> For the complete documentation index, see [llms.txt](https://greenstarresources.gbca.au/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide.md).

# Water Use calculation guide

Guidance on calculation methods for the [*Water Use*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/29-or-water-use.md) credit in Green Star Buildings.

{% hint style="warning" %}
**Release 1 - 31/08/2026**&#x20;

* Initial release for Green Star Buildings. This guidance has been adapted from the *Potable Water Calculator Guide for Green Star – Design & As Built*.

[#version-control](#version-control "mention")
{% endhint %}

<table data-search="false"><thead><tr><th width="735.25">Section</th></tr></thead><tbody><tr><td><a href="#introduction"><strong>Introduction</strong></a></td></tr><tr><td><a href="#about-this-guide">About this guide</a></td></tr><tr><td><a href="#how-to-use-this-document">How to use this document</a></td></tr><tr><td><a href="#feedback">Feedback</a></td></tr><tr><td><a href="#definitions"><strong>Definitions</strong></a></td></tr><tr><td><a href="#using-the-water-use-calculator"><strong>Using the Water Use calculator</strong></a></td></tr><tr><td><a href="#reducing-water-use">Reducing Water Use</a></td></tr><tr><td><a href="#sanitary-fixture-and-appliance-efficiency">Sanitary Fixture and Appliance Efficiency</a></td></tr><tr><td><a href="#recycled-water-infrastructure">Recycled Water Infrastructure</a></td></tr><tr><td><a href="#mixed-use-projects">Mixed Use projects</a></td></tr><tr><td><a href="#calculating-reductions-in-water-use"><strong>Calculating reductions in water use</strong></a></td></tr><tr><td><a href="#scope">Scope</a></td></tr><tr><td><a href="#demonstrating-reductions-in-the-proposed-building">Demonstrating reductions in the <em>Proposed Building</em></a></td></tr><tr><td><a href="#reclaimed-water">Reclaimed Water</a></td></tr><tr><td><a href="#references"><strong>References</strong></a></td></tr><tr><td><strong>Appendix</strong></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md">Appendix A: Calculator data entry requirements</a></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-b.-calculation-methodologies.md">Appendix B: Calculation methodologies</a></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-c.-point-potential-evapotranspiration-example.md">Appendix C: Point potential evapotranspiration example</a></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-d.-bom-10-year-average-rainfall-data.md">Appendix D: BoM 10-year average rainfall data</a></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-e.-standard-occupancy-profiles.md">Appendix E: Standard occupancy profiles</a></td></tr><tr><td><a href="https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-f.-crop-coefficient.md">Appendix F: Crop coefficient (Kc)</a></td></tr></tbody></table>

## <mark style="color:$primary;">Introduction</mark>

### About this guide

This document sets out the basis on which a project's water use modelling is to be completed for all Green Star Buildings v1 and v1.1 projects targeting the [*Water Use*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/29-or-water-use.md) credit. This guide:

* Outlines the process for targeting various criteria within the Water Use credit using the *Water Use calculator*.
* Outlines the scope of inclusions and exclusions in calculating a project's water use.
* Provides guidance on demonstrating reductions in potable water use and what is considered standard practice for the *Reference building*.
* Provides information on the data inputs and calculation methodology for the *Water Use calculator*.

This guide applies to version 1 and version 1.1 of Green Star Buildings. This guide is not applicable to projects targeting Green Star – Design & As Built. These projects should refer to the *Potable Water calculation guide*.

### How to use this document

#### Water Use credit

The methodology in this guide is applied when targeting the Water Use credit in Green Star Buildings. This guide applies to the following criteria within the Water Use credit:

* [*Sanitary Fixture and Appliance Efficiency*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.0.1-sanitary-fixture-and-appliance-efficiency) in *Minimum Expectation*.
* *Reducing Water Use* in [*Minimum Expectation*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.0.2-reducing-water-use), [*Credit Achievement*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.1.1-reducing-water-use), and [*Exceptional Performance*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.2.1-reducing-water-use).
* [*Recycled Water Infrastructure*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.1.2-recycled-water-infrastructure) in *Credit Achievement*.

A summary of how each criterion is to be targeted using the *Water Use calculator* is provided in the [Using the Water Use calculator](#using-the-water-use-calculator) section of this document.

#### Water Use calculator methodology

The *Water Use calculator* is to be used when targeting all criteria under the Water Use credit. This includes estimating a building's potable water use in comparison to a *Reference building*. The results from the calculator are used to demonstrate compliance with the *Reducing Water Use* criteria by determining the performance level targeted and points based on the building's reduction in water use.

Detailed explanations of the calculator inputs and calculation methodology are included in [Appendix A: Calculator data entry requirements](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md) and [Appendix B: Calculation methodologies](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-b.-calculation-methodologies.md).

#### Interdependence with other Green Star credits

**Energy Use**

The usage profile and properties of the water-based systems in the building must be consistent in both the Water Use and [*Energy Use*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/categories-and-credits/positive-3/23-or-energy-use.md) credit. This includes for both the *Reference* and *Proposed building* for each credit. Water-based systems may include domestic hot water, heat rejection, evaporative cooling and/or chilled water systems.

Domestic hot water usage for the *Reference* and *Proposed buildings* in the *Energy Use calculator* must be based on the calculations completed in the *Water Use calculator*.

Heat rejection water consumption for the *Proposed building* is calculated by the *Water Use calculator* based on monthly total heat rejection values. Please refer to the [Heat rejection](#heat-rejection) section of this document for guidance.

Where direct or indirect evaporative cooling systems are used in the *Proposed building* in the *Energy Use calculator*, the associated water consumption must be calculated as part of the energy performance simulation and the total entered into the *Water Use calculator*.

**Operations Resilience**

Critical infrastructure including water infrastructure, water security, and access to drinkable water must be considered for the purpose of the [*Operations Resilience Assessment*](https://greenstarresources.gbca.au/pages/7SPEovYns0R4myhhpeP1#id-18.1.1-operations-resilience-assessment) and [*Power Loss for Shelter in Place*](https://greenstarresources.gbca.au/pages/7SPEovYns0R4myhhpeP1#id-18.1.3-power-loss-for-shelter-in-place) when targeting the Operations Resilience credit.

#### Applicability to Green Star projects

Projects registered under Green Star Buildings v1 may use one of the following:

* The *Potable Water calculator for Green Star – Design & As Built v1.3* and the *Potable Water calculation guide*, or
* The *Water Use calculator for Green Star Buildings* and this guide.

Projects cannot use the Potable Water calculator and this guide and vice versa.

Green Star Buildings v1 projects will be able to target the benchmarks from Green Star Buildings v1.1 if using the *Water Use calculator* however stepped points is not available. Please refer to *Guidance on credit substitution - Using Green Star Buildings v1.1 in Green Star Buildings v1* for further guidance.

Projects registered under Green Star Buildings v1.1 must use the *Water Use calculator* and this guide.

Projects that use the *Water Use calculator* must use the version of the guide current at the time of registration or may choose to use a newer version at their discretion if available. Projects must use the selected version in its entirety.

The *Reference building* requirements should not change substantially between versions of this guide, however if you believe your project has been substantially affected by changes, please submit a Technical Question.

### Feedback

GBCA welcomes any feedback on the guidance provided. Feedback can be lodged as a feedback request in the Green Star Manager.

## <mark style="color:$primary;">Definitions</mark>

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#blackwater)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#greywater)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#proposed-building)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#rainwater)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#reclaimed-water)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#recycled-water)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#reference-building)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#stormwater)

[Glossary](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/all-definitions.md#water-efficiency-labelling-and-standards-wels-scheme)

## <mark style="color:$primary;">Using the Water Use calculator</mark>

The *Water Use calculator* is to be used when targeting all criteria under the *Water Use* credit. The methodology for targeting each criterion is summarised below.

### Criteria included

#### Reducing Water Use

The *Water Use calculator* is required to target the *Reducing Water Use* criteria in [*Minimum Expectation*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.0.2-reducing-water-use), [*Credit Achievement*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.1.1-reducing-water-use), and [*Exceptional Performance*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.2.1-reducing-water-use). These criteria are performance-based and are targeted by:

* Nominating 'Reducing Water Use' in the 'Criterion selection' section within the 'Building information' tab.
* Completing all inputs in the 'Building information' tab.
* Completing all relevant inputs in tabs 1. through 10.
* Completing the 'Summary' section within the 'Results' tab.

Inputs are to be entered in line with the guidance in the Calculating reductions in water use section of this document. All claims made in the *Water Use calculator* and Submission Templates must be supported by evidence in the submission.

#### Sanitary Fixture and Appliance Efficiency

If the project is targeting the [*Sanitary Fixture and Appliance Efficiency*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.0.1-sanitary-fixture-and-appliance-efficiency) criterion to in *Minimum Expectation*, the 'Sanitary Fixture & Appliance' tab must be completed. This criterion is prescriptive and is targeted by:

* Nominating 'Sanitary Fixture and Appliance Efficiency' in the 'Criterion selection' section within the 'Building information' tab.
* Completing all inputs in the 'Sanitary Fixture & Appliance' tab.

Projects must enter 'Yes', 'No', or 'None installed' against each requirement in the 'Sanitary Fixture & Appliance' tab. All claims made in the *Water Use calculator* and Submission Templates must be supported by evidence in the submission. It is noted that projects targeting *Credit Achievement* and *Exceptional Performance* must also complete the remaining tabs to target the *Reducing Water Use* criteria.

#### Recycled Water Infrastructure

Projects targeting *Credit Achievement* must target the [*Recycled Water Infrastructure*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.1.2-recycled-water-infrastructure) criterion. This criterion is prescriptive and is targeted by completing all inputs in the 'Recycled Water Infrastructure' tab.

Projects must enter 'Yes' or 'No' against each requirement in the 'Recycled Water Infrastructure' tab. All claims made in the *Water Use calculator* and Submission Templates must be supported by evidence in the submission.

### Mixed use projects

#### Targeting criteria in Minimum Expectation

All building class types must demonstrate compliance with the Water Use credit requirements. Different criteria may be used in different class types (i.e. Class 2 spaces may demonstrate compliance with *Reducing Water Use* while a Class 6 retail space in the same building may demonstrate compliance with [*Sanitary Fixture and Appliance Efficiency*](https://greenstarresources.gbca.au/pages/begDGgl5HVHAMw2Qsx0u#id-29.0.1-sanitary-fixture-and-appliance-efficiency)).

#### Targeting criteria in Credit Achievement and Exceptional Performance

Where more than 20% of the GFA, excluding car parks, is not the predominant building class, multiple pathways may be required to demonstrate compliance (i.e. a building with both Class 2 and 6 spaces would be required to comply with different benchmarks) provided at least 80% of the GFA and the largest building classes by area are included. Points can only be awarded to the level where both pathways meet the requirements for (i.e. a building where the Class 2 spaces demonstrate a 30% and the class 6 spaces demonstrate a 15% reduction will be deemed to comply with *Minimum Expectation*).

Where less than 20% of GFA, excluding car parks, is different building class to the majority of the building, it may be excluded.

#### Targeting the Reducing Water Use criteria across multiple class types

A single *Water Use calculator* may be provided where:

* All parts of the building fall under the 'Residential' building type. Where this is the case, the 'Residential' building type within the 'Building information' tab is to be selected, and water use is to be aggregated across the site.
* All parts of the building fall under the 'Non-residential' building type. Where this is the case, the 'Non-residential' building type within the 'Building information' tab is to be selected, and water use is to be aggregated across the site.

Refer to the Building type and location section in [Appendix A: Calculator data entry requirements](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md) for definitions on the 'Residential' and 'Non-Residential' building types.

Where the project does not meet the above requirements, a Technical Question must be submitted to the GBCA for review.

## <mark style="color:$primary;">Calculating reductions in water use</mark>

The guidance in this section applies to the *Reducing Water Use* criteria in the *Water Use* credit whereby projects are to demonstrate a reduction in water consumption on a *Reference building*.

### Scope

The scope of water use is aligned in both the *Reference* and *Proposed building*. The following uses must be included in the assessment of the building's water use, as a minimum:

* All sanitation fixtures and fittings including toilets, urinals, indoor taps, showers, and other fixtures and fittings.
* All domestic and commercial washing machines and dishwashers.
* All heat rejection systems including but not limited to conventional cooling towers, evaporative condensers and fluid coolers, and hybrid or adiabatic systems. If air-cooled and no water is used, this should be indicated by the project team in the calculator.
* Water used for washdown purposes.
* All landscaping zones, regardless of whether they are irrigated or not, and irrigation systems. Xeriscape gardens are included. Landscaping zones that are not irrigated are to be assumed to be hand watered.
* All swimming pools and related systems.
* All water from systems used during fire protection testing, including but not limited to sprinklers, hose reels and hydrant systems.
* All water used in process cooling.
* Any use of reclaimed water from greywater, blackwater, rainwater, stormwater or an off-site non-potable water supply.

The following can be excluded from the scope:

* Fixtures where the water consumption will not be altered significantly by reducing the water flow due to functional purposes including:

  * Bath taps, laboratory taps, and taps dedicated to cleaning and facility management for container filling e.g., cleaning buckets.
  * Kitchen or café tapware, where the primary use is for pot fill and container filling.
  * Kitchen or café chilled, boiling and sparkling tapware which are used to fill cups.
  * Taps provided for connection to a laundry machine.

  Laundry taps for general use in residential buildings must be included in the credit scope, as occupants in residential buildings are not limited to using the laundry taps for cleaning.

### Demonstrating reductions in the Proposed building

The *Proposed building* potable water use is calculated by providing inputs for the fixtures, fittings and systems as identified in the [Scope](#scope) section above. In most cases, these inputs are related to the properties of the installed fixtures, fittings or systems and use.

For further details on what is required for each input in the *Water Use calculator*, refer to [Appendix A: Calculator data entry requirements](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md).

Therefore, project teams can demonstrate reductions in potable water use in the *Proposed building* in two ways:

* Demonstrating the installation of fixtures, fittings and systems that are more water efficient than the *Reference building*.
* Using reclaimed water.

### Reference building assumptions

The fixtures, fittings and systems included in the *Reference building* aligns with the *Proposed building* however standard practice water efficiency is assumed. The assumptions made for what is considered standard practice for each water use in the *Reference building* are outlined below.

#### Sanitation

The water efficiency of fixtures and fittings used to determine the total standard practice water consumption is presented in *Table 1*. These values have been taken from a combination of the minimum allowable WELS ratings under *AS 6400:2016 Water efficient products—Rating and labelling*, and the GBCA's recommendations for the baseline performance of these appliances within the rating tool.

*Table 1: Standard practice water efficiency - Sanitation*

| Fixtures and fittings                | Standard practice water efficiency rating | Standard practice flow rate |
| ------------------------------------ | ----------------------------------------- | --------------------------- |
| Toilet                               | 3 Star                                    | 4 L/flush                   |
| Urinals                              | 3 Star                                    | 2 L/flush                   |
| Taps                                 | 4 Star                                    | 7.5 L/min                   |
| Showers (Class 3: hotels)            | 2 Star                                    | 12 L/min                    |
| Showers (All other building classes) | 3 Star                                    | 9 L/min                     |

The *Reference building* shower demand by occupants should align with the *Proposed building*. The following are to be assumed:

* For residential projects, this should be 100% for both the *Reference* and *Proposed building*.
* For non-residential projects, this should align with assumptions in the *Movement and Place* credit. This includes the number of showers required in the [*Changing Facilities*](https://greenstarresources.gbca.au/pages/7isN5iK0Tx6oKSfrNuxt#id-30.0.1-changing-facilities) criterion in *Minimum Expectation* and/or the mode share corresponding to cyclists in the project's Sustainable Transport Plan in the [*Sustainable Transport*](https://greenstarresources.gbca.au/pages/7isN5iK0Tx6oKSfrNuxt#id-30.1.1-sustainable-transport) criterion in the *Credit Achievement*. The same value for both the *Reference* and *Proposed building* into the *Water Use calculator* should be used.

Where there are water consumption loads not able to be captured in the designated tables (such as for public buildings where there are water consumption loads associated with public water use), the 'Other fixtures water use' table can be completed. The *Reference building* water use per year for these fixtures is to be modelled separately and included in the calculator. A summary of the modelling, assumptions and results are included in the project's submission.

#### Whitegoods

The water efficiency of whitegoods used to determine the total standard practice water consumption is presented in *Table 2*. These values have been taken from a combination of the minimum allowable WELS ratings under *AS 6400:2016 Water efficient products—Rating and labelling*, and the GBCA's recommendations for the baseline performance of these appliances within the rating tool.

*Table 2: Standard practice water efficiency - Whitegoods*

| Fixtures and fittings            | Standard practice water efficiency rating | Standard practice flow rate |
| -------------------------------- | ----------------------------------------- | --------------------------- |
| Washing machine (capacity >=5kg) | 3 Star                                    | 14.7 L/kg                   |
| Washing machine (capacity <5kg)  | 2.5 Star                                  | 17.6 L/kg                   |
| Dishwasher                       | 3.5 Star                                  | Variable                    |

The baseline for both the clothes washing machine and dishwasher will scale based on the capacity of the machine entered by the project team. In the case of the clothes washing machine, this is related to the weight of clothing that can be accommodated per cycle. For dishwashers, the baseline is linked to the number of place settings that the machine can accommodate in one cycle.

#### Heat rejection

The standard practice water efficiency is as per *Table 3*, *Table 4* and *Table 5* below.

The inputs in *Table 3* are based on the *Reference building* HVAC system types as specified in [*Table 40: Reference building HVAC system types by space usage type*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide/appendix-d.-supplementary-building-and-systems.md#reference-building-hvac-systems) in *Appendix D. Supplementary building and systems - definitions and calculation methods* within the [*Energy Use calculation guide v1.1*.](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/energy-use-calculation-guide.md) The selected *Reference building* and system type must be consistent with inputs to the *Energy Use calculator*.

For projects targeting Green Star Buildings v1, where the [*Energy Use calculation guide v1*](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/energy-use-calculation-guide.md) specifies a [Reference HVAC system](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.0-rev-c/calculation-guides/energy-use-calculation-guide.md#supplementary-building-and-systems-definitions-and-calculation-methods) that is a different type to *Table 3*, projects should select 'Other (custom value)' for the Reference building type and choose the applicable HVAC system type instead.

*Table 3: Assumed Reference building HVAC systems by space usage type. These are based on Table 40 within the Energy Use calculation guide v1.1.*

<table data-header-hidden data-search="false"><thead><tr><th></th><th></th><th></th><th></th></tr></thead><tbody><tr><td><strong>Reference building type</strong></td><td><strong>Climate zone</strong></td><td><strong>System type as per </strong><em><strong>Energy Use calculation guide Table 40</strong></em></td><td><strong>Assumed HVAC system</strong></td></tr><tr><td>Residential</td><td>All climate zones</td><td>System types 1, 2a, or 2b</td><td>Air-cooled (no water)</td></tr><tr><td>Industrial - warehouses</td><td>All climate zones</td><td>System type 3</td><td>Air-cooled (no water)</td></tr><tr><td>Other non-office and non-retail buildings</td><td>All climate zones</td><td>System types 4a, 10a, 10b, or 10c</td><td>Air-cooled (no water)</td></tr><tr><td>Office up to 20,000m² NLA</td><td>All climate zones</td><td>System types 4a, 7a, or 7b</td><td>Air-cooled (no water)</td></tr><tr><td>Office greater than 20,000m² NLA</td><td>All climate zones</td><td>System types 7d or 7e</td><td><mark style="background-color:$success;">Water-cooled (evaporative)</mark></td></tr><tr><td>Retail - street facing</td><td>All climate zones</td><td>System type 1</td><td>Air-cooled (no water)</td></tr><tr><td>Retail with enclosed area up to 20,000m² GLA</td><td>All climate zones</td><td>System types 8a, 8b, or 8c</td><td>Air-cooled (no water)</td></tr><tr><td>Retail with enclosed area greater than 20,000m² GLA</td><td>Climate zones 1-7</td><td>System types 8d or 8e</td><td><mark style="background-color:$success;">Water-cooled (evaporative)</mark></td></tr><tr><td></td><td>Climate zone 8</td><td>System type 8f</td><td>Air-cooled (no water)</td></tr><tr><td>Residential aged care</td><td>All climate zones</td><td>System type 4b</td><td>Air-cooled (no water)</td></tr><tr><td>Hotels (&#x3C;100 guest rooms)</td><td>All climate zones</td><td>System type 4c</td><td>Air-cooled (no water)</td></tr><tr><td>Hotels (≥100 guest rooms)</td><td>Climate zones 1-7</td><td>System types 9a and 9b</td><td><mark style="background-color:$success;">Water-cooled (evaporative)</mark></td></tr><tr><td></td><td>Climate zone 8</td><td>System type 9c</td><td>Air-cooled (no water)</td></tr></tbody></table>

*Table 4: Deemed duty fraction for Reference building assumed HVAC systems*

| Assumed HVAC system        | Evaporative duty fraction ($f\_{duty}$) (%) |
| -------------------------- | ------------------------------------------- |
| Water-cooled (evaporative) | 1.0                                         |
| Air-cooled (no water)      | 0                                           |

*Table 5: Standard practice water efficiency variables for drift and bleed*

| Variable                                       | Standard practice value                                                                           |
| ---------------------------------------------- | ------------------------------------------------------------------------------------------------- |
| Condenser water Δt (°C)                        | 5.5°C                                                                                             |
| Drift coefficient (%)                          | 0.002% as required in *AS/NZS 3666.1 Clause 4.4*                                                  |
| Cycles of concentration in cooling tower water | 6 cycles of concentration in alignment with previous Green Star versions' compliance requirements |

#### Washdown

A set flow rate of 12L/min is assumed for the *Reference building*. All other parameters are assumed to align with the *Proposed building*.

#### Landscape irrigation

The standard practice water efficiency is based on the following:

*Table 6: Standard practice water efficiency – Landscape irrigation*

| Monthly 'point potential' evapotranspiration  | Standard practice value     |
| --------------------------------------------- | --------------------------- |
| Monthly Rainfall                              | As per *Proposed building*  |
| Total landscaped area of the zone             | As per *Proposed building*  |
| Percentage of zone undercover                 | As per *Proposed building*  |
| Weighted average crop coefficient in the zone | 0.6                         |
| Application Efficiency of irrigation system   | 75% (night time sprinklers) |

#### Swimming pools

The standard practice water efficiency for swimming pools has been taken from the ACT Planning and Land Authority (ACTPLA) design and siting requirements for water efficiency to establish a calculation methodology for the *Reference building* swimming pool water consumption. This methodology applies to outdoor pools and the ACTPLA requirements included in the *Reference building* are:

* The use of a swimming pool cover (for outdoor pools); and
* An annual backwash (filter cleaning) consumption based on 5 flushes per year at 250 litres per flush.

For indoor pools, the methodology regarding backwash has been retained, however as evaporation is driven by indoor climatic conditions, the methodology applied to calculate evaporation has been adapted from the cooling tower evaporation methodology to determine the water lost through the discharge of pool hall exhaust. In order to determine a benchmark water loss through evaporation of indoor swimming pools, the minimum exhaust requirements of *AS 1668.2* are used to define a benchmark for discharge of moist air (which carries evaporated swimming pool water) from the pool hall.

The constants used to determine the standard practice water efficiency are summarised in *Table 7*.

*Table 7: Standard practice water efficiency – Swimming pools*

<table data-search="false"><thead><tr><th width="567">Constant</th><th>Standard practice value</th></tr></thead><tbody><tr><td>Water consumption for filter cleaning (backwash) (L/clean) ($Demand_{filter}$)</td><td>250</td></tr><tr><td>Filter cleaning frequency (cleans/year) ($Frequency$)</td><td>5</td></tr><tr><td>Evaporation coefficient ($K_{C,pool}$)</td><td>0.7</td></tr><tr><td>Relative humidity (%)¹</td><td>100</td></tr><tr><td>Water vapour molar mass (kg/kmol)</td><td>18.02</td></tr><tr><td>Dry air molar mass (kg/kmol)</td><td>28.97</td></tr><tr><td>Ideal gas constant for air (kJ/kg.K)</td><td>0.287</td></tr></tbody></table>

{% hint style="info" %}
**Note 1:** For the purposes of calculating the evaporation losses from the indoor swimming pool, the assumption is made that the swimming pool hall is as close to 100% relative humidity as practically possible for both the *Reference* and *Proposed building*. This assumption allows the calculation to be based solely on the dry-bulb temperature of the pool hall air that is exhausted and combine this with the empirical moist air data (tabulated in the 1997 ASHRAE handbook, chapter 6, 'Psychrometrics') to determine the exhaust air moisture content.
{% endhint %}

Projects that target the aquatic centre classification will be required to model and provide the monthly water consumption of the *Reference* and *Proposed building*. To use this classification, a Technical Question must be submitted to the GBCA to review the modelling assumptions and methodology used. A project cannot be classified to have both swimming pools and be an aquatic centre for the purposes of the calculator.

#### Fire protection systems

The proportion of water captured per test is assumed to be 80% for the *Reference building*. All other parameters are assumed to align with the *Proposed building*.

#### Process cooling

The *Reference building* assumes that all equipment requiring process cooling is served by an open loop system, supplied with 95% non-potable water.

### Reclaimed water

The *Reference building* does not include any water re-use systems therefore any use of reclaimed water in the *Proposed building* will be an improvement over standard practice.

The following reclaimed water sources may contribute to reducing the *Proposed building's* potable water use:

* Greywater
* Blackwater
* Rainwater
* Stormwater
* Off-site reclaimed water
* Shared rainwater, greywater or blackwater systems

To include the use of reclaimed water, refer to the Reclaimed water section in [Appendix A: Calculator data entry requirements](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md).

#### Sitewide water systems

Where reclaimed water systems are sitewide or shared, project teams are to declare any other uses of the project's on-site reclaimed water sources. This may include where there a specific uses not already included in the calculator that use the building's reclaimed water systems or where this is a centralised reclaimed water source that the project shares with multiple buildings.

Projects that have multiple buildings sharing a centralised reclaimed water source can only claim the use of this water source if the project is approved for a Multiple Building Single Rating (MBSR) Approach, Site-Wide Credits Approach or has an approved Technical Question from the GBCA. Please refer to the *Multiple Building Single Rating (MBSR) Support Document for Green Star Buildings* and *Site-Wide Credits Approach Support Document for Green Star Buildings* available via the Green Star resources portal for guidance on the above approaches.

Refer to the Sitewide water systems section in [Appendix A: Calculator data entry requirements](https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide/appendix-a.-calculator-data-entry-requirements.md) for further details on how this should be reflected in the *Water Use calculator*.

## <mark style="color:$primary;">References</mark>

Allen, R G. Pereira, L S, Raes D, Smith, M (1998) Crop evapotranspiration - Guidelines for computing crop water requirements - FAO Irrigation and drainage paper 56, Food and Agriculture Organization of the United Nations

Parsons, R A (ed.), (1997) 1997 ASHRAE fundamentals handbook

AS 3666.1:2011 Air-handling and water systems of buildings—Microbial control

AS 4180.1:2008 Measurement of drift loss from cooling towers

AS 6400:2016 Water efficient products—Rating and labelling

ACT planning and land authority (ACTPLA) design and siting requirements for water efficiency

Standards Australia,(2008) HB 230—2008 Rainwater Tank Design and Installation Handbook

British Standards Institution, (2009) BS 8515:2009 Rainwater harvesting systems – Code of practice

Aherne, V J (2009) AIRAH Best Practice Guidelines: Water conservation in cooling towers, AIRAH/State Government Victoria

AIRAH (2007) AIRAH technical handbook

AIRAH DA17 (2025): Cooling Towers

United Nations Environment Programme (2006) Electrical Energy Equipment: Cooling Towers

Green Building Council of Australia(Various dates), Green Star technical Manuals (Education v1, Healthcare v1, Office v3, Public Building v1, Industrial v1, Multi-unit Residential v1)

### <mark style="color:$primary;">Version Control</mark>

<table><thead><tr><th width="132">Revision/release/version</th><th width="130">Date</th><th>Descriptions</th></tr></thead><tbody><tr><td>1</td><td>31/08/2026</td><td>Initial release for Green Star Buildings. This guidance has been adapted from the Potable Water Calculator Guide for Green Star – Design &#x26; As Built.</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://greenstarresources.gbca.au/greenstarresources.gbca.au_ratingtools/current-green-star-rating-tools/green-star-buildings/v1.1/calculation-guides/water-use-calculation-guide.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.