><tbody><tr><td>AS/NZS 2269, testing procedure AS/NZS 2098.11 method 10 for Plywood</td><td>≤1mg/L</td></tr><tr><td>AS/NZS 1859.1 - Particle Board, with use of testing procedure AS/NZS 4266.16 method 16</td><td>≤1.5mg/L</td></tr><tr><td>AS/NZS 1859.2 - MDF, with use of testing procedure AS/NZS 4266.16 method 16</td><td>≤1mg/L</td></tr><tr><td>AS/NZS 4357.4 - Laminated Veneer Lumber (LVL)</td><td>≤1mg/L</td></tr><tr><td>Japanese Agricultural Standard MAFF Notification No.701 Appendix Clause 3 (11) - LVL</td><td>≤1mg/L</td></tr><tr><td>JIS A 5908 - Particle Board and Plywood, with use of testing procedure JIS A 1460</td><td>≤1mg/L</td></tr><tr><td>JIS A 5905 - MDF, with use of testing procedure JIS A 1460</td><td>≤1mg/L</td></tr><tr><td>JIS A1901 (not applicable to Plywood, applicable to high pressure laminates and compact laminates)</td><td>≤0.1mg/m2/hr</td></tr><tr><td>ASTM D5116 (applicable to high pressure laminates and compact laminates)</td><td>≤0.1mg/m2/hr</td></tr><tr><td>ISO 16000 part 9, 10 and 11 (also known as EN 13419), applicable to high pressure laminates and compact laminates</td><td>≤0.1mg/m2/hr (at 3 days)</td></tr><tr><td>ASTM D6007 (Refer Guidance for further information)</td><td>≤0.12mg/m³</td></tr><tr><td>ASTM E1333 (Refer Guidance for further information)</td><td>≤0.12mg/m³</td></tr><tr><td>EN 717-1 (also known as DIN EN 717-1)</td><td>≤0.12mg/m3</td></tr><tr><td>EN 717-2 (also known as DIN EN 717-2)</td><td>≤3.5mg/m²/hr</td></tr></tbody></table>

Refer *Guidance* for excluded products.

Where *Credit Achievement* is demonstrated using the Laboratory testing or Building monitoring methods, evidence of the *Minimum Expectation* may be reduced. This is not applicable to projects that use the Real-time measurements method. Refer *Guidance* and *Submission content* for further information.
{% endtab %}
{% endtabs %}

#### 14.0.3 Banned or Highly Toxic Materials

A comprehensive hazardous materials survey is carried out on any existing buildings or structures on the project site, in accordance with the relevant Environmental and Work Health and Safety (WHS) legislation.

Where the survey identified asbestos, lead, or polychlorinated biphenyls (PCBs) in any existing buildings or structures, the materials are stabilised or removed and disposed of in accordance with best practice guidelines. Refer *Guidance* for suggested guidelines.

Projects that do not have existing buildings on the site at the time of purchase or are not retaining any existing buildings on the site are exempt from the *Banned or Highly Toxic Materials* criterion.

### <mark style="color:$success;">Credit Achievement</mark>

In addition to *Minimum Expectation*, the project must comply with the following criterion:

* VOC and Formaldehyde Levels

#### 14.1.1 VOC and Formaldehyde Levels

Toxin levels are verified on-site after practical completion and prior to occupants moving into the building.

#### *Verification methods*

TVOC and formaldehyde levels are verified by one of the following methods:

<table><thead><tr><th width="225.25">Method</th><th>Requirements</th></tr></thead><tbody><tr><td>Laboratory testing</td><td><p>Laboratory tests are conducted to verify that the concentrations are below the following limits:</p><ul><li><strong>Benzene</strong>: 0.002ppm</li><li><strong>Toluene</strong>: 0.08ppm</li><li><strong>Formaldehyde:</strong> 0.02ppm</li></ul><p>Samples are collected and analysed in accordance <em>ISO 16000-6, ASTM D5197</em> or <em>EPA TO-17.</em></p></td></tr><tr><td>Building monitoring</td><td><p>Air quality monitors that measure TVOC and formaldehyde are installed. Measurements are taken prior to building occupation to verify that the concentrations are below the following limits:</p><ul><li><strong>TVOC</strong>: 0.27ppm (as isobutylene)</li><li><strong>Formaldehyde</strong>: 0.02ppm</li></ul><p>The monitors continuously measure for TVOCs and formaldehyde within the breathing zone and are located away from openings or HVAC vents.</p></td></tr><tr><td>Real-time measurements (for small buildings only where the GFA, excluding car parks, is less than 1000m2)</td><td><p>Real-time measurements are to be taken to verify that the concentrations are below the following limits:</p><ul><li><strong>TVOC</strong>: 0.27ppm (as isobutylene)</li><li><strong>Formaldehyde</strong>: 0.02ppm</li></ul><p>Measurements are taken using equipment that complies with Section 6.5 Real-time monitoring and sampling equipment in the <em>NABERS Indoor Environment for Offices Rules</em>. A sample is considered an average reading of at least 5 minutes in the same location.</p></td></tr></tbody></table>

Sampling is conducted before 12pm and under normal operating conditions. Refer *Definitions* for further information.

#### *Sample distribution*

Project teams may choose from one of the following pathways to determine the minimum number of samples to be taken based on the building's height to width ratio:

{% tabs %}
{% tab title="Low height to width ratio" %}
*(e.g., warehouse-type or shopping centre projects)*

| GFA                                      | Number of samples per floor |
| ---------------------------------------- | --------------------------- |
| < 10,000m2                               | 3                           |
| For every additional 10,000m2 thereafter | 1 additional sample         |
| {% endtab %}                             |                             |

{% tab title="High height to width ratio " %}
*(e.g., all other building types)*
{% endtab %}
{% endtabs %}

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#normal-operating-conditions)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#voc-test-certificate)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**Excluded products**\
The following items are excluded from the scope of Paints, Adhesives, Sealants, and Carpets criterion:

* Glazing film, tapes, and plumbing pipe cements;
* Paints, adhesives and sealants applied off-site, for example, applied to furniture items in a manufacturing site and later installed in the fitout; and
* Adhesives and mastics used for temporary formwork and other temporary installations.

The following items are excluded from the scope of Engineered Wood Products criterion:

* Non-engineered wood products, such as milled timber
* Formwork

**Testing protocols**\
Paints\
The most relevant standard varies depending on the VOC content:

* ISO 17895:2024, for a material with a presumed VOC content <1%
* ISO 11890-2:2020, for a material with a presumed VOC content <15%
* ISO 11890-1:2024, for a material with a presumed VOC content >15%

ASTM D3960, which is comprised of four individual testing procedures that measures TVOC (D2369) as well as density (D1475) and water content (D4017). Exempt compounds (D4457) must not be subtracted in the calculation of VOC content.

Adhesives and sealants\
The testing method for adhesive and sealants is the ASTM D3960 as detailed for paints. For more information on ASTM D3960, refer to South Coast Air Quality Management District Rule 1168.

Carpets\
Products that have been tested in accordance with the California Department of Public Health (CDPH) Standard Method v1.2-2017 using the private office scenario are accepted as they comply with the ASTM D5116 test protocol.

Engineered wood products\
Products that use ASTM D6007 and ASTM E1333 will be required to convert the final results into a EN717-1 equivalent (i.e.. in mg/m3) using a correlation ratio of 0.98.

Theoretical VOC calculations\
Paints, sealants and adhesives that are one of the following may use theoretical calculations:

* A custom product such as, but not limited to, paints with a custom tint or two part adhesives combined and applied on site.
* Not used for more than 10% of the internally applied areas.

The theoretical calculation methodology is to follow APAS AP-D181 7.1 whereby it is based on the subtotal of the known VOC values of the product's raw material components. The calculations provided are to include the following:

* Numerical TVOC results expressed in g/litre of product; and
* Statement that the results have been obtained based on the subtotal of the known TVOC values of the product's raw ingredients.

**Lead, asbestos, and PCBs**\
In the case of a refurbishment, the Banned or Highly Toxic Materials criterion is exempt for projects where the existing building on the project site began construction after 1 January 2005. This includes projects that are refurbishments or building extensions of existing buildings for which construction started after 1 January 2005. The use of the hazardous materials targeted by this credit element have been banned in Australia for several years, so this topic presents no environmental benefit to new buildings.

Relevant standards and legislation

<table><thead><tr><th width="199">Hazardous materials</th><th>Relevant Standards and Legislation</th></tr></thead><tbody><tr><td>Asbestos</td><td>Occupational Health and Safety (OH&#x26;S) legislation, Work Health and Safety (WH&#x26;S) legislation and relevant environmental legislation</td></tr><tr><td>Lead</td><td>AS/NZS 4361.1:2017 and AS/NZS 4361.2:2017: Guide to Hazardous Lead Paint Management</td></tr><tr><td>Polychlorinated Biphenyls (PCBs)</td><td>ANZECC Polychlorinated Biphenyls Management Plan</td></tr></tbody></table>

**VOC emission testing**\
To mitigate the risk of failing the VOC on-site test, it is recommended that projects specify products that have undergone an emissions test in accordance with the following Standards:

* ANSI/BIFMA e3-2011 Furniture Sustainability Standard sections 7.6.1 or 7.6.2, tested in accordance with ANSI/BIFMA Standard Method M7.1-2011
* California Department of Public Health (CDPH) Standard Method v.1.2-2017
* EPA Method TO11 Determination of Formaldehyde in Ambient Air using Adsorbent Cartridge Follow by High Performance Liquid Chromatography (HPLC)
* GEV-Emicode EC1 or EC1 Plus after 28 days

**Earliest stage for on-site testing**\
For the purposes of the *Credit Achievement*, testing can occur once all finishes and furniture have been installed.

Project teams wanting to use NABERS IE results to demonstrate compliance with the credit should submit a Technical Question to the GBCA.

**Real-time measurements**\
All sample measurements taken must be below the levels listed above.

**Evidence for&#x20;*****Minimum Expectation***\
Where *Credit Achievement* is demonstrated using the Laboratory testing or Building monitoring methods, evidence provided for the *Minimum Expectation* may be reduced to the following:

* A summary table with products used in the project and their compliance e.g., VOC content of each product and whether they comply with the required limits.
* Head contractor sign-off on the summary table that these were the products used for the project, and that the emissions limits were reviewed.

This is not applicable to projects that use the Real-time measurements method.

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

**Paints, Adhesives, Sealants and Carpets and Engineered Wood Products**

* Specifications that demonstrate emission levels or formaldehyde contents.
* Safety Data Sheets that demonstrate the compliant emission levels or formaldehyde content.
* Product VOC test certificates that demonstrate emission levels or formaldehyde contents.
* Product certificates that demonstrate certification under a recognised product certification scheme or recognised standard.
* Invoices or proof of purchase.
* Finishes schedule or similar summarising all paints, adhesives, sealants, carpets, engineered wood products and carpets installed.

Where *Credit Achievement* demonstrated using the Laboratory testing or Building monitoring methods, evidence provided for the *Minimum Expectation* may be the following:

* A summary table with products used in the project and their compliance e.g., VOC content of each product and whether they comply with the required limits.
* Head contractor sign-off on the summary table that these were the products used for the project, and that the emissions limits were reviewed.

**Banned or Highly Toxic Materials**

* Hazardous materials survey.
* Remediation plan.
* Site plan at the time of purchase.

**VOC and Formaldehyde Levels**

* On-site VOC test results.
* As built drawings showing the location of the test samples.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* GBCA - Exposure to Toxins Product Certification Scheme Index (available on the Green Star resources portal)


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/healthy-3/14-or-exposure-to-toxins.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.