> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/26-or-refrigerant-systems-impacts.md).

# 26 | Refrigerant Systems Impacts

Points: 3

## <mark style="color:$primary;">Outcome</mark>

The building's design and refrigerant-based equipment are ready for a low-emissions future.

### <mark style="color:$primary;">Climate Positive Pathway</mark>

<table data-search="false"><thead><tr><th width="244">Registration</th><th width="128.75">Star rating</th><th>Requirement</th></tr></thead><tbody><tr><td rowspan="3">Registering from 2025 onwards</td><td>4 Star</td><td rowspan="2">Meets <em>Minimum Expectation</em></td></tr><tr><td>5 Star</td></tr><tr><td>6 Star</td><td>Meets <em>Credit Achievement</em></td></tr><tr><td rowspan="3">Registering from 2028 onwards</td><td>4 Star</td><td>Meets <em>Minimum Expectation</em></td></tr><tr><td>5 Star</td><td>Meets <em>Credit Achievement</em></td></tr><tr><td>6 Star</td><td>Meets <em>Exceptional Performance</em></td></tr><tr><td rowspan="3">Registering from 2030 onwards</td><td>4 Star</td><td>Meets <em>Credit Achievement</em></td></tr><tr><td>5 Star</td><td>Meets <em>Exceptional Performance</em></td></tr><tr><td>6 Star</td><td>Meets <em>Exceptional Performance</em> and <em>Leadership Challenge: Low Global Harm Refrigerants</em></td></tr></tbody></table>

## <mark style="color:$primary;">Criteria</mark>

<mark style="color:$success;">**Minimum Expectation — Nil**</mark>

* [#id-26.0.1-future-ready-buildings](#id-26.0.1-future-ready-buildings "mention"): The building considers future-proofing the building for equipment that uses ultra-low GWP refrigerants.
* [#id-26.0.2-weighted-gwp-limit](#id-26.0.2-weighted-gwp-limit "mention"): The refrigerants in the building do not exceed a weighted average GWP limit.
* [#id-26.0.3-leak-detection](#id-26.0.3-leak-detection "mention"): The building has leak detection systems where required.

<mark style="color:$success;">**Credit Achievement — 1 point**</mark>

In addition to *Minimum Expectation*, the project meets **at least one** of the following:

* [#id-26.1.1-low-gwp-limits](#id-26.1.1-low-gwp-limits "mention"): The refrigerants in the building do not exceed the GWP limits.

or

* [#id-26.1.2-low-initial-charge](#id-26.1.2-low-initial-charge "mention"): The building has a low initial charge of refrigerants.

And the project meets the following:

* [#id-26.1.3-compensation-of-refrigerant-emissions](#id-26.1.3-compensation-of-refrigerant-emissions "mention"): Refrigerant emissions are compensated.

<mark style="color:$success;">**Exceptional Performance — 2 points**</mark>

In addition to *Credit Achievement:*

* [#id-26.2.1-lower-gwp-limits](#id-26.2.1-lower-gwp-limits "mention"): The refrigerants in the building do not exceed lower GWP limits.

or

* [#id-26.2.2-lower-initial-charge](#id-26.2.2-lower-initial-charge "mention"): The building has a lower initial change of refrigerants.

***

## <mark style="color:$primary;">Additional information</mark>

#### Scope of credit

All refrigerants used in building systems or appliances installed in the scope of the rating.

Refrigerants as part of process loads (e.g. medical equipment) are included in the Future-ready Buildings criterion in the Minimum Expectation and the Compensation for Refrigerant Emissions criterion in Credit Achievement, but not in the remaining criteria and other performance levels.

#### Stage implementation

Strategy | Brief | **Concept** | **Design** | **Tender** | **Construction** | Handover | Use

#### Synergies with other credits

* Energy Source
* Energy Use
* Upfront Carbon Reduction

#### Sustainable Development Goals

* **Goal 7:** Affordable and Clean Energy
* **Goal 13:** Climate Action

#### Relevant reporting initiatives

* GRESB
* Task Force on Climate-related Financial Disclosures **(TCFD)**
* ASRS

***

## <mark style="color:$primary;">Requirements</mark>

### <mark style="color:$success;">Minimum Expectation</mark>

The project must comply with **all** the following criterion:

* Future-ready Buildings
* Weighted GWP Limit
* Leak Detection

#### 26.0.1 Future-ready Buildings

#### *Design review*

The potential impacts of alternate refrigerants on the building design are considered by completing the Refrigerant Design Review in the *Future-ready Refrigerant Design Review and*[ *Register*](#user-content-fn-1)[^1] *template.*

#### *Refrigerant inventory*

An inventory of all refrigerant-using equipment, the refrigerant installed, the leakage detection systems installed and potential alternate refrigerants for the same equipment class is developed by completing the Refrigerant Inventory in the *Future-ready Refrigerant Design Review and*[ *Register*](#user-content-fn-1)[^1] *template.*

The *Future-ready Refrigerant Design Review and*[ *Register*](#user-content-fn-2)[^2] *template* is completed by the project's building services engineers and included in the operations and maintenance information and provided to the building owner.

#### 26.0.2 Weighted GWP Limit

The total weighted average of refrigerant Global Warming Potential (GWP) in the building is below or equal to 700.

No hydrochlorofluorocarbons (HCFCs) are used in any systems in the building, including for existing equipment. Where HCFC-based equipment is present, either:

* the refrigerants are withdrawn, destroyed and replaced with non-HCFC refrigerants, or
* the equipment is decommissioned and refrigerants are destroyed. Any replacement equipment is included in total weighted average calculated for this criterion.

#### 26.0.3 Leak Detection

Leak detection systems are provided where required in accordance with *AS/NZS 5149:2016*.

### <mark style="color:$success;">Credit Achievement</mark>

In addition to *Minimum Expectation*, the project must comply with **both** of the following criteria:

* **At least one** of the following:
  * Low GWP Limits
  * Low Initial Charge
* Compensation for Refrigerant Emissions

#### 26.1.1 Low GWP Limits

All new refrigeration equipment uses refrigerants with a GWP below the limits prescribed in the table below.

<table><thead><tr><th width="253.5">System type</th><th width="390.75">Equipment examples</th><th width="162.75">GWP limit</th></tr></thead><tbody><tr><td rowspan="2">Stationery air conditioning and heat pumps</td><td>Small and Medium (&#x3C;700kW)</td><td>500</td></tr><tr><td>Large AC (>=700kW)</td><td>10</td></tr><tr><td colspan="2">Domestic hot water heat pumps</td><td>10</td></tr><tr><td>Commercial heat pumps</td><td>Commercial heat pump and multi-function chillers, water source and ground source hot water heat pumps</td><td>150</td></tr><tr><td>Domestic and standalone retail refrigeration</td><td>Domestic refrigerators, display and storage cabinets, vending machines</td><td>10</td></tr><tr><td>Large scale refrigeration</td><td>Walk-in cold rooms, display cases, supermarket refrigeration</td><td>10</td></tr></tbody></table>

#### 26.1.2 Low Initial Charge

The Total System Direct Environmental Impact (TSDEI) of the refrigerant systems in the building are below 20 as calculated using the *Refrigerants calculator.*

#### 26.1.3 Compensation of Refrigerant Emissions

All emissions from the initial refrigerant charge are offset. The purchased offsets are nature-based and produced by a GBCA recognised entity. Further information is available in [*Climate positive buildings and our net zero ambitions*](https://gbca-web.s3.amazonaws.com/media/documents/climate-positive-buildings-net-zero-ambitions_Z3pcK5R.pdf)*.*

### <mark style="color:$success;">Exceptional Performance</mark>

In addition to *Credit Achievement*, the project must comply with **one** of the following criteria:

* Lower GWP limits
* Lower Initial Charge

Where compliance with *Exceptional Performance* is demonstrated, *Credit Achievement* and the [*Weighted GWP Limit*](#id-26.0.2-weighted-gwp-limit) criterion in *Minimum Expectation* is considered met. Projects are still required to demonstrate compliance with the [*Future-ready Buildings*](#id-26.0.1-future-ready-buildings) and [*Leak Detection*](#id-26.0.3-leak-detection) criteria in *Minimum Expectation*.

#### 26.2.1 Lower GWP Limits

All new refrigeration equipment uses refrigerants with a GWP below the limits prescribed in the table below.

<table><thead><tr><th width="274.5">System type</th><th width="364">Equipment examples</th><th width="162.5">GWP limit</th></tr></thead><tbody><tr><td rowspan="2">Stationery air conditioning and heat pumps</td><td>Small and Medium AC (&#x3C;700kW)</td><td>150</td></tr><tr><td>Large AC (>=700kW)</td><td>10</td></tr><tr><td colspan="2">Domestic hot water heat pumps</td><td>10</td></tr><tr><td>Commercial heat pumps</td><td>Commercial heat pump and multi-function chillers, water source and ground source hot water heat pumps</td><td>10</td></tr><tr><td>Domestic and standalone retail refrigeration</td><td>Domestic refrigerators, display and storage cabinets, vending machines</td><td>10</td></tr><tr><td>Large scale refrigeration</td><td>Walk-in cold rooms, display cases, supermarket refrigeration</td><td>10</td></tr></tbody></table>

#### 26.2.2 Lower Initial Charge

The Total System Direct Environmental Impact (TSDEI) of the refrigerant systems in the building are below 10 as calculated using the *Refrigerants calculator*.

***

## <mark style="color:$primary;">Alternative pathways</mark>&#x20;

Where there are alternative pathways that a project can follow to achieve the credit, or sector specific alternatives.&#x20;

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Alternative pathways</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Clarifications</mark>

Where GBCA have clarified any requirements of the credit criteria. This information is additional and it is not complusory to apply.

These were previously referred to as *Frequently Asked Questions*.&#x20;

<details>

<summary>Clarifications</summary>

Existing FAQs are currently located [*here*](https://www.gbca.org.au/greenstar-manager/faqs/). GBCA are working on bringing them across to this site. New FAQs will be published here under the relevant credit and type.

</details>

***

## <mark style="color:$primary;">Definitions</mark>

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#alternate-refrigerants)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#low-global-harm-refrigerants)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#total-weighted-average)

***

## <mark style="color:$primary;">Guidance</mark>

Guidance is supporting information for credit requirements and not mandatory to apply.

**Future-ready Refrigerant Design Register**\
Projects are encouraged to include a unique identifier in the register for each equipment.

**Global Warming Potential (GWP) values**\
For the purposes of this credit, GWP values are to be based on values published by the DCCEEW which are based on the 100 year GWPs from the Intergovernmental Panel on Climate Change (IPCC) fourth assessment report, 2007 (AR4). The Montreal Protocol will continue to use AR4 values to maintain consistency for the HFC phase-down.

**Calculating emissions from initial refrigerant charge**\
Carbon emissions are calculated by multiplying the initial refrigerant charge by the GWP for each type of refrigerant present in the building and adding the emissions together.

**Total System Direct Environmental Impact (TSDEI)**\
This calculation aims to provide a capacity-weighted average to evaluate multiple pieces of HVAC equipment of different sizes, types of refrigerants, and types of building systems. It considers leakage rates and global warming potential (GWP) of the refrigerants used, as well as the type of refrigeration equipment used and the quantity of refrigerant.

```
TSDEI = ∑(LCGWF × Qi) / Qt

LCGWF = GWP × m × (L × Life + E) / Life
```

Where:

* LCGWF = life cycle global warming factor \[kg CO2 / kWr.year]
* Q<sub>i</sub> = cooling capacity of rated equipment (kWr)
* Q<sub>t</sub> = sum of cooling capacity of all rated equipment included in the building (kWr)
* GWP = Global Warming Potential (100-year), 0 < GWP < 12,000 kg CO2/kg
* m = Specific refrigerant charge (kg of refrigerant per kWr cooling capacity), 0.1 < m < 2 kg/kWr
* L = Refrigerant leak rate (% of refrigerant charge leaked per year)
* E = End of life loss, 0.1 (default 10%)
* Life = Equipment service life, 10 < Life < 35 years

The specific refrigerant charge (kg/kWr) is a measure of the refrigerant mass a system requires to produce a specific amount of cooling capacity. The higher this number, the more charge-intensive the system, leading to the risk of higher volumes of leakage.

Where the actual annual refrigerant leak rate is known, this is to be used. Where the actual leak rate is unknown, the leak rate for the relevant equipment class from Refrigerant Leak Study – [A data-driven insight from Australia 2024](https://www.refrigerantsaustralia.org/images/resources/Refrigerant%20Leak%20Study%20V2.0.pdf) may be assumed.

**No refrigerants**\
Projects that do not install refrigerant-using equipment are considered to comply with all requirements up to and including *Exceptional Performance* in this credit. Projects will also meet requirements for the Low Global Harm Refrigerants Leadership Challenge.

**Leadership Challenge: Low Global Harm Refrigerants**\
This Leadership Challenge is awarded where there are either no refrigerants used on site for building services, or all refrigerant-based equipment use low global harm refrigerants (i.e., all refrigerants have a GWP of less than 10 and do not degrade to form TFA/PFAS as defined in *Definitions*). A Leadership Challenge factsheet with further details will be made available on the Green Star Resources Hub.

***

## <mark style="color:$primary;">Submission content</mark>

Submissions for this credit must contain:

* **Submission form** through Green Star Online
* **Future-ready Refrigerant Design Review and**[ **Register**](#user-content-fn-3)[^3] **template.**
* **Evidence** to support claims made in the submission

#### Recommended evidence

The following list of evidence serves as a guide for the Certified submission and is not exhaustive. Project teams are not required to provide all of the listed items and alternate forms of documentation can be used to demonstrate compliance. The key requirement is that evidence is provided to support each claim.

**Future-ready Buildings**

* As built drawings or on-site photos showing all building systems.
* Product data sheets.
* Extracts from operations and maintenance information showing the inclusion of the Refrigerant Inventory.

**Weighted GWP Limit, GWP Limits and Lower GWP Limits**

* As built drawings or on-site photos showing all building systems.
* Product data sheets.
* Calculations of total weighted average.

**Leak Detection**

* As built drawings of leak detection systems.

**Compensation of Refrigerant Emissions**

* Calculations showing the total refrigerant charge to be offset.
* Evidence of purchase of offsets (e.g., contract) showing the length of offset.

**Low Initial Charge** and **Lower Initial Charge**

* Refrigerant calculator.
* As built drawings or on-site photos showing all building systems.
* Product data sheets.

Refer to the [Guidance for Submitting for Designed Assessments](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/other-useful-resources/guidance-for-submitting-for-designed-assessments.md) for further information on submitting evidence for the Designed assessment.

***

## <mark style="color:$primary;">Supporting information</mark>

The following resources support this credit:

* AIRAH – [Refrigerant Handling Code of Practice – Part 1: Self-contained low charge systems](https://airah.org.au/Common/Uploaded%20files/Resources/AIR018%20Refrigerant%20Handling%20Codes%20of%20Practice%202024_Part%201_Web_FINAL.pdf)
* AIRAH – [Refrigerant Handling Code of Practice – Part 2: Systems other than self-contained low charge systems](https://airah.org.au/Common/Uploaded%20files/Resources/AIR018%20Refrigerant%20Handling%20Codes%20of%20Practice%202024_Part%202_Web_FINAL.pdf)
* AIRAH – [Resilience Checklist](https://airah.org.au/Common/Uploaded%20files/Archive/Resources/2021_AIRAH_Resilience_Checklist.pdf)
* AS/NZS 5149 series – Refrigerating systems and heat pumps - Safety and environmental requirements
* Department of Climate Change, Energy, the Environment and Water (DCCEEW) – [Hydrofluorocarbon (HFC) phase-down](https://www.dcceew.gov.au/environment/protection/ozone/hfc-phase-down/hfc-phase-down-faqs)
* DCCEEW – [Cold Hard Facts 4](https://www.dcceew.gov.au/environment/protection/ozone/publications/cold-hard-facts-4)
* GBCA – Freeze Frame
* GBCA - Climate positive buildings and our net zero ambitions
* Introba - Refrigerants & Environmental Impacts: A Best Practice Guide
* Refrigerants Australia – [Refrigerant leak study – A data-driven insight from Australia 2024](https://www.refrigerantsaustralia.org/images/resources/Refrigerant%20Leak%20Study%20V2.0.pdf)

[^1]: **18/11/2026:**\
    Ad-hoc: Updated from *Inventory* to *Register*

[^2]: **26/10/2026:**\
    Ad-hoc: Updated from *Inventory* to *Register*

[^3]: 26/10/2026:\
    Changed from *Inventory* to *Register*


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/26-or-refrigerant-systems-impacts.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.