> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/23-or-energy-use.md).

# 23 | Energy Use

Points: 6

## <mark style="color:$primary;">Outcome</mark>

The building has low energy consumption.

### <mark style="color:$primary;">Climate Positive Pathway</mark>

<table data-search="false"><thead><tr><th>Registration</th><th width="139">Star rating</th><th>Requirement</th></tr></thead><tbody><tr><td rowspan="3">Registering from 2025 onwards</td><td>4 Star</td><td>Meets <em>Minimum Expectation</em></td></tr><tr><td>5 Star</td><td rowspan="2">Meets requirement for all points in <em>Credit Achievement</em></td></tr><tr><td>6 Star</td></tr><tr><td rowspan="3">Registering from 2028 onwards</td><td>4 Star</td><td rowspan="3">Meets requirement for all points in <em>Credit Achievement</em></td></tr><tr><td>5 Star</td></tr><tr><td>6 Star</td></tr><tr><td rowspan="3">Registering from 2030 onwards</td><td>4 Star</td><td rowspan="3">Meets requirement for all points in <em>Credit Achievement</em></td></tr><tr><td>5 Star</td></tr><tr><td>6 Star</td></tr></tbody></table>

## <mark style="color:$primary;">Pathways</mark>

There are five pathways available for this credit. Projects can choose from one of the following based on their building type:

* Pathway A: Reference building pathway
* Pathway B: NABERS Commitment Agreement pathway – Available to Class 3 hotels, Class 5 offices, Class 6 standalone retail stores and shopping centres, Class 7b warehouses and cold stores, Class 9b schools and Class 9c residential aged care and retirement living facilities
* Pathway C: Residential pathway – Available to Class 2 residential buildings only
* Pathway D: Small non-residential buildings pathway
* Pathway E: Industrial pathway – **In development**; this pathway will be available in future

Refer below for pathway criteria.

Mixed use projects may use a combination of these pathways, however they must meet the criteria for all targeted pathways to be eligible for points. Where multiple pathways are used, points will only be awarded where both pathways meet the requirements of the same points value for the targeted performance level. Points will not be averaged across multiple pathways. For *Credit Achievement* and *Exceptional Performance*, up to 1,000 m2 or 20% of the building's GFA, excluding car parks, (whichever is smaller) can be excluded if it is a different building class to the majority of the building.

## <mark style="color:$primary;">Criteria</mark>

#### ***Pathway A: Reference building pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23a.0.1-reducing-energy-use](#id-23a.0.1-reducing-energy-use "mention"): The building's energy use is at least 10% less than a reference building.

<mark style="color:$success;">**Credit Achievement — Up to 3 points**</mark>

In conjunction with *Minimum Expectation*:

* [#id-23a.1.1-reducing-energy-use](#id-23a.1.1-reducing-energy-use "mention") The building's energy use is at least 20% less than a reference building.

<mark style="color:$success;">**Exceptional Performance — Up to 3 points**</mark>

In conjunction with *Credit Achievement:*

* [#id-23a.2.1-reducing-energy-use](#id-23a.2.1-reducing-energy-use "mention")The building's energy use is at least 30% less than a reference building.

#### ***Pathway B: NABERS commitment agreement pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23b.0.1-nabers-commitment-agreement](#id-23b.0.1-nabers-commitment-agreement "mention") The building's energy use is modelled to perform at a specified minimum NABERS star rating (by building class).

<mark style="color:$success;">**Credit Achievement — Up to 3 points**</mark>

In conjunction with *Minimum Expectation*:

* [#id-23b.1.1-nabers-commitment-agreement](#id-23b.1.1-nabers-commitment-agreement "mention")**:** The building's energy use is modelled to perform at a specified NABERS star rating (by building class).

<mark style="color:$success;">**Exceptional Performance — Up to 3 points**</mark>

In conjunction with *Credit Achievement:*

* [#id-23b.2.1-nabers-commitment-agreement](#id-23b.2.1-nabers-commitment-agreement "mention"): The building's energy use is modelled to perform at a specified NABERS star rating (by building class).

#### ***Pathway C: Residential pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23c.0.1-nathers-ratings](#id-23c.0.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 7.5 stars and at least a NatHERS 6 stars for each sole-occupancy unit.
* [#id-23c.0.2-domestic-hot-water](#id-23c.0.2-domestic-hot-water "mention"): The building addresses domestic hot water demand.
* [#id-23c.0.3-pool-covers](#id-23c.0.3-pool-covers "mention"): Where a pool exists, it has a pool cover.
* [#id-23c.0.4-energy-efficiency-requirements](#id-23c.0.4-energy-efficiency-requirements "mention"): The building complies with NCC Parts J3 to J8.

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

In conjunction with *Minimum Expectation:*

* [#id-23c.1.1-nathers-ratings](#id-23c.1.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 7.5 Stars and at least a NatHERS 6.5 Stars for each sole-occupancy unit.
* [#id-23c.1.2-building-services](#id-23c.1.2-building-services "mention"): The building addresses four out of nine building services energy uses.

<mark style="color:$success;">**Exceptional Performance — 3 points**</mark>

In conjunction with *Credit Achievement:*

* [#id-23c.2.1-nathers-ratings](#id-23c.2.1-nathers-ratings "mention"): The building has a weighted-area average of NatHERS 8 Stars and at least a NatHERS 7 Stars for each sole-occupancy unit.
* [#id-23c.2.2-building-services](#id-23c.2.2-building-services "mention"): The building addresses six out of nine building services energy uses.

#### ***Pathway D: Small non-residential buildings pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-23d.0.1-building-envelope-attributes](#id-23d.0.1-building-envelope-attributes "mention"): The building has several efficient building fabric attributes.
* [#id-23d.0.2-building-systems-attributes](#id-23d.0.2-building-systems-attributes "mention"): The building has several efficient building systems attributes.
* [#id-23d.0.3-minimum-energy-efficiency](#id-23d.0.3-minimum-energy-efficiency "mention")
* [#id-23d.0.4-energy-consumption-estimate](#id-23d.0.4-energy-consumption-estimate "mention")The project estimates its energy use.

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

In conjunction with *Minimum Expectation:*

* [#id-23d.1.1-building-envelope-attributes](#id-23d.1.1-building-envelope-attributes "mention"): The building has several more efficient building fabric attributes.
* [#id-23d.1.2-building-systems-attributes](#id-23d.1.2-building-systems-attributes "mention"): The building has an increased number of efficient building systems attributes.

#### ***Pathway E: Industrial pathway***

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

In development

<mark style="color:$success;">**Credit Achievement — 3 points**</mark>

In development

<mark style="color:$success;">**Exceptional Performance — 3 points**</mark>

In development

***

## <mark style="color:$primary;">Additional information</mark>

#### Scope of credit

All energy use in the project related to building systems that have been installed by the building owner. Refer to the relevant pathway for further information.

#### Stage implementation

Strategy | **Brief** | **Concept** | **Design** | **Tender** | Construction | Handover | Use

#### Synergies with other credits

* Verification and Handover
* Disclosure of Impacts
* Climate Change Resilience
* Operations Resilience
* Grid Resilience

#### Sustainable Development Goals

* **Goal 7:** Affordable and Clean Energy
* **Goal 13:** Climate Action

#### Relevant reporting initiatives

* GRESB
* Task Force on Climate-related Financial Disclosures **(TCFD)**

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

{% tabs %}
{% tab title="A: Reference building " %}

***

## <mark style="color:$primary;">Requirements</mark>

Where reference is made to Section J requirements of the National Construction Code (NCC), this refers to Volume One 2022 version. All projects must use the requirements in NCC 2022, irrespective of location. No state amendments or exclusions are allowed.

If the building's approval is subject to a later code, the building must use that version and the project is subject to the requirements of the later version for this credit. Please contact the GBCA prior to registration if your project is subject to a later version than NCC 2022.

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with the following criterion:

* Reducing Energy Use

#### 23A.0.1 Reducing Energy Use

The building's energy use is at least 10% less than a reference building.

#### *Calculating energy use reductions*

The energy use reductions are calculated by comparing the predicted energy use of the project against a reference building.

The predicted energy use of the project includes the predicted annual energy (in MJ/year) consumed by building systems.

The reference building is a building modelled to NCC 2022 Section J or later. If the building's approval is subject to a later code, the building must use that version.

On-site renewable energy generation systems connected behind the meter do not contribute to reductions in energy use.

Refer to the [*Energy Use calculation guide*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide.md) for more information.

#### *Minimum Provisions*

Each building systems is compliant with the relevant parts of NCC Section J:

* The performance of wall-glazing constructions and display windows (Part J4D6) comply with the total system R value, total system U value and system SHGC requirements, inclusive of thermal bridging effects.
* The performance of fan systems (Part J6D5), pump systems (Part J6D8), refrigerant chillers (Part J6D11) and heat rejection equipment (Part J6D13) comply with the applicable efficiency requirements.
* The performance of artificial lighting systems (Part J7D3) complies with the overall lighting efficiency requirements.

{% hint style="success" icon="dot" %}
**Tenanted buildings**\
Modelling of energy use is based on the provision of base building systems to the tenancy and an assumption that minimum NCC requirements will be met for tenant systems. Modelled energy use for tenanted spaces to be based on the most energy-intensive allowed by base building system requirements outlined in the tenancy fitout guide and NCC DTS provisions. For cold shell spaces where there is no provision for connection to base building systems, the project team are to model standalone (supplementary) tenant systems based on the most energy-intensive allowed by requirements outlined in leasing agreement documentation.

Tenancy fitout guide identifies (including but not limited to) the tenant's allowable internal loads (tenant lighting and equipment power allowances), HVAC system zoning requirements (internal and perimeter zones with independent temperature control), HVAC system type & design capacities, and outdoor air rates. The design team must demonstrate the design provision (e.g., space allowance) that has been made for accommodating the system type modelled.

Consumption from tenant systems such as plug loads, domestic appliances, and manufacturing or process loads are excluded from the calculation.

Refer to the [*Energy Use calculation guide*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide.md) for more information.
{% endhint %}

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with *Minimum Expectation*, the project must comply with the following criterion:

* Reducing Energy Use

#### 23A.1.1 Reducing Energy Use

The building's energy use is at least 20% less than a reference building.

Refer [*Minimum Expectation*](#id-23a.0.1-reducing-energy-use) for further information on calculating energy use reductions.

Stepped points are available for energy use reductions between 10% to 20% as below. Projects meeting the Climate Positive Pathway must demonstrate at least 20% less than a reference building for this performance level.

<table><thead><tr><th width="231.5">Available points</th><th>Percentage requirements</th></tr></thead><tbody><tr><td>1 point</td><td>At least <strong>13%</strong> less energy use than a reference building.</td></tr><tr><td>1 additional point</td><td>At least <strong>16%</strong> less energy use than a reference building.</td></tr><tr><td>1 additional point</td><td>At least <strong>20%</strong> less energy use than a reference building.</td></tr></tbody></table>

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with *Credit Achievement*, the project must comply with the following criterion:

* Reducing Energy Use

#### 23A.2.1 Reducing Energy Use

The building's energy use is at least 30% less than a reference building.

Refer [*Minimum Expectation*](#id-23a.0.1-reducing-energy-use) for further information on calculating energy use reductions.

Stepped points are available for energy reductions between 20% to 30% as below.

<table><thead><tr><th width="214">Available points</th><th>Percentage requirements</th></tr></thead><tbody><tr><td>1 point</td><td>At least 23% less energy use than a reference building.</td></tr><tr><td>1 additional point</td><td>At least 26% less energy use than a reference building.</td></tr><tr><td>1 additional point</td><td>At least 30% less energy use than a reference building</td></tr></tbody></table>

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Energy Use calculator**
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

* Energy modelling report reflecting as built conditions.
* Extracts from commissioning reports confirming all systems have been commissioned and are operating as designed.
* As built drawings and schedules of the façade / building envelope.
* Product data sheets or similar.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* Australian Building Codes Board (ABCB) - [National Construction Code 2022 Volume One](https://ncc.abcb.gov.au/editions/ncc-2022/adopted/volume-one/preface/copyright-and-licence-notice)
* GBCA - Climate positive buildings and our net zero ambitions
* GBCA - Climate Positive Roadmap
* GBCA - Energy Use calculation guide
* World GBC - [Net Zero Carbon Buildings Commitments](https://www.worldgbc.org/thecommitment)
  {% endtab %}

{% tab title="B: NABERS Commitment Agreement" %}

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with the following criterion:

* NABERS Commitment Agreement

#### 23B.0.1 NABERS Commitment Agreement

The project has a NABERS Energy Commitment Agreement to predict the energy and greenhouse gas performance and achieves a target rating that is equivalent or greater than the ratings outlined in the below table for its building class.

<table data-search="false"><thead><tr><th>Building class</th><th>NABERS Energy Commitment Agreement target rating</th><th>NABERS Energy Estimate model rating progress metric</th></tr></thead><tbody><tr><td>Class 3 hotels</td><td>4.5 Stars</td><td>4.5 Stars</td></tr><tr><td>Class 5 offices</td><td>5.5 Stars</td><td>5.5 Stars</td></tr><tr><td>Class 6 retail stores</td><td>4 Stars</td><td>4 Stars</td></tr><tr><td>Class 6 shopping centres</td><td>5 Stars</td><td>5.2 Stars</td></tr><tr><td>Class 7b warehouses and cold stores</td><td>4 Stars</td><td>4.5 Stars</td></tr><tr><td>Class 9b schools</td><td>4 Stars</td><td>4 Stars</td></tr><tr><td>Class 9c residential aged care and retirement living facilities</td><td>4 Stars</td><td>4.5 Stars</td></tr></tbody></table>

On-site renewable energy generation systems connected behind the meter **do not** contribute to reductions in energy use for the NABERS Energy estimate model rating progress metric.

#### *Modelling requirements*

The scope of the NABERS Energy rating is as per the NABERS Energy Rules for the respective building classes.

The energy performance results use reference scenario modelling inputs, not off-axis scenario inputs. Refer to the [*Handbook for Estimating NABERS ratings*](https://www.nabers.gov.au/sites/default/files/2022-11/Handbook%20for%20estimating%20NABERS%20ratings.pdf) for more information.

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with *Minimum Expectation*, the project must comply with the following criterion:

* NABERS Commitment Agreement

#### 23B.1.1 NABERS Commitment Agreement

The project has a NABERS Energy Commitment Agreement to predict the energy and greenhouse gas performance and achieves a target rating that is equivalent or greater than the ratings outlined in the below table for its building class.

Stepped points are available. Projects meeting the *Climate Positive Pathway* must achieve the highest target rating noted for the relevant building class for this performance level.

<table data-search="false"><thead><tr><th>Building class</th><th>Available points</th><th>NABERS Energy Commitment Agreement target rating</th><th>NABERS Energy Estimate model rating progress metric</th></tr></thead><tbody><tr><td rowspan="3">Class 3 hotels</td><td>1 point</td><td>4.5 Stars</td><td>4.6 Stars</td></tr><tr><td>1 additional point</td><td>4.5 Stars</td><td>4.8 Stars</td></tr><tr><td>1 additional point</td><td>5 Stars</td><td>5 Stars</td></tr><tr><td rowspan="3">Class 5 offices</td><td>1 point</td><td>5.5 Stars</td><td>5.5 Stars*</td></tr><tr><td>1 additional point</td><td>5.5 Stars</td><td>5.6 Stars</td></tr><tr><td>1 additional point</td><td>5.5 Stars</td><td>5.7 Stars</td></tr><tr><td rowspan="3">Class 6 retail stores</td><td>1 point</td><td>4 Stars</td><td>4.2 Stars</td></tr><tr><td>1 additional point</td><td>4 Stars</td><td>4.4 Stars</td></tr><tr><td>1 additional point</td><td>4.5 Stars</td><td>4.5 Stars</td></tr><tr><td rowspan="3">Class 6 shopping centres</td><td>1 point</td><td>5 Stars</td><td>5.3 Stars</td></tr><tr><td>1 additional point</td><td>5 Stars</td><td>5.4 Stars</td></tr><tr><td>1 additional point</td><td>5.5 Stars</td><td>5.5 Stars</td></tr><tr><td rowspan="3">Class 7b warehouses and cold stores</td><td>1 point</td><td>4.5 Stars</td><td>4.6 Stars</td></tr><tr><td>1 additional point</td><td>4.5 Stars</td><td>4.8 Stars</td></tr><tr><td>1 additional point</td><td>5 Stars</td><td>5 Stars</td></tr><tr><td rowspan="3">Class 9b schools</td><td>1 point</td><td>4 Stars</td><td>4.2 Stars</td></tr><tr><td>1 additional point</td><td>4 Stars</td><td>4.4 Stars</td></tr><tr><td>1 additional point</td><td>4.5 Stars</td><td>4.5 Stars</td></tr><tr><td rowspan="3">Class 9c residential aged care and retirement living facilities</td><td>1 point</td><td>4.5 Stars</td><td>4.6 Stars</td></tr><tr><td>1 additional point</td><td>4.5 Stars</td><td>4.8 Stars</td></tr><tr><td>1 additional point</td><td>5 Stars</td><td>5 Stars</td></tr></tbody></table>

\*The energy performance results using reference scenario modelling inputs and off-axis scenario inputs both meet the minimum requirements.

On-site renewable energy generation systems connected behind the meter **do not** contribute to reductions in energy use for the NABERS Energy estimate model rating progress metric.

Refer [*Minimum Expectation*](#modelling-requirements) for further information on modelling requirements.

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with *Credit Achievement,* the project must comply with the following criterion:

* NABERS Commitment Agreement

#### 23B.2.1 NABERS Commitment Agreement

The project has a NABERS Energy Commitment Agreement to predict the energy and greenhouse gas performance and achieves a target rating that is equivalent or greater than the ratings outlined in the below table for its building class.

<table data-search="false"><thead><tr><th>Building class</th><th>Available points</th><th>NABERS Energy Commitment Agreement target rating</th><th>NABERS Energy Estimate model rating progress metric</th></tr></thead><tbody><tr><td>Class 3 hotels</td><td>1 point</td><td>5 Stars</td><td>5.2 Stars</td></tr><tr><td>Class 3 hotels</td><td>1 additional point</td><td>5 Stars</td><td>5.3 Stars</td></tr><tr><td>Class 3 hotels</td><td>1 additional point</td><td>5.5 Stars</td><td>5.5 Stars</td></tr><tr><td>Class 5 offices</td><td>1 point</td><td>5.5 Stars</td><td>5.8 Stars</td></tr><tr><td>Class 5 offices</td><td>1 additional point</td><td>5.5 Stars</td><td>5.9 Stars</td></tr><tr><td>Class 5 offices</td><td>1 additional point</td><td>6 Stars</td><td>6 stars</td></tr><tr><td>Class 6 retail stores</td><td>1 point</td><td>4.5 Stars</td><td>4.7 Stars</td></tr><tr><td>Class 6 retail stores</td><td>1 additional point</td><td>4.5 Stars</td><td>4.8 Stars</td></tr><tr><td>Class 6 retail stores</td><td>1 additional point</td><td>5 stars</td><td>5 stars</td></tr><tr><td>Class 6 shopping centres</td><td>1 point</td><td>5.5 Stars</td><td>5.7 Stars</td></tr><tr><td>Class 6 shopping centres</td><td>1 additional point</td><td>5.5 Stars</td><td>5.8 Stars</td></tr><tr><td>Class 6 shopping centres</td><td>1 additional point</td><td>6 Stars</td><td>6 stars</td></tr><tr><td>Class 7b warehouses and cold stores</td><td>1 point</td><td>5 Stars</td><td>5.2 Stars</td></tr><tr><td>Class 7b warehouses and cold stores</td><td>1 additional point</td><td>5 Stars</td><td>5.3 Stars</td></tr><tr><td>Class 7b warehouses and cold stores</td><td>1 additional point</td><td>5.5 Stars</td><td>5.5 stars</td></tr><tr><td>Class 9b schools</td><td>1 point</td><td>4.5 Stars</td><td>4.7 Stars</td></tr><tr><td>Class 9b schools</td><td>1 additional point</td><td>4.5 Stars</td><td>4.8 Stars</td></tr><tr><td>Class 9b schools</td><td>1 additional point</td><td>5 Stars</td><td>5 stars</td></tr><tr><td>Class 9c residential aged care and retirement living facilities</td><td>1 point</td><td>5 Stars</td><td>5.2 Stars</td></tr><tr><td>Class 9c residential aged care and retirement living facilities</td><td>1 additional point</td><td>5 Stars</td><td>5.4 Stars</td></tr><tr><td>Class 9c residential aged care and retirement living facilities</td><td>1 additional point</td><td>5.5 Stars</td><td>5.5 stars</td></tr></tbody></table>

On-site renewable energy generation systems connected behind the meter **do not** contribute to reductions in energy use for the NABERS Energy estimate model rating progress metric.

Refer [*Minimum Expectation*](#modelling-requirements) for further information on modelling requirements.

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#class-6-retail-stores)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#class-7b-warehouses-and-cold-stores)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**NABERS commitment agreement**\
Project teams must demonstrate that the project is subject to a NABERS Energy Commitment Agreement. This pathway recognises NABERS Energy Commitment Agreements where a NABERS-recognised Independent Design Reviewer has completed a full peer review of the base building design and associated energy performance simulation assessment.

**Mixed use buildings**\
For mixed use buildings, this pathway may be used to assess the areas where requirements for the relevant building class are available. Areas where the relevant building class is not available must use another pathway to demonstrate compliance.

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Energy Use calculator**
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

* Signed copy of the NABERS Energy Commitment Agreement.
* NABERS Design Reviewed Target Rating certified.
* NABERS Energy Independent Design Review report.
* NABERS Energy Estimation model report.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* GBCA - Climate positive buildings and our net zero ambitions
* GBCA - Climate Positive Roadmap
* NABERS - [Commitment Agreements](https://www.nabers.gov.au/ratings/commitment-agreements)
* NABERS – [Handbook for estimating NABERS ratings](https://www.nabers.gov.au/publications/commitment-agreement-documentation)
  {% endtab %}

{% tab title="C: Residential " %}
Where reference is made to Section J requirements of the National Construction Code (NCC) it refers to Volume One 2022 version. All projects must use the requirements in NCC 2022, irrespective of location. No state amendments or exclusions are allowed.

If the building's approval is subject to a later code, the building must use that version and the project is subject to the requirements of the later version for this credit. Please contact the GBCA prior to registration if your project is subject to a later version than NCC 2022.

This pathway is available to Class 2 buildings (or parts of buildings) only.

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all** the following criteria:

* NatHERS ratings
* Domestic Hot Water Demand
* Pool Covers
* Energy Efficiency Requirements

#### 23C.0.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building achieves a NatHERS energy rating of at least 7.5 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit achieve a NatHERS energy rating of at least 6 stars.

#### 23C.0.2 Domestic Hot Water

The below fixtures and water-using appliances installed have a minimum WELS ratings of the following:

<table><thead><tr><th width="250.25">Fixture type</th><th>WELS rating</th></tr></thead><tbody><tr><td>Showers</td><td>3 Stars with a maximum flow rate of 9L/min</td></tr><tr><td>Taps – kitchen</td><td>4 Stars with a maximum flow rate of 7.5L/min</td></tr><tr><td>Taps – hand wash basins</td><td>5 Stars with a maximum flow rate of 6L/min</td></tr></tbody></table>

#### 23C.0.3 Pool Covers

Where heated pools are installed, a pool cover with a minimum R-value of 0.075 for external pools or 0.05 for internal pools is installed.

Projects that do not have heated pools are exempt from the *Pool Covers* criterion.

#### 23C.0.4 Energy Efficiency Requirements

The building complies with the requirements under NCC Section J Parts J5 to J9 with no state amendments or exclusions except for projects in NSW that comply with BASIX.

Projects in NSW must comply with the following:

* BASIX Version 4.0 or later.
* NCC Section J Parts NSW J2D2 (2), (3), (4) and (5).

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with *Minimum Expectation*, the project must comply with **both** of the following criteria:

* NatHERS ratings
* Building Services

#### 23C.1.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building achieves a NatHERS energy rating of at least 7.5 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit achieve a NatHERS energy rating of at least 6.5 stars.

#### 23C.1.2 Building Services

The building complies with **one** of the following:

* Building Services Requirements
* BASIX Building Services

#### *Building Services Requirements*

The building includes at least **four** out the eight[^1] building services requirements.

<table data-search="false"><thead><tr><th width="216.5">Building service</th><th>Requirement</th></tr></thead><tbody><tr><td>Domestic Hot Water</td><td>All showers have a minimum WELS rating of 4 Stars with a maximum flow rate of 7.5L/min.<br><br>All hot water pipes outside of the sole-occupancy units are insulated with a minimum R-value of 1.0. All hot water pipes inside sole-occupancy units are insulated with a minimum R-value of 0.5.</td></tr><tr><td>Domestic Hot Water Generation</td><td><p>The building provides one or a combination of:</p><ul><li>A solar thermal heating system is provided, or heat is recovered from another process (e.g., chiller heat recovery) or a combination of both, which contributes at least 30% of the annual thermal energy requirement for water heating.</li><li>The primary non-renewable heat source for domestic hot water is an electric heat pump with a minimum COP of 3.0 at 20°C ambient and 65°C leaving temperature.</li></ul></td></tr><tr><td>Heating and Cooling of Sole Occupancy Units</td><td><p>The building provides efficient outcomes for heating and cooling.<br><br>For cooling, the building provides one or a combination of the following:</p><ul><li>DX split systems: a minimum 3.5 Star ZERL Cooling Star Rating (average zone).</li><li>Centralised condenser water system: water cooled packaged units with a minimum cooling EER of 3.5 AND the condenser water system exceeds energy efficiency requirements of NCC Section J Part J6D8 and J6D13 by at least 10%.</li><li>Central chilled water system: the chiller and chilled water systems exceed energy efficiency requirements of NCC Section J Part J6D8 and J6D11 by at least 10%. If a cooling tower is installed, then this must exceed energy efficiency requirements of NCC Section J Part J6D13 by at least 10%.</li><li>No refrigerant-based cooling is provided.<br><br>For heating, the building provides one or a combination of the following:</li><li>DX split systems: 3 Star ZERL Heating Star Rating (average zone).</li><li>Centralised condenser water system: water cooled package units with a minimum heating EER of 4.0 AND the condenser water pump system exceeds energy efficiency requirements of NCC Section J Part J6D8 by at least 10%.</li><li>Central heating hot water system: the heat source is a heat pump with a with a minimum COP of 4.0 at 10°C ambient outside air temperature AND the heating hot water pumping system exceeds energy efficiency requirements of NCC Section J Part J6D8 by at least 10%.</li><li>Electric heater: 10% better than NCC Section J Part J6D10 requirements.</li><li>No electric or combustion-based heating is provided.</li></ul></td></tr><tr><td>Clothes Drying</td><td><p>95% of dwellings have the following:</p><ul><li>Access to an external clothes drying facility.</li></ul><p>And complies with <strong>one</strong> of the following:</p><ul><li>Has no available space for a clothes dryer.</li></ul><p><em>or</em></p><ul><li>Has a heat pump clothes dryer with auto-sensing feature.</li></ul></td></tr><tr><td>Ceiling Fans</td><td>Ceiling fans are installed in all bedrooms and living rooms and comply with the requirements of NCC Section J0.3.</td></tr><tr><td>Car Parking</td><td><p>The building complies with <strong>one</strong> of the following:</p><ul><li>No undercover car parking is provided.</li><li>75% of undercover car parking is naturally ventilated with no mechanical ventilation systems.</li><li>Undercover car parking is limited to 1 car space per 5 sole-occupancy units.</li></ul><p>Where undercover parking is provided, lighting control linked to occupancy sensors must be installed, with minimum lighting levels provided for safety and security purposes.</p></td></tr><tr><td>Vertical Transportation</td><td><p>The energy associated with lift machinery or other vertical transportation complies with <strong>all</strong> the following:</p><ul><li>The minimum lift energy efficiency is class A or B in accordance with <em>ISO 25745-2</em>.</li><li>The lift idle and standby energy performance level is 1 in accordance with <em>ISO 25745-2</em>.</li><li>The minimum escalator energy performance is class A+ to A+++ in accordance with <em>ISO 25745-3</em>.</li></ul><p>Requirements are met for all relevant systems where present.</p></td></tr><tr><td>Lift Lobbies and Corridors</td><td><p>Lift lobbies and hallways (excluding main entrance lobby to the building) are either:</p><ul><li>Naturally ventilated</li><li>Supply / exhaust air only with no heating or cooling (A/C or tempered)</li></ul></td></tr></tbody></table>

#### *BASIX*

Projects in NSW achieve a BASIX Energy score 20% better than minimum compliance (rounded down to nearest integer).

**Calculating BASIX Energy Score**\
Fridges are entered as "not specified" for the purposes of this credit.

All other inputs are to be as per the BASIX assessment used for the Occupancy Certificate.

### <mark style="color:$success;">Exceptional Performance</mark>

In conjunction with *Credit Achievement*, the project must comply with **both** the following criteria:

* NatHERS ratings
* Building Services

#### 23C.2.1 NatHERS ratings

#### *Area weighted average*

The weighted-area average of all sole occupancy units in the building must achieve a NatHERS energy rating of at least 8 stars.

#### *Sole Occupancy rating*

Each sole-occupancy unit must achieve a NatHERS energy rating of at least 7 stars.

#### 23C.2.2 Building Services

Project teams must comply with one of the following:

* Building Services Requirements
* BASIX Building Services

#### *Building Services Requirements*

The building includes at least **six** out the eight[^2] building services requirements.

Refer [*Credit Achievement*](#id-23c.1.2-building-services) for requirements.

#### *BASIX*

Projects in NSW achieve a BASIX Energy score 30% better than minimum compliance (rounded down to nearest integer).

**Calculating BASIX Energy Score**\
Fridges are entered as "not specified" for the purposes of this credit.

All other inputs are to be as per the BASIX assessment used for the Occupancy Certificate.

***

## <mark style="color:$primary;">Definitions</mark>

Definitions provided here must be applied to Requirements unless agreed with GBCA via a Technical Question.

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#external-clothes-drying-facility)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for the credit requirements and is not mandatory to apply.

**Passivhaus Certification**\
Projects which have achieved a Passivhaus Certification are considered to meet the NatHERS Ratings criterion in the *Minimum Expectation*, *Credit Achievement* and *Exceptional Performance*. Project teams must submit a Technical Question outlining how they have also met similar outcomes for the Building Services requirement.

**NatHERS**\
The NatHERS modelling must be carried out by an accredited assessor and the NatHERS Universal Certificate produced by an NatHERS accredited assessor.

* Projects located in NSW must meet the maximum heating and cooling loads as per the BASIX ® Thermal Comfort Protocol.
* Projects located in all other states must meet the heating and cooling loads applicable as per the ABCB Standard - NatHERS heating and cooling loads limits.
* NatHERS rating is based on thermal loads only and excludes any Star rating benefit provided by ceiling fans, water tanks or other ESD provisions allowable in some States.

**ABCB Standard - NatHERS heating and cooling loads limits**\
For further information about the heating and cooling load limits, please refer to the ABCB web page <https://www.abcb.gov.au/Resources/Publications/Education-Training/NatHERS-heating-and-cooling-load-limits>

**External clothes drying facility**\
External balconies alone are not considered to be an external clothes drying facility. The intent of the credit is to ensure tenants have access to dedicated zero-energy clothes drying facilities.

**Electric vehicle charging**\
Requirements relating to electric vehicle charging provisions are included in the Low-Emissions Transport credit. Load management systems for electric vehicle charging can also contribute to the [22 | Energy Source](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/22-or-energy-source.md) and [21 | Grid Resilience](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/resilient-2/21-or-grid-resilience.md) credits.

***

## <mark style="color:$primary;">Submission content</mark>

#### Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

* NatHERS certification summary report issued to the Building Certifier at time of Building Approval.
* As built documentation showing compliance with the nominated building services requirements.
* BASIX Certificate.
* BASIX Report showing BASIX score without fridges (unless BASIX certificate already excludes these).

**Domestic Hot Water**

* Schedule demonstrating that all fittings achieve the required WELS rating.

**Domestic Hot Water Generation**

* Manufacturers' documentation showing the gross thermal efficiency or coefficient of performance (COP) of the heating appliance.
* Documentation demonstrating that the solar heating system and/or heat recovery systems contributes at least 30% of the annual requirement.

**Heating and Cooling**

* Schedule identifying all air-conditioners installed in the building, their capacities and the manufacturer and model of each.
* Manufacturers' documentation or information from [www.energyrating.gov.au](http://www.energyrating.gov.au) confirming the energy star rating applicable to each air-conditioner or heater.

**Clothes Drying**

* As built drawings demonstrating provision of external drying facilities.
* Documentation demonstrating the specification of the dryer installed.

**Ceiling Fans**

* As built drawings demonstrating that ceiling fans have been provided to all living rooms and bedrooms.
* Schedule identifying all ceiling fans installed the in the building, and the manufacturer and model of each.

**Car Parking**

* As built drawings demonstrating that no undercover parking is provided.
* Extract from the Commissioning Report demonstrating enclosed car parking areas are naturally ventilated.
* Documentation showing that no more than 1 car space per 5 sole-occupancy units is provided.
* Documentation showing location and CO sensors and Variable Speed Drive on all fans.

**Vertical Transportation**

* Schedule identifying all vertical transportation systems installed in the building, and the manufacturer and model of each.
* Documentation showing the energy efficiency class and idle and standby energy performance level in accordance with ISO 25745-2 for all installed lifts (where applicable).
* Documentation showing the energy performance class in accordance with ISO 25745-3 for all installed escalators (where applicable).
* Extract(s) from the commissioning report demonstrating (through supporting evidence) that the vertical transportation systems have been commissioned and operate as intended by the design.

**Lift lobbies and corridors**

* As built drawings for each naturally ventilated space showing openings, with dimensions clearly indicated, and ventilation inlets and outlets.
* Documentation showing supply / exhaust air only with no heating or cooling.

**Pool Cover**

* Product data sheets showing the R value of the pool cover installed.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* Australian Building Codes Board (ABCB) - National Construction Code 2022 Volume One
* GBCA - Climate positive buildings and our net zero ambitions
* GBCA - Climate Positive Roadmap
* Sustainability Victoria - Reduce clothes dryer costs at home<br>
  {% endtab %}

{% tab title="D: Small non-residential" %}
Where reference is made to Section J requirements of the National Construction Code (NCC), this refers to the 2022 version. All projects must use the requirements in NCC 2022, irrespective of location. No state amendments or exclusions are allowed.

If the building's approval is subject to a later code, the building must use that version and the project is subject to the requirements of the later version for this credit. Please contact the GBCA prior to registration if your project is subject to a later version than NCC 2022.

***

## <mark style="color:$primary;">Requirements</mark>

This pathway is only available to spaces that meet all the following prerequisites:

* The building class space type is not Class 2.
* The net conditioned area (NCA) is less than 1,000m² or a contract value of at most $10m.
* Less than or equal to three storeys.
* Has heating load and cooling load of less than 250kW.

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all** the following criteria:

* Building Envelope Attributes
* Building Systems Attributes
* Minimum Energy Efficiency
* Energy Consumption Estimate

#### 23D.0.1 Building Envelope Attributes

The building includes the following building envelope attributes:

* Roof lights
* At least **two** out of the five remaining attributes:

<table><thead><tr><th width="192.75">Attributes</th><th>Requirement</th></tr></thead><tbody><tr><td>Roof lights</td><td><p>Where the total area of roof lights exceeds 2% of the total GFA of the building, all roof lights have both of the following:</p><ul><li>A total system U-value not more than U3.0.</li><li>A total system SHGC of less than or equal to 85% of the maximum values specified in NCC Section J Table J4D5.</li></ul><p>Where the total area of roof lights is less than 2% of the total GFA of the building, all roof lights comply with NCC Section J J4D5.</p></td></tr><tr><td>Display glazing</td><td><p>All display glazing has both of the following:</p><ul><li>A total system U-value not more than U4.0.</li><li>A total system SHGC of less than or equal to 85% of the maximum values specified in NCC Section J J4D4 (7).</li></ul></td></tr><tr><td>Roof and ceiling insulation</td><td>All roofs and ceilings have a total R-Value that is R0.75 greater than the minimum specified by NCC Section J Part J4D4.</td></tr><tr><td>Walls and glazing</td><td><p>The walls and glazing comply with both of the following:</p><ul><li>All wall-glazing construction has a total system U-value of less than or equal to 85% of the maximum values specified in NCC Section J Part J4D6 (1) calculated in accordance with Specification 37.</li><li>All wall components of all wall-glazing construction have a R-value that is R0.5 higher than minimum required in NCC Section J Part J4D6 (4) calculated in accordance with Specification 37.</li></ul></td></tr><tr><td>Externally facing wall-glazing construction</td><td>All externally facing wall-glazing construction have a solar admittance that is at least 15% less than NCC Section J Part J4D6 (5) calculated in accordance with Specification 37.</td></tr><tr><td>Floors</td><td>All floors have a total R-value that is R0.5 greater than the minimum specified in NCC Section J Table J4D7.</td></tr></tbody></table>

#### 23D.0.2 Building Systems Attributes

The building includes at least **three** out of the nine following building systems attributes:

<table data-search="false"><thead><tr><th width="189">Attributes</th><th>Requirement</th></tr></thead><tbody><tr><td>Fans and duct systems</td><td>The fan motor input power per unit of flowrate is 15% lower than the reference fan motor input power per unit flow rate calculated from the deemed-to-satisfy requirements of NCC Section J Parts J6D5 (2), (3), (4) and (5).<br><br>This is calculated on an average weighted basis for all fans in the building based on their rated power in kW.<br><br><em>If the annual fan energy consumption is estimated to be less than 5% of the total building energy consumption this cannot be targeted.</em></td></tr><tr><td>Pumps</td><td>The pump motor input power per unit of flowrate is 15% lower than the reference pump motor input power per unit flow rate calculated from the deemed-to-satisfy requirements of NCC Section J Part J6D8 (2), (3) and (4).<br><br>This is calculated on an average weighted basis for all pumps in the building based on their rated power in kW.<br><br><em>If the annual pump energy consumption is estimated to be less than 5% of the total building energy consumption this cannot be targeted.</em></td></tr><tr><td>Space Heating</td><td><p>The building complies with one or a combination of the following:</p><ul><li>No heating provided.</li><li>Air conditioning systems up to 65kW: a minimum 4 Star Heating Star Rating (mixed zone).</li><li>Electric heat pump systems greater than 65kW: a minimum annual coefficient of performance (ACOP) of 3.5 measured in accordance with Greenhouse and Energy Minimum Standards (Air Conditioners above 65kW) Determination) 2022.</li></ul><p><em>If the capacity (kW) of any direct electric heating elements is more than 20% of the total heating capacity in the building this cannot be targeted.</em></p></td></tr><tr><td>Space Cooling</td><td><p>The building complies with one or a combination of the following:</p><ul><li>No cooling provided.</li><li>Air conditioning systems up to 65kW: a minimum 4 Star Cooling Star Rating (mixed zone).</li><li>Electric heat pump systems up to 65 kW: a minimum annual energy efficiency ratio (AEER) of 3.5 measured in accordance with <em>Greenhouse and Energy Minimum Standards (Air Conditioners above 65kW) Determination) 2022</em>.</li><li>Unitary air conditioning equipment greater than 65kWr: an energy efficiency ratio 15% more than the minimum requirements in Part J6D12 from NCC 2022.</li><li>Refrigerant chillers: an energy efficiency ratio 15% more than the minimum requirements in Part J6D11 from NCC 2022.</li><li>Heat rejection equipment: a motor rated power 10% less than that required in Part J6D13 from NCC 2022.</li></ul></td></tr><tr><td>Internal artificial lighting</td><td>The aggregate design illumination power load of the internal lighting is 20% less than the sum of allowances calculated in accordance with Part J7D3(2) from NCC 2022.</td></tr><tr><td>Domestic Hot Water</td><td><p>At least 85% of annual domestic hot water consumption is supplied via an electric heat pump system (which has a minimum COP of 3.0 at 20°C ambient and 65°C leaving temperature or equivalent performance).</p><p><br><em>If the annual DHW energy consumption is likely to be less than 5% of the total building energy consumption this cannot be targeted.</em></p></td></tr><tr><td>Natural Ventilation</td><td>Where at least 50% of the regularly occupied areas are naturally ventilated, it is controlled by the occupants and is designed to operate for at least 50% of standard operating hours without mechanical systems operating.</td></tr><tr><td>Ceiling Fans</td><td>Where at least 70% of the regularly occupied areas have ceiling fans, it is able to be controlled directly by the occupants, and with a coverage of 1 fan per 25m².</td></tr><tr><td>Ventilation Heat Recovery</td><td><p>Where the regularly occupied areas have a ventilation heat recovery system, the system complies all of the following:</p><ul><li>A thermal efficiency of at least 70%.</li><li>A bypass for when heat recovery is not beneficial.</li><li>Covers at least 80% of the building's outside air supply.</li></ul></td></tr></tbody></table>

#### 23D.0.3 Minimum Energy Efficiency

The building, irrespective of location, complies with the requirements under NCC 2022 Section J for all elements not targeted under the *Building Fabric Attributes or Building Systems Attributes*. No state amendments or exclusions are applicable.

#### 23D.0.4 Energy Consumption Estimate

The annual electricity consumption in kWh and an approximate breakdown by building system is estimated for the project. This can be based on rules of thumb or other benchmarking and does not require energy modelling.

### <mark style="color:$success;">Credit Achievement</mark>

In conjunction with *Minimum Expectatio*n, the project must comply with **both** of the following criteria:

* Building Envelope Attributes
* Building Systems Attributes

#### 23D.1.1 Building Envelope Attributes

The building includes at least **three** out of the four building envelope attributes.

<table><thead><tr><th width="228">Attributes</th><th>Requirement</th></tr></thead><tbody><tr><td>Roof and ceiling insulation</td><td>All roofs and ceilings have a total R-Value that is R1.5 greater than the minimum specified by NCC Section J Part J4D4.</td></tr><tr><td>Walls and glazing</td><td><p>The walls and glazing comply with both of the following:</p><ul><li>All wall-glazing construction has a total system U-value of less than or equal to 85% of the<br>maximum values specified in NCC Section J Part J4D6 (1) calculated in accordance with<br>Specification 37.</li><li>All wall components of all wall-glazing construction have a R-value that is R0.5 higher than<br>minimum required in NCC Section J Part J4D6 (4) calculated in accordance with Specification 37</li></ul></td></tr><tr><td>Solar admittance</td><td>All externally facing wall-glazing construction have a solar admittance that is at least 30% less than the<br>maximum specified in NCC Section J Table J4D6b/c for the relevant building class</td></tr><tr><td>Floors</td><td>The total R-value of the floor is R0.5 greater than that required in Table J4D7 from NCC 2022.</td></tr></tbody></table>

#### 23D.1.2 Building Systems Attributes

The building includes at least **five** out of the nine building systems attributes.

Refer [*Minimum Expectation*](#id-23d.0.2-building-systems-attributes) for requirements.

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

**Roof lights** and **Internal artificial lighting**

* As built architectural drawings.
* Lighting schedule and data sheets.

**Display glazing, Roof and ceiling insulation, Walls and glazing, Externally facing wall-glazing construction** and **Floors**

* As built architectural and façade drawings.
* Glazing data sheets

**Fans and duct systems, Pumps, Space Heating, Space Cooling, Domestic Hot Water** and **Ventilation Heat Recovery**

* Schedule identifying all systems installed in the building, their capacities and the manufacturer and model of each.
* Manufacturers' documentation demonstrating the relevant attributes.
* Information from [www.energyrating.gov.au](http://www.energyrating.gov.au) confirming the energy star rating applicable to each air-conditioner or heater.

**Natural ventilation**

* As built architectural drawings including openings.
* Evidence of conditioning times.

**Ceiling Fans**

* As built drawings demonstrating location of ceiling fans.
* Schedule identifying all ceiling fans installed the in the building, and the manufacturer and model of each.

**Minimum Energy Efficiency**

* Evidence of compliance with Section J

**Energy Consumption Estimate**

* Energy consumption estimates with assumptions included.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.
{% endtab %}
{% endtabs %}

[^1]:

[^2]: **18/11/2026**

    Correction: Number of requirements have been corrected.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/23-or-energy-use.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.