> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/22-or-energy-source.md).

# 22 | Energy Source

Points: 4

## <mark style="color:$primary;">Outcome</mark>

The building is fossil fuel free, powered by renewables and designed to maximise renewable grid interaction.

### <mark style="color:$primary;">Climate Positive Pathway</mark>

<table data-search="false"><thead><tr><th>Registration</th><th width="134">Star rating</th><th>Requirement</th></tr></thead><tbody><tr><td rowspan="3">Registering from 2025 onwards</td><td>4 Star</td><td rowspan="2">Meets <em>Minimum Expectation</em></td></tr><tr><td>5 Star</td></tr><tr><td>6 Star</td><td>Meets <em>Credit Achievement</em></td></tr><tr><td rowspan="3">Registering from 2028 onwards</td><td>4 Star</td><td>Meets <em>Minimum Expectation</em></td></tr><tr><td>5 Star</td><td rowspan="2">Meets <em>Credit Achievement</em></td></tr><tr><td>6 Star</td></tr><tr><td rowspan="3">Registering from 2030 onwards</td><td>4 Star</td><td rowspan="3">Meets <em>Credit Achievement</em></td></tr><tr><td>5 Star</td></tr><tr><td>6 Star</td></tr></tbody></table>

## <mark style="color:$primary;">Pathways</mark>

There are two pathways currently available in this credit. Projects can choose from one of the following based on their building type:

* **Pathway A: Owner Operated pathway** – Available to buildings where the building owner retains control over the majority of base building energy use and infrastructure. This includes buildings where the owner is responsible for managing, monitoring, and procuring energy for services such as heating, cooling, lighting, and hot water, and can implement energy strategies directly.
* **Pathway B: Tenant Operated pathway** – Available to buildings where the tenant/s have signed a lease agreement that makes them responsible for managing, monitoring and use of up to 80% of the GFA. This may include Class 2 apartments, Class 3 hotels and student accommodation and Class 5 offices.
* **Pathway C: Industrial pathway** – In development; this pathway will be available in future.

## <mark style="color:$primary;">Criteria</mark>

#### ***Pathway A: Owner Operated pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23a.0.1-all-electric-building-services](#id-23a.0.1-all-electric-building-services "mention")**:** The building is all-electric and has no infrastructure for fossil fuels for hot water, space heating and cooking.
* [#id-23a.0.2-remaining-emissions-roadmap](#id-23a.0.2-remaining-emissions-roadmap "mention")**:** If there are other uses of fossil fuels, a roadmap is provided to eliminate these.

<mark style="color:$success;">**Credit Achievement — 2 points**</mark>

In addition to Minimum Expectation:

* [#id-23a.1.1-renewable-ready](#id-23a.1.1-renewable-ready "mention")**:** The building has management systems and a strategy to shift its electricity consumption to utilise grid energy when there are more renewables.

or

* [#id-23a.1.2-renewable-electricity](#id-23a.1.2-renewable-electricity "mention")**:** 100% of the electricity under the building owner's control comes from renewables.

<mark style="color:$success;">**Exceptional Performance — 2 points**</mark>

In addition to Credit Achievement, the project meets both of the following::

* [#id-23a.2.1-renewable-ready](#id-23a.2.1-renewable-ready "mention")**:** The building has management systems and a strategy to shift its electricity consumption to utilise grid energy when there are more renewables.
* [#id-23a.2.2-renewable-electricity](#id-23a.2.2-renewable-electricity "mention")**:** 100% of the electricity under the building owner's control comes from renewables.

#### ***Pathway B: Tenant Operated pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23b.0.1-all-electric-building-services](#id-23b.0.1-all-electric-building-services "mention")**:** The building is all-electric and has no infrastructure for fossil fuels for hot water, space heating and cooking.
* [#id-23b.0.2-remaining-emissions-roadmap](#id-23b.0.2-remaining-emissions-roadmap "mention")**:** If there are other uses of fossil fuels, a roadmap is provided to eliminate these.

<mark style="color:$success;">**Credit Achievement — 2 points**</mark>

In addition to Minimum Expectation:

* [#id-23b.1.1-renewable-ready](#id-23b.1.1-renewable-ready "mention")**:** The building has management systems and a strategy to shift its electricity consumption to utilise grid energy when there are more renewables.
* [#id-23b.1.2-renewable-electricity](#id-23b.1.2-renewable-electricity "mention")**:** 100% of the electricity under the building owner's control comes from renewables.

<mark style="color:$success;">**Exceptional Performance — 2 points**</mark>

In addition to Credit Achievement:

* [#id-23b.2.1-tenant-engagement](#id-23b.2.1-tenant-engagement "mention")**:** The building owner engages with tenants to source renewable energy.

#### ***Pathway C: Industrial pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

In development

<mark style="color:$success;">**Credit Achievement — 2 points**</mark>

In development

<mark style="color:$success;">**Exceptional Performance — 2 points**</mark>

In development

***

## <mark style="color:$primary;">Additional information</mark>

#### Scope of this credit

All energy under the control of the building owner and all non-electricity energy provided for uses that are not under the building owner's control (e.g., tenant use for hot water, space heating and cooking). Electricity use for tenant loads is excluded.

#### Stage implementation

Strategy | **Brief** | **Concept** | **Design** | **Tender** | Construction | Handover | Use

#### Synergies with other Credits

* Verification and Handover
* Energy Use
* Grid Resilience
* Operations Resilience

#### Sustainable Development Goals

* **Goal 7:** Affordable and Clean Energy
* **Goal 13:** Climate Action

#### Relevant reporting initiatives

* GRESB
* Task Force on Climate-related Financial Disclosures **(TCFD)**

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

{% tabs %}
{% tab title="A: Owner Operated " %}

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **both** of the following criteria:

* All-electric Building Services
* Remaining Emissions Roadmap

#### 22A.0.1 All-electric Building Services

The building operates with no connection to or provision for fossil fuel infrastructure for any hot water, space heating and cooking uses by the base build or tenants.

Fossil fuel infrastructure for the following uses is excluded:

* Process loads
* Emergency power
* Laboratory equipment

Any fossil fuels used for:

* Process loads are addressed in the [Remaining Emissions Roadmap](https://greenstarresources.gbca.au/pages/vqD8Vh2UQ7bnU6H3SxjN#id-23a.0.2-remaining-emissions-roadmap).
* Emergency power is used in emergency situations only, is less than 1% of the total building energy consumption and is offset for the first five years of operation.
* Laboratory equipment is less than 1% of the total building energy consumption and is offset for the first five years of operation.

#### 22A.0.2 Remaining Emissions Roadmap

Where there are fossil fuels used for process loads, a Remaining Emissions Roadmap for the building is developed. The Roadmap covers the consumption, procurement, and generation of process loads under the control of the building owner and infrastructure for non-building owner process loads.

The Roadmap identifies:

* Alternative fossil fuel free options for process loads that use fossil fuels. Where viable fossil fuel free options are not known, consideration is given to hydrogen and biofuels.
* Changes that are required to be undertaken to the identified alternative fossil fuel free options. This includes spatial considerations and physical interventions.
* A pathway with estimated timeframes to transition to the alternative fossil fuel free options including strategies to incentivise current tenants if there are fossil fuels used for tenant process loads.
* Strategies to encourage fossil fuel free options to be adopted by future tenants.
* A target date for the building to be fossil fuel free.

The Roadmap is signed off by the building owner prior to the construction phase of the project and included in the operations and maintenance information provided to the building owner.

Where there are no fossil fuels user for process loads, projects are exempt from the *Remaining Emissions Roadmap* criterion.

### <mark style="color:$success;">Credit Achievement</mark>

In addition to *Minimum Expectation*, the project must comply with **one** of the following criteria:

* Renewable Ready
* Renewable Electricity

#### 22A.1.1 Renewable Ready

#### *Energy Management and Information Systems*

The building has real-time energy management and information systems that sets up the building to be grid interactive.

As a minimum, the system can:

* Monitor the local electricity network's demand and greenhouse gas (GHG) emissions intensity (≤ 15-minute intervals) to allow for an appropriate and timely demand response.
* Measure, process and report on energy used by all major energy uses of the building in ≤ 15-minute intervals.
* Report on GHG emissions based on the near real-time (≤ 15-minute intervals) carbon intensity of grid electricity supplies, in addition to the most recent electricity grid's average annual GHG emissions factors for the building's location published in the National Greenhouse Accounts Factors.
* Measure input and output energy and GHG emissions (calculated using 15-minute increment GHG emission factors) from systems that generate and/or store electricity, e.g., quantify emissions from the discharge of Battery Energy Storage Systems (BESS) by accounting for the time-varying emissions intensity of the electricity used for charging.
* Allow the building to automatically control different energy uses in the building to minimise GHG emissions and reduce peak demand.

#### *Load Shifting Strategy*

A strategy to shift at least 10% of the building's electricity consumption from a 3 hour period of high GHG emissions intensity in the grid to periods of low GHG emissions intensity is developed.

As a minimum, the strategy describes:

* The systems that contribute to shifting energy consumption.
* How each system shifts energy, how much it contributes towards the target and how it does not compromise occupant amenity or the functioning of the building. Detailed energy modelling is not required and contributions can be estimated by the project's building services engineers.
* The intended control strategy including whether any systems are linked directly to signals from the electricity network operator.

The strategy is included in the operations and maintenance information provided to the building owner.

#### 22A.1.2 Renewable Electricity

All energy under the control of the building owner is accounted for and sourced from renewables. Electricity use for tenant loads is excluded from this credit.

Both on-site or off-site renewables or a combination of both are acceptable.

Where the project team claims the credit through off-site renewables, a renewable energy contract is to be in place. The shortest contract length is:

* Three years
* One year, where the building is owned and managed by an entity that has signed to the Global Commitment for Net Zero Carbon Buildings managed by WorldGBC. Other commitments may be acceptable through a Technical Question.

The contract can be part of a corporate power purchasing agreement for a building portfolio.

Refer to the [*Climate positive buildings and our net zero ambitions*](https://gbca-web.s3.amazonaws.com/media/documents/climate-positive-buildings-net-zero-ambitions_Z3pcK5R.pdf) document for more information on suitable options recognised by Green Star.

The project's rating is valid provided the procurement of renewable electricity or energy continues. Should the building not continue to be powered by renewables, the building owner can no longer communicate the rating.

### <mark style="color:$success;">Exceptional Performance</mark>

In addition to *Credit Achievement*, the project must comply with **both** of the following criteria:

* Renewable Ready
* Renewable Electricity

#### 22A.2.1 Renewable Ready

Refer [*Credit Achievement* ](#id-23a.1.1-renewable-ready)for requirements

#### 22A.2.2 Renewable Electricity

Refer [*Credit Achievement*](#id-23a.1.2-renewable-electricity) for requirements.

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#laboratory-equipment)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#major-energy-uses)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#occupant-amenity)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#process-loads)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**Relationship with Grid Resilience**\
The requirements of this credit are intended to be complimentary to the [*Grid Resilience*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/resilient-2/21-or-grid-resilience.md) credit. Both credits take into consideration the changing landscape of the grid to one that will be made up of more renewables however the challenges and opportunities that arise are addressed differently.

The increase in renewables in the grid provides an opportunity for buildings to maximise their use of renewables. This is the opportunity that has influenced the *Energy Source* credit which aims to ensure the building has implemented systems and a load shifting strategy to set the building up to maximises the use of renewables.

Meanwhile the *Grid Resilience* credit focuses on the building's contribution to grid stability during operation to smooth out peaks in supply and demand and other related shocks. This is provided by buildings that are able to adjust their demand in response to the needs of the grid at a point in time. The same systems may contribute to demonstrating compliance with both credits however as the intent of the credit is different, the way the systems are used will be different.

**Emergency power**\
Emergency situations\
*AS/NZS 3009:1998* provides guidance on the areas and functions for which emergency power is required. If this exceeds 1% of the total building energy consumption, project teams should submit a Technical Question.

Calculating emissions\
For fire systems, diesel pumps and other emergency services that use fossil fuels, the amount of carbon emissions to be offset should be based on estimated fuel use from regular scheduled testing and predicted peak shaving events (where it is anticipated systems will be deployed for this use). The fuel-specific emissions factor from National Greenhouse Accounts factors published at the year of project registration (or any subsequent year by choice) is applied.

**Renewable electricity**\
The building is considered to have all of its electricity considered as renewables if the sum of all renewable energy generated on-site and off-site is equal to, or greater than, the total electricity use of the building annually.

**Market-based method and the renewable power percentage (RPP)**\
Project teams can claim the percentage of renewable energy in the grid (the RPP) as published by the Clean Energy Regulator at the date of Practical Completion of the building as off-site renewable energy supply.

For further information, refer <http://www.cleanenergyregulator.gov.au/RET/Scheme-participants-and-industry/the-renewable-power-percentage>

Projects located in ACT where the state government has purchased 100% Green Power can claim this as off-site renewable electricity.

**Renewable ready**\
The intent of the criteria is to set the building up to be able to load shift when needed. The project does not need to actively load shift however the capability is demonstrated.

**Near real-time greenhouse gas emissions**\
This information is available at [Open Electricity.](https://openelectricity.org.au/)

**Periods of emissions intensity in the grid**\
The following time periods can be assumed as high GHG emissions intensity:

* 6:00am to 9:30am
* 4:30pm to 8:00pm

Alternative timeframes can be proposed if the above time periods are not appropriate for the building type and/or building's electricity consumption profile.

The three hours of load shifting should occur during the normal operating hours of the building wherever possible (e.g., an office building operating from 8am to 6pm could have load shifting from 8:00am to 9.30am and 4.30pm to 6:00pm to 11:00am to 2:00pm)

**Contributing systems**\
Examples of systems that could contribute to load shifting include, but are not limited to, HVAC, domestic hot water and electric vehicle charging. On-site renewable generation and energy storage can also contribute to load shifting. Energy storage solutions may be electricity storage (e.g., batteries) or thermal storage (e.g., domestic hot water storage tanks, chilled water tanks).

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### **Recommended evidence**

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

**All-electric Building Services**

* As built drawings demonstrating the absence of fossil fuel systems and infrastructure.
* Evidence of support estimate of emergency power testing and peak shaving events.
* Evidence to support estimate of laboratory equipment usage.
* Evidence of purchase of offsets (e.g., contract) clearly showing the length of offset.

**Remaining Emissions Roadmap**

* Extract of operations and maintenance information of the Remaining Emissions Roadmap.
* Sign off from building owner.
* Evidence of no fossil fuels as process loads.

**Renewable Ready**

* Evidence that the energy management and information system has implemented the minimum system requirements.
* Extract of operations and maintenance information of the Load Shifting Strategy.

**Renewable Electricity**

* Signed energy contract or PPA or evidence of on-site generation.
* Public commitment to the Global Commitment for Net Zero Carbon Buildings managed by WorldGBC.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* CSIRO -[ Real-time carbon emissions intensity of the National Electricity Market](https://research.csiro.au/dch/access-data/)
* Department of Climate Change, Energy, the Environment and Water –[ National Greenhouse Accounts Factors](https://www.dcceew.gov.au/climate-change/publications/national-greenhouse-accounts-factors)
* Energy Efficiency Council – [Clean Energy Clean Demand](https://eec.org.au/publication/clean-energy-clean-demand/)
* GBCA - [From net zero to zero: A discussion paper on grid-interactive efficient buildings](https://new.gbca.org.au/case-studies/building/grid-interactive-efficient-buildings-paper/)
* [New Building Institute](https://newbuildings.org/gridoptimal-metrics-offer-guidance-on-optimizing-building-grid-interaction/)
* Open Electricity - [Open Electricity Tracker](https://explore.openelectricity.org.au/energy/nem/?range=7d\&interval=30m\&view=discrete-time\&group=Detailed)
  {% endtab %}

{% tab title="B: Tenant operated" %}

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **both** of the following criteria:

* All-electric Building Services
* Remaining Emissions Roadmap

#### 22B.0.1 All-electric Building Services

Refer to [*Minimum Expectation*](#id-23a.0.1-all-electric-building-services) in the *Energy Source – Owner Operated pathway* for requirements.&#x20;

#### 22B.0.2 Remaining Emissions Roadmap

Refer to [*Minimum Expectation*](#id-23a.0.2-remaining-emissions-roadmap) in the *Energy Source – Owner Operated pathway* for requirements.&#x20;

### <mark style="color:$success;">Credit Achievement</mark>

In addition to *Minimum Expectation*, the project must comply with both of the following criteria:

* Renewable Ready
* Renewable Electricity

#### 22B.1.1 Renewable Ready

#### *Energy Management and Information Systems*

Refer to [*Credit Achievement*](#id-23a.1.1-renewable-ready) in the *Energy Source – Owner Operated* pathway for requirements.&#x20;

#### *Load Shifting Strategy*

Refer to [*Credit Achievement*](#id-23a.1.1-renewable-ready) in the *Energy Source – Owner Operated* pathway for requirements.&#x20;

#### *Tenant engagement*

The building owner or the building management team actively engages with the tenants to participate in the building's load shifting strategy by including at least one of the following in all standard leasing agreements:

* Provide permission for tenant-controlled domestic hot water or HVAC systems to be controlled by the base building energy management system in a load shifting event.
* Commit to installing systems that can facilitate flexible demand.

The removal of the above from the leasing agreement is only done when the tenant proposes an alternative approach that meets a similar outcome.

#### 22B.1.2 Renewable Electricity

Refer to [*Credit Achievement*](#id-23a.1.2-renewable-electricity) in *Energy Source – Owner Operated* pathway for requirements.&#x20;

Projects that have no electricity under the control of the building owner are exempt from the *Renewable Electricity* criterion.

### <mark style="color:$success;">Exceptional Performance</mark>

In addition to *Credit Achievement,* the project must comply with the following criterion:

* Tenant Engagement

#### 22B.2.1 Tenant Engagement

The building owner or the building management team actively engages with the tenants to encourage the procurement of renewable electricity.

#### *Tenant engagement*

All standard leasing documents have a clause for tenants to procure 100% renewable electricity.

The building owner actively engages tenants during lease negotiations to propose a renewable electricity option. The removal of any provisions related to procurement of renewable electricity is only done at the tenant's request after the building owner has exhausted all options to provide them with a renewable electricity solution.

#### *Energy source information*

The building owner has mechanisms in place to collect information from building tenants on their type of energy sources. This can be through leasing requirement for tenants to disclose their annual energy consumption and energy source data.

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#occupant-amenity)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**Relationship with Grid Resilience**\
The requirements of this credit are intended to be complimentary to the [*Grid Resilience*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/resilient-2/21-or-grid-resilience.md) credit. Both credits take into consideration the changing landscape of the grid to one that will be made up of more renewables however the challenges and opportunities that arise are addressed differently.

The increase in renewables in the grid provides an opportunity for buildings to maximise their use of renewables. This is the opportunity that has influenced the *Energy Source* credit which aims to ensure the building has implemented systems and a load shifting strategy to set the building up to maximises the use of renewables.

Meanwhile the Grid Resilience credit focuses on the building's contribution to grid stability during operation to smooth out peaks in supply and demand and other related shocks. This is provided by buildings that are able to adjust their demand in response to the needs of the grid at a point in time. The same systems may contribute to demonstrating compliance with both credits however as the intent of the credit is different, the way the systems are used will be different.

**Periods of emissions intensity in the grid**\
The following time periods can be assumed as high GHG emissions intensity:

* 6:00am to 9:30am
* 4:30pm to 8:00pm

Alternative timeframes can be proposed if the above time periods are not appropriate for the building type and/or building's electricity consumption profile.

The three hours of load shifting should occur during the normal operating hours of the building wherever possible (e.g., an office building operating from 8am to 6pm could have load shifting from 8:00am to 9.30am and 4.30pm to 6:00pm to 11:00am to 2:00pm)

**Contributing systems**\
Examples of systems that could contribute to load shifting include, but are not limited to, HVAC, domestic hot water and electric vehicle charging. On-site renewable generation and energy storage can also contribute to load shifting. Energy storage solutions may be electricity storage (e.g., batteries) or thermal storage (e.g., domestic hot water storage tanks, chilled water tanks).

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* Submission form through Green Star Online
* Evidence to support claims made in the submission

#### **Recommended evidence**

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

**All-electric Building Services**

* As built drawings demonstrating the absence of fossil fuel systems and infrastructure.
* Evidence of support estimate of emergency power testing and peak shaving events.
* Evidence to support estimate of laboratory equipment usage.
* Evidence of purchase of offsets (e.g., contract) clearly showing the length of offset.

**Remaining Emissions Roadmap**

* Extract of operations and maintenance information of the Remaining Emissions Roadmap.
* Sign off from building owner.
* Evidence of no fossil fuels as process loads.

**Renewable Ready**

* Evidence that the energy management and information system has implemented the minimum system requirements.
* Extract of operations and maintenance information of the Load Shifting Strategy.
* Extracts of tenant leasing agreements.

**Renewable Electricity**

* Signed energy contract or PPA or evidence of on-site generation.
* Public commitment to the Global Commitment for Net Zero Carbon Buildings managed by WorldGBC.

**Tenant Engagement**

* Extracts of leasing documents.
* Evidence of active engagement with tenants.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* CSIRO -[ Real-time carbon emissions intensity of the National Electricity Market](https://research.csiro.au/dch/access-data/)
* Energy Efficiency Council – [Clean Energy Clean Demand](https://eec.org.au/publication/clean-energy-clean-demand/)
* GBCA - [From net zero to zero: A discussion paper on grid-interactive efficient buildings](https://new.gbca.org.au/case-studies/building/grid-interactive-efficient-buildings-paper/)
* [New Building Institute](https://newbuildings.org/gridoptimal-metrics-offer-guidance-on-optimizing-building-grid-interaction/)
* Open Electricity - [Open Electricity Tracker](https://explore.openelectricity.org.au/energy/nem/?range=7d\&interval=30m\&view=discrete-time)
  {% endtab %}
  {% endtabs %}


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/22-or-energy-source.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.